GRID
GSE
DS Agile OI OVERVIEW
Global Systems Engineering
Global Systems Engineering
Global Systems Engineering
Global Systems Engineering
03/05/2012
DS Agile Training
DS Agile Training
DS Agile Training
Summary
1) DS Agile Operator Interface Features Page 3
1.1) DS Agile OI Basic Purpose
Basic Purpose :
Display business views
SCP : Substation Control Point Get data, Archive and logging
Which DS Agile element ? OI Client
Composition :
1) OI Server
IS main SBUS Client (also server of few System Info like Printer status) HAS Hard Disk for Archives (Historian SQL server)
HAS Printers (for SOE…) IS Server of All OI Client
2) OI Client
Subscribe to OI Server Display data
1.2) DS Agile OI Sub-components
What is, and how is composed DS Agile OI ?
SBUS Agency Ethernet SBUS Factory Link SCADA 2000 Communication Data Processing Alarm and Events Historian Trends Controls INFRASTRUCTURE OI Servers SQL Server OI Clients Internet
1.3) DS Agile OI Technical Data
Common DS Agile OI capabilities :
–
From
1
to
8
OI Client
(including remote and embedded OI client(s))
–
Up to
4
VDU on each OI Client
–
Multi-active OI server
(redundancy, twin servers)
–
Watchdog : DS Agile OI server application must be launched through
DS Agile
Watch
, so application can restart automatically in case of unexpected failure.
(continuity)
(available from V4.6.x)–
Watchdog : DS Agile OI Client application must start using
DS Agile Client
1.4) DS Agile OI Hardware Composition
Hardware composition and required OS :
PC with :
- At least 3 GBytes RAM and 1.5 GHz processor (better if dual core)
- Up to 4 monitor screens Ethernet connection, Maximum resolution 3200*2400 - Windows XP SP3
- SQL Server (Personal Edition),(SQL2005, SQL2005 embedded)
Available from DS Agile 5.0.2:
Windows Seven Windows 2008 server Microsoft SQL server 2008
Summary
1) DS Agile Operator Interface Features Page 3
2.1) DS Agile OI Windows
1) Title
2) Tools
3) Mimic
4) Short Alarms
5)Navigator
2.2) Title Bar
ALSTOM logo animated by DS Agile OI Server State
Substation Name defined into the SCE
Connected OI server for this OI client
icon displaying SBUS coupling status between DS Agile OI Server and the SBUS agency
Mode status, Substation control mode.
•Remote substation driven from RCP.
•Local substation driven through DS Agile OI.
User and Profile names are updated after logging in or out.
Time and Date are given by PC synchronised by OI Server
2.3) Command Bar
Alternately Log in and Log off (default user profile). Short cut : F2
Stops the DS Agile OI Client.
Short cut : F10 Opens the Password
Utility dialog box.
Indicates if at least one memo is active in mimics. Launches Operator Station tools Launches DS Agile SMT HMI Prints : •full screen (F5)
•active mimic (Shift+F5) Stops audible
alarms Opens the User
2.4) Custom General View Mimic
General View Mimic : (Substation, Voltage Level, …)
Electrical controllable devices (Various representations : IEC, ANSI,
customised)
2.5) Custom Bay Mimic
Detailed Bay Mimic :
Electrical controllable devices (Various representations : IEC, ANSI,
customised)
2.6) Custom System View Mimic
System View Mimic :
DS Agile System devices (MiCOM Computers, DS Agile OI, DS Agile
Gateway,…)
IED (Protections, Measurement Centres, …)
2.7) Alarm Viewer
Browser (option) Alarm List
2.8) States Viewer
2.9) Events Viewer
2.10) Trend Viewer
2.11) Direct Control Pop-up
SPC one state
SPC
2.12) SBO FSS Control
Select Before Operate
SBO for
Synchronised CB
Force
Substitute
Suppress
2.13) Hot Redundancy for OI Server
1) On
DS Agile
, Hot redundancy is possible => no manual operations
1.1) OI Client is connected to
“preferred” OI Server
. If server not available it
will immediately try connect to the other one.
Client B
Client A Client C
IEC 61850 Station Bus
Server 1 Server 2
SQL database SQL database
1.2) Both OI server perform
DP acquisition simultaneously
. There is a
GRID
GSE