• No results found

L2 V4 03 Datapoints Profiles E 01

N/A
N/A
Protected

Academic year: 2021

Share "L2 V4 03 Datapoints Profiles E 01"

Copied!
23
0
0

Loading.... (view fulltext now)

Full text

(1)

Datapoints Profiles

PCL

PCL

PCL

PCL

PACiS

PACiS

PACiS

PACiS Technical

Technical

Technical

Technical Training

Training

Training

Training Level

Level

Level

Level 2

2

2

2

CS&P

CS&P

CS&P

(2)

• Content

 Generalities

 Inputs Profiles

 Outputs Profiles

(3)

• Content

 Generalities

 Inputs Profiles

 Outputs Profiles

(4)

Supervision Profiles …

What are Supervision DataPoint?

xPS

MV

xCT

FSS, SBMC dependency

Few acquisition options

State labels

Archive&Logging / state

Interlock Boolean / state

Alarm / state

SPS,

SPS_Profile

DPS,

DPS_Profile

MPS,

MPS_Profile

MV,

MV_Profile

Counter, Counter_Profile

FOR

(5)

Control Profiles …

What are Control DataPoint?

xPC

SetPoint

DE / SBO

Few acquisition options

State labels

Archive&Logging on event

Interlock Boolean / state

Alarm on Negative Ack.

SPC,

SPC_Profile

DPC,

DPC_Profile

SetPoint, SetPoint_Profile

FOR

(6)

• Content

 Generalities

 Inputs Profiles

 Outputs Profiles

(7)

Single, Double, Multi Point Status : General Tab

Allow FSS on DP

Yes/No

Allow SBMC on DP

(Yes/No)

when bay has SBMC ON :

SBMC Substitutes values to RCP by: - SPS : Set/Reset/Suppressed

- DPS : Jammed/Open/Close/Suppressed - MPS : Undefined/Suppressed

Toggling Filtering for SPS, DPS

Yes/No

Initial Status

For software info => status at start-up

No

No

Never use Motion

• xPS Profiles (1)

(8)

Single, Double, Multi Point Status : State Labels tab : Alarms / Log Print

All Invalid States or FSS Label

SPS :

Set/Reset

DPS :

Jammed/Open/Close/Undefined

MPS :

1 among N(<16) State0..State15/ Undefined

2) On OI : printer and viewers labels are concatenation of

Force/Substitute & Value (open/close) : “forced open”

3) Profile is linked to DP then words can change

DPS Switch gear => Open/Close R/L => Remote/Local MPS N and associate DP impact labels

1) Labels are Business Language

dependant

(9)

State by State, archiving policy

For OI :

- No Archive, No logging = nothing in SQL Historian database

- Archive only = all states in VTQ

(states/values) SQL Historian database tables (Trend Viewer)

- Archive & Logging = all states in VTQ (states/values) SQL Historian database tables + states marked with “Logging” in Events SQL database table (Event Viewer + Archive viewer + printer)

Single, Double, Multi Point Status : State Treatment Tab

Relation “has events logged on” for SOE

printing

For C264 :

- Archive & Logging = Archive means stored in event list (2048 events in memory) & Logging means displayed in event list of front face (200 events).

(10)

Single, Double, Multi Point Status : Interlock tab : Boolean value by state

Note : For MPS, no convention => depends on context of use

SPS Set and Reset Boolean value in all PSL and

interlocking :

convention : SET=TRUE, RESET=FALSE

DPS Jammed, Open and Closed Boolean value

in all PSL and interlocking :

convention : CLOSED=TRUE, OPEN=FALSE, JAMMED=INVALID,UNDEFINED=INVALID

(11)

Single, Double, Multi Point Status : Alarm tab, Alarm definition state by state

Alarm Generation

Appearance/Appearance disappearance 1 / 2 alarms

Alarmed state or not

Spurious SPS is Set and never reset

Alarm not generated

if state follow control (RFI SBUS)

Delay before alarm generation

(if DP reset for example)

Gravity 1->5

Audibility (klaxon)

Alarms are acknowledged by

operator, but clearing can be

manual or automatic

Relation “has alarm events

logged on” for alarm printing

(12)

Measurement Values : General tab

Allow FSS on MV

Yes/No

Allow SBMC on MV

(Yes/No)

when bay in SBMC ON:

Substitutes values by Suppressed

MV value display on OI

Mimic

No # after decimal.

U to display unit

No

No

• MV Profile (1)

(13)

Measurement Values : State Labels tab

Alarms

Log Print

IED disconnected

Board acquisition saturated

Digital Measurement coding

error

4-20mA DC input when

under 4mA

Threshold violation

(14)

State by State, archiving policy

For OI :

- No Archive, No logging = nothing in SQL Historian database

- Archive only = all states in VTQ

(states/values) SQL Historian database tables (Trend Viewer)

- Archive & Logging = all states in VTQ (states/values) SQL Historian database tables + states marked with “Logging” in Events SQL database table (Event Viewer + Archive viewer + printer)

Measurement Values : State Treatment Tab

Note :

- Archive only for valid => value will be available for trend viewer

- Archive & Logging for SelfCheckFault and Unknown to store acquisition errors

• MV Profile (3)

(15)

Measurement Values :

Interlocking tab

Note : Goal is use MV associated status in PSL. No convention => depends on context of use

• MV Profile (4)

(16)

Measurement Values :

Alarm Management tab

Alarm Generation

Appearance/Appearance disappearance 1 / 2 alarms

Alarmed state or not

Delay before alarm generation

Gravity 1->5

Audibility (klaxon)

Alarms are acknowledged by

operator, but clearing can be

manual or automatic

(17)

Measurement Values :

Mean Value tab cf. PS06

Reference hour :

- Hour of day for min/max/average values calculation

- Daily mean values stored in monthly VTQ table for 15 months

Reference day :

- Day of month for min/max/average

values calculation

- Monthly mean values stored in yearly

VTQ table for about 5 years

Daily Monthly Yearly .csv VTQ tables SQL HISTORIAN Event SQL HISTORIAN VTQ 35 days storing 15 months storing 5 years storing

• MV Profile (6)

(18)

Single, Double CounTer: Status…

Like MV Except

Pulse value

multiplicative coefficient

Counter over max value

Double Counter invalidity

(19)

• Content

 Generalities

 Inputs Profiles

 Outputs Profiles

(20)

Single, Double Point Control: General tab

Define SBUS control sequence

in one or two steps :

In DE :

Client send control to Server Server send back Ack to Client In SBO :

- Step Selection

kept by Server with Time Out [0..600](s)

- Step Execution

SBO Many => transformer

Note : At PACiS OI Level, DE/SBO pop-up.

DE with SBO popup = Control is DE appearing in SBO-like popup

• xPC Profiles (1)

(21)

Single, Double Point Control:

use and labels

Set Point => no order

Usage :

Some controls are using only one “channel” e.g. Master Trip Reset

Labels “status” for control send

logging, alarms, popup buttons

On Control

(22)

Single, Double Point Control:

interlocking and FBD tab

PSL status on control

False/True

Note : Goal is use xPC associated status in PSL.

• xPC Profiles (3)

(23)

Single, Double Point Control:

Alarm on NACK

Alarm on control

Yes/No

Clearing Acknowledged alarms

Delay

[0..120]

Gravity

[1..5]

Klaxon

[Yes/No] + Relation

V4.7

• xPC Profiles (4)

References

Related documents