TIA-568-C.3-1

December 2011

Optical Fiber Cabling Components

Standard – Addendum 1, Addition of OM4

Cabled Optical Fiber and Array

Connectivity

ANSI/TIA-568-C.3-1-2011 APPROVED: OCTOBER 13, 2011

(2)

NOTICE

TIA Engineering Standards and Publications are designed to serve the public interest through

eliminating misunderstandings between manufacturers and purchasers, facilitating interchangeability

and improvement of products, and assisting the purchaser in selecting and obtaining with minimum

delay the proper product for their particular need. The existence of such Standards and Publications

shall not in any respect preclude any member or non-member of TIA from manufacturing or selling

products not conforming to such Standards and Publications. Neither shall the existence of such

Standards and Publications preclude their voluntary use by Non-TIA members, either domestically or

internationally.

Standards and Publications are adopted by TIA in accordance with the American National Standards

Institute (ANSI) patent policy. By such action, TIA does not assume any liability to any patent owner,

nor does it assume any obligation whatever to parties adopting the Standard or Publication.

This Standard does not purport to address all safety problems associated with its use or all applicable

regulatory requirements. It is the responsibility of the user of this Standard to establish appropriate

safety and health practices and to determine the applicability of regulatory limitations before its use.

(From Standards Proposal No. ANSI/TIA-PN-568-C.3-1, formulated under the cognizance of the TIA

TR-42 Telecommunications Cabling Systems, TR-42.11 Subcommittee on Optical Systems).

Published by

TELECOMMUNICATIONS INDUSTRY ASSOCIATION

Standards and Technology Department

2500 Wilson Boulevard

Arlington, VA 22201 U.S.A.

PRICE: Please refer to current Catalog of

TIA TELECOMMUNICATIONS INDUSTRY ASSOCIATION STANDARDS

AND ENGINEERING PUBLICATIONS

or call IHS, USA and Canada

(1-877-413-5187) International (303-397-2896)

or search online at

http://www.tiaonline.org/standards/catalog/

All rights reserved

(3)

NOTICE OF COPYRIGHT

This document is copyrighted by the TIA.

Reproduction of these documents either in hard copy or soft copy (including posting on the

web) is prohibited without copyright permission. For copyright permission to reproduce portions

of this document, please contact the TIA Standards Department or go to the TIA website

(

www.tiaonline.org

) for details on how to request permission. Details are located at:

http://www.tiaonline.org/standards/catalog/info.cfm#copyright

or

Telecommunications Industry Association

Technology & Standards Department

2500 Wilson Boulevard, Suite 300

Arlington, VA 22201 USA

+1.703.907.7700

Organizations may obtain permission to reproduce a limited number of copies by entering into a

license agreement. For information, contact

IHS

15 Inverness Way East

Englewood, CO 80112-5704

or call

USA and Canada (1.800.525.7052)

International (303.790.0600)

(4)
(5)

NOTICE OF DISCLAIMER AND LIMITATION OF LIABILITY

The document to which this Notice is affixed (the “Document”) has been prepared by one or more Engineering Committees or Formulating Groups of the Telecommunications Industry Association (“TIA”). TIA is not the author of the Document contents, but publishes and claims copyright to the Document pursuant to licenses and permission granted by the authors of the contents.

TIA Engineering Committees and Formulating Groups are expected to conduct their affairs in accordance with the TIA Engineering Manual (“Manual”), the current and predecessor versions of which are available at http://www.tiaonline.org/standards/procedures/manuals/TIA’s function is to administer the process, but not the content, of document preparation in accordance with the Manual and, when appropriate, the policies and procedures of the American National Standards Institute (“ANSI”). TIA does not evaluate, test, verify or investigate the information, accuracy, soundness, or credibility of the contents of the Document. In publishing the Document, TIA disclaims any undertaking to perform any duty owed to or for anyone.

If the Document is identified or marked as a project number (PN) document, or as a standards proposal (SP) document, persons or parties reading or in any way interested in the Document are cautioned that: (a) the Document is a proposal; (b) there is no assurance that the Document will be approved by any Committee of TIA or any other body in its present or any other form; (c) the Document may be amended, modified or changed in the standards development or any editing process.

The use or practice of contents of this Document may involve the use of intellectual property rights (“IPR”), including pending or issued patents, or copyrights, owned by one or more parties. TIA makes no search or investigation for IPR. When IPR consisting of patents and published pending patent applications are claimed and called to TIA’s attention, a statement from the holder thereof is requested, all in accordance with the Manual. TIA takes no position with reference to, and disclaims any obligation to investigate or inquire into, the scope or validity of any claims of IPR. TIA will neither be a party to discussions of any licensing terms or conditions, which are instead left to the parties involved, nor will TIA opine or judge whether proposed licensing terms or conditions are reasonable or non-discriminatory. TIA does not warrant or represent that procedures or practices suggested or provided in the Manual have been complied with as respects the Document or its contents.

If the Document contains one or more Normative References to a document published by another organization (“other SSO”) engaged in the formulation, development or publication of standards (whether designated as a standard, specification, recommendation or otherwise), whether such reference consists of mandatory, alternate or optional elements (as defined in the TIA Engineering Manual, 4th edition) then (i) TIA disclaims any duty or obligation to search or investigate the records of any other SSO for IPR or letters of assurance relating to any such Normative Reference; (ii) TIA’s policy of encouragement of voluntary disclosure (see Engineering Manual Section 6.5.1) of Essential Patent(s) and published pending patent applications shall apply; and (iii) Information as to claims of IPR in the records or publications of the other SSO shall not constitute identification to TIA of a claim of Essential Patent(s) or published pending patent applications.

TIA does not enforce or monitor compliance with the contents of the Document. TIA does not certify, inspect, test or otherwise investigate products, designs or services or any claims of compliance with the contents of the Document. ALL WARRANTIES, EXPRESS OR IMPLIED, ARE DISCLAIMED, INCLUDING WITHOUT LIMITATION, ANY AND ALL WARRANTIES CONCERNING THE ACCURACY OF THE CONTENTS, ITS FITNESS OR APPROPRIATENESS FOR A PARTICULAR PURPOSE OR USE, ITS MERCHANTABILITY AND ITS NONINFRINGEMENT OF ANY THIRD PARTY’S INTELLECTUAL PROPERTY RIGHTS. TIA EXPRESSLY DISCLAIMS ANY AND ALL RESPONSIBILITIES FOR THE ACCURACY OF THE CONTENTS AND MAKES NO REPRESENTATIONS OR WARRANTIES REGARDING THE CONTENT’S COMPLIANCE WITH ANY APPLICABLE STATUTE, RULE OR REGULATION, OR THE SAFETY OR HEALTH EFFECTS OF THE CONTENTS OR ANY PRODUCT OR SERVICE REFERRED TO IN THE DOCUMENT OR PRODUCED OR RENDERED TO COMPLY WITH THE CONTENTS.

TIA SHALL NOT BE LIABLE FOR ANY AND ALL DAMAGES, DIRECT OR INDIRECT, ARISING FROM OR RELATING TO ANY USE OF THE CONTENTS CONTAINED HEREIN, INCLUDING WITHOUT LIMITATION ANY AND ALL INDIRECT, SPECIAL, INCIDENTAL OR CONSEQUENTIAL DAMAGES (INCLUDING DAMAGES FOR LOSS OF BUSINESS, LOSS OF PROFITS, LITIGATION, OR THE LIKE), WHETHER BASED UPON BREACH OF CONTRACT, BREACH OF WARRANTY, TORT (INCLUDING NEGLIGENCE), PRODUCT LIABILITY OR OTHERWISE, EVEN IF ADVISED OF THE POSSIBILITY OF SUCH DAMAGES. THE FOREGOING NEGATION OF DAMAGES IS A FUNDAMENTAL ELEMENT OF THE USE OF THE CONTENTS HEREOF, AND THESE CONTENTS WOULD NOT BE PUBLISHED BY TIA WITHOUT SUCH LIMITATIONS.

(6)
(7)

ANSI/TIA-568-C.3-1

i Optical Fiber Cabling Components Standard – Addendum 1,

Addition of OM4 Cabled Optical Fiber and Array Connectivity Table of Contents

FOREWORD ... i 

1  SCOPE ... 1 

2  Normative references ... 1 

Table 1  Cable transmission performance ... 1 

6.4.3  Array ... 2 

FOREWORD

(This foreword is not considered part of this Standard.)

TIA standards documents are developed within the Technical Committees of the TIA and the standards coordinating committees of the TIA standards board. Members of the committees serve voluntarily and without commission. The companies that they represent are not necessarily members of the TIA. The standards developed within the TIA represent a consensus of the broad expertise on the subject. This expertise comes from within the TIA as well as those outside of the TIA that have an expressed interest. The viewpoint expressed at the time that this standard was approved was from the contributors’ experience and the state of the art at that time. Users are encouraged to verify that they have the latest revision of the standard.

This addendum has been prepared by the TR-42.11 Subcommittee and approved by the TR-42 Engineering Committee.

There are no annexes in this addendum.

Introduction

Deleted text is shown as strikethrough. New text is shown as underlined. Clause, figure and table numbering will require updating after subclause 6.4.3.2.6.

(8)
(9)

ANSI/TIA-568-C.3-1

1 1 SCOPE

This addendum updates ANSI/TIA-568-C.3 with the addition of 50/125 µm laser-optimized OM4 cabled optical fiber and components for array connectivity.

2 NORMATIVE REFERENCES

The following reference shall be added to clause 2, “Normative references” within the cable standards section.

TIA-492AAAD-2009, Detail Specification for 850-nm Laser-Optimized, 50 µm Core

Diameter/125 µm Cladding Diameter Class 1a Graded-Index Multimode Optical Fibers Suitable for Manufacturing OM4 Cabled Optical Fiber

The following references shall be shall be modified to clause 2, “Normative references” within the cable standards section.

• TIA-492AAAA-AB-20022009, Detail Specification for 62.5 μm Core Diameter/125 μm

Cladding Diameter Class Ia Graded-Index Multimode Optical Fibers

• TIA-492AAAB-A-20022009, Detail Specification for 50 μm Core Diameter/125 μm Cladding

Diameter Class Ia Multimode, Graded-Index Optical Waveguide Fibers

• TIA-492AAAC-AB-20032009, Detail Specification for 850-nm Laser-Optimized, 50-μm Core

Diameter/125-μm Cladding Diameter Class 1a Graded-Index Multimode Optical Fibers

TABLE 1 CABLE TRANSMISSION PERFORMANCE

Modify the title of table 1 as follows, “Optical fiber cable1 transmission performance parameters”. The first row of table 1 shall be modified as follows:

Optical fiber and cable type 2 Wavelength (nm) Maximum attenuation (dB/km) Minimum overfilled modal bandwidth-length product (MHz⋅km)12 Minimum effective modal bandwidth-length product (MHz⋅km)12

The following row shall be added to table 1 after the row specifying OM3.

850 nm Laser-Optimized 50/125 µm Multimode

TIA 492AAAD (OM4)

850 1300 3.5 1.5 3500 500 4700 Not Required

The second note of the “NOTES” of table 1, shall be changed to Note 1 and modified as follows:

2 1 - The fiber designations(OM1, OM2, OM3, OM4, OS1 and OS2) corresponds to the designationsof used

within ISO/IEC 11801 or ISO/IEC 24702.

(10)

ANSI/TIA-568-C.3-1

2 6.4.3 Array

Subclause 6.4.3, “Array” shall be modified as follows: 6.4.3 Array

6.4.3.1 General

Array system connectivity methods require a specific combination of components (array patch cord, optical fiber transitions, duplex patch cord) to maintain polarity. Some of the components are common to other connectivity methods such as duplex systems.

NOTES

1 - The array patch cords and array cables of shown in figures 7, 8 and 9through figure 12 are shown unpinned on both ends for simplicity. In some instances, such as when supporting parallel signals, it may be necessary to use a combination of unpinned and pinned connectors on array cables and array patch cords. At any connection using MPO connectors, it is necessary for one plug to be pinned and the other to be unpinned.

2 - See ANSI/TIA 568 C.0 for guidance on usage of polarity methods. 6.4.3.2 Array patch cords and array cables

The Array patch cords and array cables should be clearly identified. 6.4.3.2.1 Type-A:1-1 array patch cord and array cable

Type-A:1-1 array patch cords and array cables are used to provide connectivity between array interfaces in which the fibers are arranged in a single row. As shown in figure 7, a Type-A:1-1 array patch cord or array cable has a sequential number assigned to each fiber as follows:

a) On one end of the array patch cord or array cable, the fibers are fixed within the array connector in consecutive number (1,2,3,4…12) from left to right as viewed looking at the end-face of the array connector with the connector key up (see table 2).

b) On the other end of the array patch cord or array cable, the fibers are fixed within the array connector also in consecutive number (1,2,3,4…12) from left to right as viewed looking at the end-face of the array connector with the connector key up (see table 2).

Table 2 - Type-A:1-1 array patch cord and array cable fiber sequence Near /

Far End

Fiber Sequence sequence (viewing the array connector plug end-face

of the connector with key up)

Near 1 2 3 4 5 6 7 8 9 10 11 12

(11)

ANSI/TIA-568-C.3-1

3 Figure 7 - Type-A:1-1 array patch cord and array cable (key-up to key-down)

6.4.3.2.2 Type-A:2-1 array patch cord

Type-A:2-1 array patch cords are used to provide connectivity between an array interface in which the fibers are arranged in two rows within one array connector plug and two array interfaces in which the fibers are arranged in one row in each of two array connector plugs. As shown in figure 8, a

Type-A:2-1 array patch cord has a sequential number assigned to each fiber as follows:

a) On one end of the array patch cord, the fibers are fixed within in each of two rows of the array connector plug in consecutive number (1,2,3,4…12) from left to right as viewed looking at the end-face of the array connector plug with the key up (see table 3).

b) On the other ends of the array patch cord, the fibers are fixed within each array connector plug also in consecutive number (1,2,3,4…12) from left to right as viewed looking at the end-face of the array connector plug with the key up (see table 3).

Table 3 - Type-A:2-1 array patch cord fiber sequence

End Fiber sequence (viewing the array connector plug end-face with key

up) 2-row plug, top row 1 2 3 4 5 6 7 8 9 10 11 12 2-row plug, bottom row 1 2 3 4 5 6 7 8 9 10 11 12 1-row plugs 1 2 3 4 5 6 7 8 9 10 11 12

(12)

ANSI/TIA-568-C.3-1

4

Position 12 Top Row: Position 1

Bottom Row: Position 13

Position 1 Position 1

Position 12

Top Row: Position 12 Bottom Row: Position 24 Fibers, Top Row 1 2 3 4 5 6 7 8 9 10 11 12 Fibers, Bottom Row 1 2 3 4 5 6 7 8 9 10 11 12 Fibers, Both Plugs 1 2 3 4 5 6 7 8 9 10 11 12

Key up Key down

Figure 8 - Type-A:2-1 array patch cord (key-up to key-down)

6.4.3.2.3 Type-B:1-1 array patch cord and array cable

Type–B:1-1 array patch cords and array cables are used to provide connectivity between array interfaces in which the fibers are arranged in a single row. As shown in figure 89, a Type-B:1-1 array patch cord or array cable has a sequential number assigned to each fiber as follows:

a) On one end of the array patch cord or array cable, the fibers are fixed within the array connector plug in consecutive number (1,2,3,4…12) from left to right as viewed looking at the end-face of the array connector with the connector key up (see table 34).

b) On the other end of the array patch cord or array cable, the fibers are fixed within the array connector plug in reverse consecutive number (12,11,10,9…1) from left to right as viewed looking at the end-face of the array connector with the connector key up (see table 34).

Table 3 4 - Type-B:1-1 array patch cord and array cable fiber sequence Near /

Far End

Fiber Sequence sequence (viewing the array connector plug end-face

of the connector with key up)

Near 1 2 3 4 5 6 7 8 9 10 11 12

Far 12 11 10 9 8 7 6 5 4 3 2 1

(13)

ANSI/TIA-568-C.3-1

5

6.4.3.2.4 Type-B:2-1 array patch cord

Type-B:2-1 array patch cords are used to provide connectivity between an array interface in which the fibers are arranged in two rows within one array connector plug and two array interfaces in which the fibers are arranged in one row in each of two array connector plugs. As shown in figure 10, a Type-B:2-1 array patch cord has a sequential number assigned to each fiber as follows:

a) On one end of the array patch cord, the fibers are fixed within in each of two rows of the array connector plug in consecutive number (1,2,3,4…12) from left to right as viewed looking at the end-face of the array connector plug with the key up (see table 5).

b) On the other ends of the array patch cord, the fibers are fixed within each array connector plug in reverse consecutive number (12,11,10,9…1) from left to right as viewed looking at the end-face of the array connector plug with the key up (see table 5).

Table 5 - Type-B:2-1 array patch cord fiber sequence

End Fiber sequence (viewing the array connector plug end-face with key

up) 2-row plug, top row 1 2 3 4 5 6 7 8 9 10 11 12 2-row plug, bottom row 1 2 3 4 5 6 7 8 9 10 11 12 1-row plugs 12 11 10 9 8 7 6 5 4 3 2 1 PULL PUSH PULL PUSH PU LL PUSH PUSH PUSH

Figure 10 - Type-B:2-1 array patch cord (key-up to key-up)

6.4.3.2.36.4.3.2.5 Type-C:1-1 array patch cord and array cable

Type-C:1-1 array patch cords and array cables are used to provide connectivity between array interfaces in which the fiber are arranged in a single row. As shown in figure 911, Type-C:1-1 array patch cord or array cable has a sequential number assigned to each fiber as follows:

a) On one end of the array patch cord or array cable, the fibers are fixed within the array connector in consecutive number (1,2,3,4…12) from left to right as viewed looking at the end-face of the array connector with the connector key up (see table 46).

(14)

ANSI/TIA-568-C.3-1

6 b) On the other end of the array patch cord or array cable, the fibers are pair-wise flipped within

the array connector (2,1; 4,3; 6,5…12,11) from left to right as viewed looking at the end-face of the array connector with the connector key up (see table 46).

Table 4 6 - Type-C:1-1 array patch cord and array cable fiber sequence Near /

Far End

Fiber Sequence sequence (viewing the array connector plug end-face

of the connector with key up)

Near 1 2 3 4 5 6 7 8 9 10 11 12

Far 2 1 4 3 6 5 8 7 10 9 12 11

Figure 9 11 - Type-C:1-1 array patch cord and array cable (pair-wise flipped, up to key-down)

6.4.3.2.6 Type-C:2-1 array patch cord

Type-C:2-1 array patch cords are used to provide connectivity between an array interface in which the fibers are arranged in two rows within one array connector plug and two array interfaces in which the fibers are arranged in one row in each of two array connector plugs. As shown in figure 12, a Type-C:2-1 array patch cord has a sequential number assigned to each fiber as follows:

a) On one end of the array patch cord, the fibers are fixed within in each of two rows of the array connector plug in consecutive number (1,2,3,4…12) from left to right as viewed looking at the end-face of the array connector plug with the key up (see table 7).

b) On the other ends of the array patch cord, the fibers are fixed within each array connector plug in pair-wise flipped (2,1; 4,3; 6,5…12,11) from left to right as viewed looking at the end-face of the connector plug with the key up (see table 7).

Table 7 - Type-C:2-1 array patch cord fiber sequence

End Fiber sequence (viewing the array connector plug end-face with key

up) 2-row plug, top row 1 2 3 4 5 6 7 8 9 10 11 12 2-row plug, bottom row 1 2 3 4 5 6 7 8 9 10 11 12 1-row plugs 2 1 4 3 6 5 8 7 10 9 12 11

(15)

ANSI/TIA-568-C.3-1 7 PU LL PUSH PULL PU SH PULL PUSH PUSH PUSH

(16)
(17)
(18)

 

 

References

Related documents

$1000 and a complimentary letter to Mary Patten for her heroic work in bringing the fast sailing clipper ship safely around the dangerous Cape Horn?. When Mary and Captain

Political Parties approved by CNE to stand in at least some constituencies PLD – Partido de Liberdade e Desenvolvimento – Party of Freedom and Development ECOLOGISTA – MT –

Other ways that equality and diversity has been promoted in the college to raise awareness included College events to celebrate success and achievement such as Supported

Claims are subject to regular auditing by external Insurers and internal audit, Claimants are also advised that any complaints regarding the outcome of the claim or the handling of

In the previous sections, we dis- cuss the expectation that a neural network exploiting the fractional convolution should perform slightly worse than a pure binary (1-bit weights

The Department of Health, Physical Education, Recreation and Dance offers a Master of Science in Education in Health and Physical Education and a Master of Science in

• Taxpayers subject to the provisions of Title II of the Income Tax Law (ITL) which have declared taxable income of $644,599,005 or more in the immediately preceding tax

Most companies recruit for full-time and internship positions, but some indicate Co-Op as a recruiting priority, while not attending Professional Practice