With reference to the below mentioned Scope of Work, please find attached is the Commercial Offer for Air Field &
Infrastructure for EK Flight Training Organization Facilities at DWC Dubai. 1. Scope of Work
The Scope of work includes the following systems for this proposed package:
Automatic Sprinkler System
Stand Pipe System &Fire Extinguishers
Low Level High Expansion Foam system with Electric actuation (Detection) for Hangar Area
Foam-Water Spray Deluge System with Heat Detection (5 Rooms).
FM200 Clean Agent Fire Suppression System with Photo Electric Smoke Detection (13nos. Rooms).
Fire alarm & detection system.
Design, Supply, Installation and Testing & Commissioning for above mentioned Systems. 2. Commercial Offer:
Commercial Offer : Main Offer (Based on the design drawing issued)
# Description Total Price (in AED)
Design, Supply, Testing and Commissioning of Equipment’s for following systems for Air Field & Infrastructure project for EK Flight Training Organization Facilities at DWC Dubai.
1 Automatic Sprinkler SystemEquipment. 307,687.00
2 Standpipe System Equipment and Fire Extinguishers. 419,755.00
3 High Expansion Foam system equipment with Electric actuation(Detection) for Hangar Area. 1,516,299.00
4 Deluge Foam-Water Spray System equipment with Heat Detection. 647,634.00
5 FM200 Clean Agent Fire Suppression System equipment withPhoto Electric Smoke Detection. 1,162,576.00
6 Fire alarm& Detection system. 765,279.00
7 Spares & Extra materials as per specification. 473,602.00
8
Supply of Pipes (GI Seamless ASTM A 53 Gr. B; Sch. 40, GRE Pipes), Fittings, Supports, Cables, and Conduits & Accessories , Labor for installation Charges Complete Fire Protection, Detection & Alarm systems.
3,309,225.00
9 Supply of Fire Station Foam Equipment’s - 2nos. 800 Gallon FoamBladder Tank with 1595 Gallon of ANSULITE 3% AFFF (AFC-3A) 197,829.00 Grand Total 8,799,886.00 (AED EIGHT MILLION SEVEN HUNDRED NINETY NINE THOUSAND EIGHT HUNDRED EIGHTY SIX.)
3. Optional Offer: ( Not shown in the Drawings.) Commercial Offer : Optional Offer
# Description Total Price (in AED)
1 Design, Supply, Installation, Testing & Commissioning of FM 200 System forUnprotected Rooms – 7 Nos. 351,323.00 2 Actual Discharge Test For Hangar Area High Expansion foam system, Smallestroom of FM 200 system. 70,356.00
3 Extended Warranty for Additional 4 Years. 228,409.00
4 Design, Supply, Installation, Testing & Commissioning of Seismic Supports. 329,526.00
Grand Total 979,614.00
4. Bill Of Material for the above proposed systems: Automatic Sprinklers System Bill Of Materials
# Product Description Unit Quantity Make
1 Upright Sprinkler Heads
K80, Upright Sprinkler, 1/2" NPT, 68⁰C – Fast Response, Brass, UL/ FM Nos 414 Tyco
K115, Upright Sprinkler, 3/4" NPT, 93⁰C - Fast Response, Brass, UL/
FM Nos 330 Tyco
2 Concealed Pendent Sprinkler Heads
Concealed Pendent Sprinkler, K80, 1/2" NPT, 68⁰C - Quick Response,
Chrome, C/w Series RFII Cover Plate, UL listed Nos 246 Tyco
3 Spare Sprinkler Head Cabinet & Wrench
Spare Sprinkler Cabinets Nos 3 Tyco
Standard Wrench for 1/2" NPT sprinklers Nos 6 Tyco
4 Alarm Check Valve Assembly
Ø8" Alarm Check Valve, G X G, 300Psi, UL/ FM Nos 1 Tyco
Ø8" Alarm check valve trim, Vertical Installation, UL/ FM Nos 1 Tyco
Retard chamber 1/2" NPT, UL/ FM Nos 1 Tyco
Water motor alarm Nos 1 Tyco
Alarm pressure switch, Single contact, UL/ FM Nos 1 Tyco
Ø8" Gate Valve, OS&Y Flange Type, UL/ FM, C/w Supervisory switch Nos 1 NIBCO
Ø6" Alarm Check Valve, G X G, 300Psi, UL/ FM Nos 1 Tyco
Ø6" Alarm check valve trim, Vertical Installation, UL/ FM Nos 1 Tyco
Retard chamber 1/2" NPT, UL/ FM Nos 1 Tyco
Water motor alarm Nos 1 Tyco
Alarm pressure switch, Single contact, UL/ FM Nos 1 Tyco
Ø6" Gate Valve, OS&Y Flange Type, UL/ FM, C/w Supervisory switch Nos 1
NIBCO
s
Ø2-1/2" Alarm check valve trim, Vertical Installation, UL/ FM Nos 1 Tyco
Retard chamber 1/2" NPT, UL/ FM Nos 1 Tyco
Water motor alarm Nos 1 Tyco
Alarm pressure switch, Single contact, UL/ FM Nos 1 Tyco
Ø2-1/2" Gate Valve, OS&Y Flange Type, UL/ FM, C/w Supervisory
switch Nos 1 NIBCO
5 Zone Check valve Unit
Ø8" Zone control valve Unit
Ø8" Butterfly Valve, Grooved, Gearbox operated, UL/ FM Nos 1
NIBCO
Ø8" Water Flow switch UL/ FM approved Nos 1 Tyco
Ø1" Test & Drain valve, NPT threaded, 1/2" Orifice, UL/ FM Nos 1 Tyco
Water pressure gauge, C/w globe valve Nos 1 Tyco
Ø1" Inspector test Connection, UL/ FM approved Nos 1 Tyco
Ø8" Check Valve, Flanged, UL/ FM Nos 1
NIBCO
Ø6" Zone control valve Unit
Ø6" Butterfly Valve, Grooved, Gearbox operated, UL/ FM Nos 3
NIBCO
Ø6" Water Flow switch UL/ FM approved Nos 3 Tyco
Ø1" Test & Drain valve, NPT threaded, 1/2" Orifice, UL/ FM Nos 3 Tyco
Water pressure gauge, C/w globe valve Nos 3 Tyco
Ø1" Inspector test Connection, UL/ FM approved Nos 3 Tyco
Ø6" Check Valve, Flanged, UL/ FM Nos 3
NIBCO
Ø3" Zone control valve Unit
Ø3" Butterfly Valve, Grooved, Gearbox operated, UL/ FM Nos 1
NIBCO
Ø3" Water Flow switch UL/ FM approved Nos 1 Tyco
Ø1" Test & Drain valve, NPT threaded, 1/2" Orifice, UL/ FM Nos 1 Tyco
Water pressure gauge, C/w globe valve Nos 1 Tyco
Ø1" Inspector test Connection, UL/ FM approved Nos 1 Tyco
Ø3" Check Valve, Flanged, UL/ FM Nos 1
NIBCO
Ø2-1/2" Zone control valve Unit
Ø2-1/2" Butterfly Valve, Grooved, Gearbox, UL/ FM Nos 1
NIBCO
Ø2-1/2" Water Flow switch UL/ FM approved Nos 1 Tyco
Ø1" Test & Drain valve, NPT threaded, 1/2" Orifice, UL/ FM Nos 1 Tyco
Water pressure gauge, C/w globe valve Nos 1 Tyco
Ø1" Inspector test Connection, UL/ FM approved Nos 1 Tyco
6 Breeching Inlet & Cabinet
Single breeching inlet cabinet Surface Mounted Wired Glass
Complete Stainless steel ( Brush316) Size:600x600x300 Nos 3
NAFFCO
Breeching Inlet Ø6" X 4 way, Red painted, Kite mark Nos 3
NAFFCO
Ø6" Check Valve, Flanged, UL/ FM Nos 3
NIBCO
7 Building Isolation Valve
Ø8" Gate Valve, OS&Y Flange Type, UL/ FM, C/w Supervisory switch Nos 3
NIBCO
Ø8" Backflow Preventer Nos 3
AMES
Ø2-1/2" Gate Valve, OS&Y Flange Type, UL/ FM, C/w Supervisory
switch Nos 1
NIBCO
Ø2-1/2" Check Valve, Flanged, UL/ FM Nos 1
NIBCO
8 Air Release Valve
1" Automatic Air Release Valve, UL/ FM approved Nos 6 Tyco
1" Ball Valve Nos 6 Tyco
Water pressure gauge, C/w globe valve Nos 6 Tyco
9 Drain Valves
2" Ball Valve Nos 13 Tyco
1
0 Pipes, Fitting & Other accessories
Supply of Pipes (Above ground: GI Seamless, Sch.40 ASTM A 53 Gr. B, Underground: GRE), Fittings, Supports, Painting and other consumables, Labor for installation, Supervision, Engineering, testing & Commissioning Charges.
Lot 1 Pipes: Shield, Fittings: National / Equivalen t
Stand Pipe System Bill Of Materials
# Product Description Unit Quantity Make
1 Breeching Inlet & Cabinet
Single breeching inlet cabinet Surface Mounted Wired Glass Complete
Stainless steel ( Brush316) Size:600x600x300 Nos 3 NAFFCO
Breeching Inlet Ø6" X 4 way, Kite mark approved Nos 3 NAFFCO
Ø6" Check Valve, Flanged, UL/ FM Nos 3 NIBCO
2 Stand Pipe riser isolation valve
Ø6" Gate Valve, OS&Y Flange Type, UL/ FM, C/w Supervisory switch Nos 2 NIBCO
Ø2-1/2" Gate Valve, OS&Y Flange Type, UL/ FM, C/w Supervisory
switch Nos 1 NIBCO
3 Surface mounted type Fire Hose Cabinets -FHC-1
Double vertical hose reel cabinet, surface type solid door, stainless
steel 316 Facia (Mirror) Nos 17 NAFFCO
1-1/2" Landing Valve, Double female, Chrome - UL Listed Nos 17 ELKHART
1-1/2" X 30 Mtrs Fire Hose C/W polished chrome coupling UL listed + 1 1/2" Fire Hose Rack polished Chrome finish + Rack nipple - polished chrome finish.
No
s 17 ELKHART
s
1-1/2" Nozzle Polished Chrome Finish - UL Nos 17 ELKHART
2-1/2" Landing valve double female, chrome - UL Listed Nos 17 ELKHART
2-1/2" Female BS 336 Instantaneous Adaptor Nos 17 Local make
2-1/2" X 30 Mtrs Fire Hose C/W light alloy couplings - UL Listed Nos 17 Walker fire
2-1/2" Connecting adopter for hose & nozzle Nos 19 Local make
2-1/2" nozzle chrome finish - UL Nos 17 ELKHART
Ø3" Water Flow switch UL/ FM approved Nos 17 TYCO
10Lbs CO2 Fire Extinguisher Nos 17 AMEREX
10Lbs ABC with hose & horn Fire Extinguisher Nos 17 AMEREX
4 Surface mounted type Fire Hose Cabinets -FHC-2
Double vertical hose reel cabinet, surface type solid door, stainless
steel 316 Facia (Mirror) Nos 1 NAFFCO
2-1/2" Landing valve double female, chrome - UL Listed Nos 1 ELKHART
2-1/2" Female BS 336 Instantaneous Adaptor Nos 1 Local make
2-1/2" X 30 Mtrs Fire Hose C/W light alloy couplings - UL Listed Nos 1 Walker fire
2-1/2" Connecting adopter for hose & nozzle Nos 1 Local make
2-1/2" nozzle chrome finish - UL Nos 1 ELKHART
Ø3" Water Flow switch UL/ FM approved Nos 1 TYCO
10Lbs CO2 Fire Extinguisher Nos 1 AMEREX
10Lbs ABC with hose & horn Fire Extinguisher Nos 1 AMEREX
5 Fire Extinguishers
10Lbs CO2 Fire Extinguisher Nos 41 AMEREX
10Lbs ABC with hose & horn Fire Extinguisher Nos 41 AMEREX
20Lbs CO2 Fire Extinguisher, Trolley type Nos 2 AMEREX
6 Air Release Valve
1" Automatic Air Release Valve, UL/ FM approved Nos 6 Tyco
1" Ball Valve Nos 6 Tyco
Water pressure gauge, C/w globe valve Nos 6 Tyco
7 Drain Valves
2" Ball Valve Nos 3 Tyco
8 Pipes, Fitting & Other accessories
Supply of Pipes (Above ground: GI Seamless, Sch.40 ASTM A 53 Gr. B, Underground: GRE), Fittings, Supports, Painting and other consumables, Labor for installation, Supervision, Engineering, testing & Commissioning Charges.
Lot 1 Pipes: Shield, Fittings: National / Equivalen t
High Expansion Foam System Protected area Details: # DescriptioRoom n Level Building Un it QTY Area m2 Design Density CMM/ m2
1 High Expansion Foam System Protected area Details:
Hangar
Area Ground Floor Maintenance, Repair and Overhaul Hangar no 1 3,600.00 0.9
High Expansion Foam System Bill Of Materials:
# Product Description Unit Quantity Make
1 Deluge Valve Assembly
Ø8" Deluge Valve, G X G, UL/ FM approved Nos 1 Tyco
Ø8" Deluge valve Electric Trimming Nos 1 Tyco
Water motor alarm Nos 1 Tyco
Alarm pressure switch, Double Contact, UL/ FM Nos 1 Tyco
Solenoid valve 24VDC, 1/2" NPT Nos 1 Tyco
Ø8" Gate Valve, OS&Y Flange Type, UL/ FM, C/w Supervisory switch Nos 1 NIBCO
2 Horizontal Bladder tanks-Foam
Bladder Tank, 500 gal. Horizontal, Standard Red Nos 2 Tyco/ Ansul
3 Bladder Tank Accessories
Sight Gauge Assembly, for 500-1500 gal. VBT Nos 2 Tyco/ Ansul
Bladder Tank Fill Pump (includes suction and clear discharge hose) Nos 1 Tyco/ Ansul
4 Proportioner - Between Flanged
Proportioner, 8 in., Flanged, 2% Jet-X Nos 2 Tyco/ Ansul
5 Water Inlet Valves
2-1/2 in. Water Inlet Ball Valve Nos 2 Tyco/ Ansul
6 Concentrate Isolation Valves
2-1/2 in. Concentrate Isolation Ball Valve, Nos 2 Tyco/ Ansul
7 Check Valves
2-1/2 in. Swing Check Valve (brass) Nos 2 Tyco/ Ansul
8 Hydraulic Concentrate Control Valves
2-1/2 in. Hydraulic Concentrate Ball Valve Nos 2 Tyco/ Ansul
9 JET-X High Expansion Foam Generators
High Expansion Generator, JET-X-15A (UL) Nos 15 Tyco/ Ansul
JET-X-15 Wall Relief Louver, NEMA 4 Nos 15 Tyco/ Ansul
1
0 JET-X High Expansion Foam Concentrate
JET-X 2% High Expansion Foam Concentrate, 55 Gallon Drum Nos 19 Tyco/ Ansul
1
1 36 Gallon Foam Stations
Foam Station w/hose reel and nozzle (100 ft. hose), 36 gallon, CR
Epoxy Red Nos 4 Tyco/ Ansul
s Ansul 1
2 Building Isolation Valve
Ø6" Gate Valve, OS&Y Flange Type, UL/ FM, C/w Supervisory switch Nos 1 NIBCO
1
3 Other Valves & Accessories
Ø2" Gate Valve, OS&Y, Threaded, 175 psi, UL/ FM, C/w Supervisory
switch Nos 15 Tyco
Ø2" Y-Strainer for High expansion Foam generator Nos 15 DCD Approved
1
4 Drain Valves
2" Ball Valve Nos 4 Tyco
1
5 Pipes, Fitting & Other accessories
Supply of Pipes (Above ground: GI Seamless, Sch.40 ASTM A 53 Gr. B, Underground: GRE), Fittings, Supports, Painting and other consumables, Labor for installation, Supervision, Engineering, testing & Commissioning Charges.
Lot 1 Pipes: Shield, Fittings: National / Equivalen t
Foam-Water Spray System Protected Rooms List:
# DescriptionRoom RoomNo. Level Unit QTY Area(m2)
Design Density LPM/ m2 Foam Discharge Duration (Min)
Airfield Electrical Substation Building
1 Generator Room G01-A Ground Floor no 1 49.68 12.2 20
Airport Fire Station Building
2 Generator Room G20-A Ground Floor no 1 33.00 12.2 20
Maintenance, Repair and Overhaul Hangar Building:
3 Generator Room G19-A Ground Floor no 1 51.94 12.2 20
MRO Hangar Utility Service Building:
4 Thinner Storage Room G07-A Ground Floor no 1 14.00 12.2 20
5 Oil Storage Room G02-A Ground Floor no 1 14.00 12.2 20
(NOTE: The dimension’s mentioned above are as per the drawings forwarded by Client. Any change to dimension’s later-on will bring about changes commercially if necessary.)
Foam-Water Spray System Description:
The proposed Deluge Foam-Water Spray System shall be provided for above mentioned rooms. The system to be designed to provide adequate proportioned foam – water solution at Design Density of 12.20 LPM/M² over the entire protected areas with foam discharge duration of 20 minutes.
FM200 Clean agent System Protected room details : (As per Design drawings)
# Room Description Level Void Area (m2) Height (m) Volume (m3)
Airfield Electrical Substation Building:
1 CCR Room-G07-A Ground Room void 77.76 5.10 396.58
Trench 30.00 1.25 37.50
2 Control Room-G08-F Ground Room void 25.92 5.10 132.19
3 MV Room-G02-A Ground Room void 77.76 5.10 396.58
Trench 20.30 1.25 25.38
FM200 Clean agent System Protected room details : (As per Design drawings)
# Room Description Level Void Area (m2) Height (m) Volume (m3)
Airfield Electrical Substation Building:
Trench 46.00 1.25 57.50
Airport Fire Station Building:
5 LV Room-G19-A Ground Room void 87.12 5.30 461.74
Trench 50.00 1.250 62.50
6 MV Room-G04-A Ground Room void 23.76 5.30 125.93
Trench 16.00 1.25 20.00
7 Equipment Room-F04-H 1st Floor
Room void 37.29 2.28 85.02 Ceiling Void 37.29 1.13 42.14 Floor Void 37.29 0.70 26.11 8 LV Room-F12-H 1st Floor Room void 19.47 2.28 44.39 Ceiling Void 19.47 1.13 22.00 Floor Void 19.47 0.70 13.63
9 VCR-S01-H VCR Level Room void 57.50 3.25 186.88
Maintenance, Repair and Overhaul Hangar Building: 1 0 LV Room-G16-A Ground Room void 95.00 5.10 484.50 Trench 42.00 1.25 52.50 1 1 MV Room-G17-A Ground Room void 61.74 5.10 314.87 Trench 12.60 1.25 15.75 1
2 Batteries Room-G23-B Ground Room void 29.76 5.10 151.78
1
3 Dangerous Goods-G25-A Ground Room void 13.50 5.10 68.85
(NOTE: The dimension’s mentioned above are as per the drawings and Room List forwarded by Client. Any change to dimension’s later-on will bring about changes commercially if necessary.)
FM200 Clean agent System Protected room details : (Optional Rooms)
# Room Description Level Void Area (m2) Height (m) Volume (m3)
Airport Fire Station Building:
1 Tel. Room-G09-E Ground Room void 4.96 5.30 26.29
Maintenance, Repair and Overhaul Hangar Building:
2 Tel. Room-G03-E Ground Room void 17.60 5.10 89.76
3 MV Room-G17-A Ground Room void 36.30 5.10 185.13
4 Elec. Room-F06-E 1st Floor Room void 20.50 3.93 80.57
5 Tel. Room-F21-E 1st Floor Room void 9.30 3.93 36.55
6 BMS Room-F07-F 1st Floor Room void 26.68 3.93 104.85
MRO Hangar Utility Service Building:
7 Elec. Room-G06-A Ground Room void 6.16 5.10 31.42
(NOTE: The dimension’s mentioned above are as per the drawings and Room List forwarded by Client. Any change to dimension’s later-on will bring about changes commercially if necessary.)
FM200 System Description
The proposed FM200 Fire Suppression System will protect the above room by Stand Alone System with Main &
Reserved Cylinders and the cylinders will be placed inside/outside the protected rooms in an appropriate location.
The system proposed is a total flooding, FM200 system designed in accordance with manufacturer standards with
Design Concentration of 7.1% and flooding factor of 0.5562 @ 21°C.
The FM200 System protected room is provided with a stand-alone (conventional) extinguishing release control panel connected with detectors, abort switch, pull station, alarm bells and sounders / flashers. 1st stage alarm sounders are provided inside the protected risk and 2nd stage flasher outside the room is provided.
The release control panel has a fire/fault volt free contact output that can be interface to existing Building FACP by others.
The FM200 system can be activated by;
Automatic Release from the Releasing Panel & Smoke Detectors Manual Release (Electrical) at the Manual Release Station
Addressable Fire Alarm& detection System
# Description UNIT Quantity
1 Main Fire alarm control panel (FACP) with battery& power supply. No 1
2 Sub Fire alarm control panel (FACP) with battery& power supply. No 3
3 Graphic station with PC,BAC net interface, Printer Lot 1
4 Optical smoke detector with standard base No 116
5 Optical smoke detector with Void No 58
6 Response indicator No 58
7 Intrinsic safe smoke detector No 1
8 Heat Detector with standard base No 5
9 Multi sensor detector No 14
10 Triple IR Flame detector No 13
11 Beam detector No 2
12 Gas detector No 1
13 Double action manual call point No 34
14 Double action manual call point W/P No 25
15 Fire alarm bell No 42
16 Fire alarm bell Outdoor No 7
17 Fire alarm sounder No 12
18 Ceiling strobe S1 No 34
19 Ceiling strobe S2 No 1
20 Ceiling strobe S3 No 1
21 Wall mounted strobe S1 No 17
22 Wall mounted strobe S2 No 4
23 Wall mounted strobe S3 No 9
24 Monitor module No 186
25 Relay module No 53
26 Isolator Module No 49
27 Installation tools Lot 1
28 Spare parts 2% Lot 1
29 LHS cable with controller for Hanger area Lot 1
30 VLF 250 VESDA detector No 3
31 PIPIES&ACCESSORIES for VESDA Lot 1
5. Brand offered:
Mechanical Hardware:
Sprinklers, Alarm valve : Tyco Safety Products, UL/FM Approved.
Stand Pipe equipment : ELKHART
Fire Extinguishers : AMREX, UL/ FM approved
FM 200 Gas Suppression : Tyco Safety Products, UL/FM Approved.
Pipes : Shield, UL / FM Approved.
Electrical Hardware:
Fire Detection & Alarm System : Tyco Safety Products, UL Listed.
6. Terms & Conditions:
Payment : To be Discussed
Price : In UAE Dirham
Delivery FF Hardware’s : 08 – 12 Weeks (After Official Design Approval) Delivery FA Hardware’s : 10 – 12 Weeks (After Official Design Approval)
Payment Terms : To be confirmed upon credit approval process
This commercial offer is made in accordance with the Tyco UAE Terms and Conditions of Sale, Which can be downloaded from the following web
page:-http://www.tycofireuae.com/Products-Solutions/solutions-services 7. Reference Drawings List:
Fire Fighting System
# Drawing No. Drawing Title. Rev /Date
1 D14010-0100D-TD-MF-MRO-101 Maintenance, Repair and Overhaul HangarFloor LevelFIRE FIGHTING Ground 20.11.20Rev 02/ 15 2 D14010-0100D-TD-MF-MRO-102 Maintenance, Repair and Overhaul HangarFloor LevelFIRE FIGHTING First 20.11.20Rev 02/
15 3 D14010-0100D-TD-MF-MRO-103 Maintenance, Repair and Overhaul HangarRoof Level FIRE FIGHTING Top of 20.11.20Rev 01/
15
4 D14010-0100D-TD-MF-MRO-121 MRO Utility Service Block Plans FIRE FIGHTING 12.05.20Rev 01/
15 5 D14010-0100D-TD-MF-MRO-701 Maintenance, Repair and Overhaul HangarDIAGRAM FIRE FIGHTING RISER 12.05.20Rev 01/
15
6 D14010-0100D-TD-MF-AFS-101 Airport Fire Station Ground Floor Level FIRE FIGHTING 20.11.20Rev 02/
15
7 D14010-0100D-TD-MF-AFS-102 Airport Fire Station First Floor Level FIRE FIGHTING 20.11.20Rev 02/
15 8 D14010-0100D-TD-MF-AFS-103 Airport Fire Station Intermediate Floor Level FIRE FIGHTING 20.11.20Rev 01/
15
9 D14010-0100D-TD-MF-AFS-104 Airport Fire Station VCR Floor Level FIRE FIGHTING 20.11.20Rev 01/
15
10 D14010-0100D-TD-MF-AFS-701 Airport Fire Station RISER DIAGRAM FIRE FIGHTING 20.11.20Rev 01/
15
11 D14010-0100D-TD-MF-AES-101 Airfield Electrical Substation Plans FIRE FIGHTING 27.04.20Rev 00/
15
Fire Alarm System
# Drawing No. Drawing Title. Rev /Date
1 D14010-0100D-TD-E-MRO-401 Maintenance, Repair and Overhaul HangarFloor LevelFIRE ALARM LAYOUT Ground 20.11.20Rev 01/ 15 2 D14010-0100D-TD-E-MRO-402 Maintenance, Repair and Overhaul HangarFloor LevelFIRE ALARM LAYOUT First 20.11.20Rev 01/
15 3 D14010-0100D-TD-E-MRO-702 Maintenance, Repair and Overhaul Hangarschematic diagram sheet 1 of 3 ELV 27.04.20Rev 00/
15
4 D14010-0100D-TD-E-MRO-704 Maintenance, Repair and Overhaul HangarELV
15 5 D14010-0100D-TD-E-AFS-401 Airport Fire Station Ground Floor Level FIRE ALARMLAYOUT 20.11.20Rev 01/
15 6 D14010-0100D-TD-E-AFS-402 Airport Fire Station First Floor Level FIRE ALARM LAYOUT 20.11.20Rev 01/
15 7 D14010-0100D-TD-E-AFS-403 Airport Fire Station Intermediate Floor Level FIRE ALARM LAYOUT 20.11.20Rev 01/
15
8 D14010-0100D-TD-E-AFS-703 Airport Fire Station ELV Schematic diagram sheet 2of 2 20.11.20Rev 01/
15
8. Inclusions & Consideration:
This offer is based on the Drawings and Specifications provided. If it should prove necessary to
amend our proposals, when more detailed information becomes available, major changes in comparison with the present information, we reserve the right to amend our quotation accordingly. We are proposing our standard Products as mentioned in section-6, Since Vendor list
are not available.
Proposed Fire Hose cabinets are solid door type only. Size, thickness and finishing are as per
manufacturer’s standard only.
Any changes in Drawings and Room Schedule provided and its description type more than our
proposal will be consider as additional cost.
Room dimension for FM200 Clean agent Fire Suppression System and Foam Water Spray Deluge
System are as per the drawings provided along with the enquiry. Any changes on the dimension that will affect our gas calculation and costing, we reserve to amend the quote accordingly.
FM200 storage containers (red epoxy polyester finish) are designed to hold FM200 in liquid form
and Nitrogen, which is used to super-pressurize the container to 24.8 bar (360 psi) at 20 deg. C
We assume that FM200 rooms are sealed to contain the gas inside the risks protected. Closing
of all openings into the room and any other openings that might dilute or allow the escape of the extinguishing gas is by others.
Extinguishing Panel Enclosure for FM200 System is Surface Mounted, IP30, 1.2mm mild sheet
steel, Epoxy powder coated Red RAL 3002, 230 Vac and not IP21 to IEC 60529, enameled steel cabinet
06 Lamps Status Unit indicating/ illuminating status of the system will be provided outside each
protected FM200 Space and not a Graphic Annunciator type of panel.
Stand by Power for the FM200 Extinguishing Panel is Lead Acid Batteries for 24 Hours only and
not 72 Hours.
Photoelectric Smoke Detectors has been considered (and not Ionization Type) for the smoke
detection part of FM200 Protected Space and Detector, Heat, Rate Compensated, 140º F, Vert. for the Foam Water Spray Deluge System protected space.
We have considered the Tie-In connection from existing network is taken from Isolation Valve Outlet. Any live tapping or any draining requirement shall be carried out by additional cost.
Proposed above ground pipes for Water based system as GI. Seamless ASTM A. 53 Gr. B Sch. 40,
and for Clean agent system GI. Seamless ASTM A 53 Gr. B Sch. 40.
We have considered Galvanized 3000 lbs. forged steel fittings for the FM200 System.
For interfacing with other systems – only one volt free contacts in extinguishing control panel
&Fire alarm panel are available.
Interfacing are only available for the below mentioned points
A. Common Fire
B. Common Fault
C. Gas Release Signal
D. 1st Stage Alarm
E. 2nd Stage Alarm
*Any additional interfacing requirements if required can be provided at additional cost.
Interfacing module for HVAC, Firefighting, Exhaust fans is approximate quantity will be taken in our offer (details not provided)
We have Proposed MFACP located at MRO building, other building considered for SUB fire alarm
panel.
Single graphic station with PC with printer considered for MRO building.
VESDA panel considered for telecom room based on the drawings. Interfacing with fire alarm
panel.
We have considered Fire rated FP200 cables for Fire detection& alarm system.
All components are suitable for indoor/ outdoor & safe environment and not flameproof / explosion proof.
All equipment proposed is Civil defense approved.
Design Documentation like Design Drawing and Technical Submittal, Operation & Maintenance
Manual are included in the offer.
Room Integrity Test: Any gas extinguishing system should have room integrity to establish the
pressure retention properties of the room. This test shall establish the ability of the room to retain the gas & also if a vent is required. We have included for integrity testing for all the FM200 Gas Fire Suppression System protected areas in our offer. However, if the initial test may fail, we shall provide a second Room Integrity Test which shall incur variation.
All items quoted in our offer is strictly based on the drawings. Any item not mentioned in our
quotation is not part of our offer and will be quoted separately if required.
Any interpretation or variation other than the above should be brought to our notice based on
which our offer will be revised.
Procurement of system equipment’s is after approval of Technical Submittal and Design Drawings & Calculations from Consultants.
Our standard warranty will be for 12 months from the date of commissioning the systems against manufacturing defects.
Material Submittals and datasheets shall be provided against order confirmation.
For approval of System Design Drawings by Civil Defense; our scope is limited to providing all
necessary supporting documents and liaising with CD office for such approvals. Any Fees levied for approval shall be paid by the customer at actual to CD.
As Built Drawings.
9. Exclusions:
All kind of Civil Works, Grouting, Pipe sleeves, Fire sealant, Valve chambers and Pit covers,
Escutcheons, Concrete thrust blocks, Hume pipes for Road crossing, Excavation, Backfilling, any type of foundations and Poles.
Any Works related Structural, Electrical; any other mechanical which is not comes under fire
protection scope.
Manlift/Scissor Lift for access above 3 meters height installation works.
Crane/Fork Lift
Any other equipment/ instrument/ materials other than provided BOQ.
Seismic supports and Seismic restrained system, Building expansion joints.
Sway bracing supports, Secondary Structural supports for Sprinkler and Firefighting piping.
Design, Supply, Installation, Testing & Commissioning of Fire water storage tank & Tank accessories, Fire pump sets, Pump room building, Plinths, etc., Since fire water is tapped from Existing network.
Post indicators for External Underground valves.
Sprinkler indicator panel.
Weight contact device underneath the fire extinguishers in the Fire hose cabinets are excluded.
Extract Fan, Pressure Relief, Smoke Clearance Ventilation, Drop/Louver Curtains & Fire/Smoke
Damper. Automatic/Magnetic Door Closure/Holder/Release.
Pressure Relief / Automatic Fire dampers in air conditioning ductwork are excluded.
Pressure reducing station is excluded since not indicated in the design drawings.
Actual Discharge Test for FM200 and Foam Water Spray Deluge System & Factory acceptance
test.
Stand by Power of 72 hours for the Extinguishing/ Release Panels.
Temporary Fire Fighting System.
Remote annunciation to the building security system and illuminate LED light on graphic annunciator for FM200 and Foam Fire Suppression System.
Any type of Pneumatic/ Nitrogen Filled/ Pilot Cylinders for actuation of the FM200 Fire Suppression System.
Interfacing and cabling works of FM200 and Foam Fire Suppression System to other third party equipment / Systems (HVAC, Dampers, BMS, SCADA, Discharge of FM200 Gas shall shut down power the equipment within the protected area, Closing of Supply return dampers and local AHU shall be shutdown wherever and whichever is applicable).
Any other interfacing requirements other than the point highlighted in Inclusions and Considerations.
Containment (Cable trays/ Trunking/MICC Cables) for Fire Alarm has not been considered part of
this offer.
Incoming power cable, isolator / MCCB and ear thing for extinguishing panel, Fire alarm panel
and detection system for Clean Agent System.
Earth / Electrical Continuity test for Pipe work within the Firefighting system equipment
Water, Power/ Electricity at site required during testing and commissioning of the systems.
Interface with existing DWC airport facility Edwards make fire alarm panel shall be excluded from our scope of works.
Fire alarm panel having in build Amplifier module& fire telephone modules are not considered.
Auto Dialer/ 24 X 7 Civil defense Panel.
Interface with CCTV, Security, Access Control, Smoke management station since details is not
provided, as per system requirement if any additional modules is required to integrate fire alarm panel with other system will be extra cost applicable.
Repeater or Annunciator Panel/MIMIC Panel.
Duct Detector, Emergency & exit Light system (Self-contained or Central battery), Voice Evacuation System, Public address system, CO detector, Firefighting Telephone System.
Networking & Graphic control station for VESDA
Passive Fire Protection (Fire Proof Paint, Fire Doors, Fire Proof Sealant) and Earthling of Fire Fighting Pipes.
Maintenance
Breathing Apparatus & Personal Safety Equipment.
Any type of Government/ Civil Defense fees.
Charges related to third party inspection/client inspection, Air fares, travels, boarding/lodging,
accommodations, foods, etc.
Site office, Site stores for Material storage.
QA/ QHSE/ HSC provided by Main contractor.
Coordination with other services.
Third party consultant approval.
We trust our offer meets with your acceptance and we look forward for your valuable order. Should you need any further assistance, please feel free to contact the undersigned on +971-4-2544774