BETAflam
®
Fire
Resistant
Safety
Cables
2
Safetyinstructions
Cablesaretobeusedforthedesignatedapplicationsonly.Incaseoffailureor damagetothecableorconnector,switchoffpowerimmediatelyandreplaceall damagedparts.Maintenance,repairandreplacementofthecablesandconnectors mayonlybecarriedoutbyauthorisedandtrainedpersonnel.
Waiver
Whiletheinformationcontainedinthisdocumenthasbeencarefullycompiledto thebestofourknowledge,itisnotintendedasarepresentationorwarrantyofany kindonourpartregardingthesuitabilityoftheproductsconcernedforany particularuseorpurposeandneithershallanystatementcontainedhereinbe construedasarecommendationtoinfringeanyindustrialpropertyrightsorasa licensetouseanysuchrights.Thesuitabilityofeachproductforanyparticular purposemustbecheckedbeforehandwithourspecialists.
Ourpolicyisoneofcontinuousmaterialandproductdevelopment.Wereservethe righttoofferalternativesconsistentwithourmanufacturingprogrammeatthe timeofenquiry.
Allinformationconcerningmaterialproperties,fireperformance,construction, electricalandtechnicaldata,pricesetc.reflectsourcurrentlevelofknowledgeand isprovidedwithoutobligation.Dimensionsandweightsareonlygivenasaguide. Thespecificationsmaychangeanytimewithoutpriornotice.
RoHSCompliance
Weconfirmthatfrom1stJanuary2006onwards,allproductslistedinthiscatalogue, aremanufacturedinfullcompliancewiththeEUDirective2002/95/EG(RoHS).
Contact
Consulting and sales
Switzerland
Phone +41 (0)62 288 82 82
Fax
+41 (0)62 288 83 83
sales@leoni-studer.ch
www.leoni-infrastructure-datacom.com
www.leoni-studer.ch
Germany
Phone +49 (0)6158 9208 0
Fax
+49 (0)6158 9208 19
info@leoni-kerpen.de
www.leoni-infrastructure-datacom.com
www.leoni-kerpen.de
3
Content
Page
LEONI – The Quality Connection.
The LEONI Group 4
People can move about in safety. 6
Safety from one source. 7
BETAflam® Safety and Communication Cables
Overview 8
FRT-MI 90 / Single Core / Single Insulated 10
FRT-MI 90 / Single Core / Double Insulated 13
FR-MI 90 / Single Core / Single Insulated 16
FR-MI 90 / Single Core / Double Insulated 19
FR-MI 110 / Single Core / Single Insulated 22
FR-MI 110 / Single Core / Double Insulated 25
FR-MI 110 / Multicore 28
FR-MI 110 / Multicore / Steel Tape Armour (STA) 31
FR-MI 110 / Multicore / Steel Wire Armour (SWA) 34
FR-MI 110 Comms Cables 37
BETAflam® Safety Power and Communication Cables
Overview 40
BETAfixss® Laying System
Overview 41 Page Technical information Current rating 44 Core identification 48 Halogen free 49
Degree of acidity of combustion gases 49
Smoke density 50
Flame retardant 50
No flame propagation 51
Circuit integrity under fire 51
Circuit integrity with mechanical shock 52
System integrity 52
Resistance to fire alone 53
Resistance to fire with water 53
Resistance to fire with mechanical shock 54
Summary of standards 55
General handling, storage and installation Instructions 56
Duration of system circuit integrity in the building laws 60
General Conditions of Sale and Delivery 61
Further products 63
Flexible BETAtherm® and BETAflam® Cables
Overview 42
Flexible BETAtrans® Cables
4
Service
Optical cables Hybrid cables
Copper cables
Cable systems / Wiring Systems
Relay and safety systems Sensors
Cable harnesses
Connectors Optical fibers
Wires & strands
Eng
ine
er
ing
Products and services portfolio at a glance
LEONI is a leading supplier of cable systems and related
services for the automotive industry and various other
industrial sectors.
Our group of companies employs more than 59'000 people in
33 countries. Corporate vision, highest quality and innovative
power have made us one of the leading cable manufacturers in
Europe. LEONI develops and produces technically sophisticated
products ranging from wire and optical fibers to cables through
to complete cable systems and also offers the related services.
Moreover, the product portfolio comprises strands,
standard-ised cables, hybrid cables, glass fiber as well as special cables,
cable harnesses, wiring systems components and fully
assem-bled systems for applications in various industrial markets.
The LEONI Group
Cable and cable system solutions for different industrial markets.
5
Automotive
&
Commercial Vehicles
Communication
&
Infrastructure
Industry
&
Healthcare
Electrical
Appliances
Conductors
&
Copper Solutions
Your markets – our strength.
As diverse as our product and service range are the markets and
sectors LEONI is supplying. We focus our activities on customers
in the fields of Automotive & Commercial Vehicles, Industry &
Healthcare, Communication & Infrastructure, Electrical
Appli-ances and Conductors & Copper Solutions.
LEONI's core markets
We are among the leading European suppliers in the
Communi-cation & Infrastructure market to which at LEONI as a cable
manufacturer also belong activities in the fields of infrastructure
& data communications, industrial plant projects, solar- and
wind power, energy & telecommunications, irradiation
cross-linking and traffic engineering. Our customers benefit
world-wide from innovative as well as reliable and long-lasting
products of high quality. LEONI – we create the best connection
for your future.
for further informations www.leoni.com
LEONI – The Quality Connection6
Building and transport infrastructure nowadays have high
requirements in terms of protection against disruption and fire.
Developers and planners take their responsibility seriously and
impose higher expectations on the safety technology of
build-ings such as hospitals, event facilities and office complexes.
This ensures that people can escape in the event of fire and that
successful firefighting minimises the damage caused. While
infrastructure is presented with fresh challenges from ever more
complex applications, the obligation everywhere is to provide
maximum safety. Our BETAflam
®products meet the key
interna-tional regulations and standards in both structural and civil
engineering.
We are convinced that the trend towards comprehensive safety
will also be the focus of much attention in the future, and that
we will make a crucial contribution in this regard with our high
quality products.
Public buildings …
Our cables and support systems energise the safety
equip-ment and escape routes.
Train stations, underground stations, airports …
Lighting, emergency exits and signalling ensure safety in
infrastructure buildings. Thanks to their system integrity
dur-ing exposure to fire, our products make a crucial contribution
in critical situations.
Transport routes …
Our products are used for the markings, illumination and
control of transport routes.
Tunnels …
With our cables and support systems we safeguard the
light-ing and optical control equipment as well as power supply to
ventilators and escape routes for emergency situations.
People can move about in safety.
Protection to life and property is assured.
7
Safety from one source.
Universal
application
with
system
integrity.
LEONI – The Quality Connection
CertificateNo.896
BETAflam
®cables according
to German VDE Standard
Wires and cables for highest
safety requirements with
circuit integrity in accordance
with DIN VDE 0266
VDE approval and
surveillance
Fire resistant
No flame propagation
Cross-linked by irradiation
System circuit integrity to
DIN 4102 part 12, E30 - E90
Halogen and silicone free
Low smoke and gas
emission
In compliance with RoHS
directive
Operating temperature
90 °C
BETAflam
®cables according
to British Standard
Single and Multicore cables
for highest safety
require-ments, in accordance with
BS 6387 C.W.Z.
LPCB approval and
surveillance
PSB Product Listing
Scheme, SG
Fire resistant / Circuit
integrity
No flame propagation
Cross-linked by irradiation
Halogen and silicone free
Low smoke and gas
emission
In compliance with RoHS
directive
Operating temperature
90 °C and 110 °C
BETAflam
®cables according
to Swiss Standard
Single and Multicore cables
for high safety requirements
in accordance with
SEV TP 20B/3C.
ElectroSuisse approval
Fire resistant / retardant
No flame propagation
System circuit integrity
E30
Halogen and silicone free
Low smoke and gas
emission
In compliance with RoHS
directive
Operating temperature
90 °C
BETAfixss
®cable support
system with total circuit
integrity in fire according
to German DIN Standard
This support system is used in
electrical cable installations
with system integrity. They
also ensure fire resistant
fixing of cables laid in the area
between floors as well as F30
and F90 suspended ceilings.
DIN 4102 part 12 /
ABP approval
High quality materials
Long laying distances
Reduced cost of materials
Short installation time
One source for cables and
laying system
8
BETAflam
®
Safety and Communication Cables
Overview
FRT-MI
90
0.6 / 1 kV
LSOH
FRT-MI 90 / Single Core / Single Insulated
Page 10
FRT-MI 90 / Single Core / Double Insulated
Page 13
FR-MI 90
0.6 / 1 kV
LSOH
BS
6387
C.W.Z.
FR-MI 90 / Single Core / Single Insulated
Page 16
FR-MI 90 / Single Core / Double Insulated
Page 19
FR-MI
110
0.6 / 1 kV
LSOH
BS
6387
C.W.Z.
FR-MI 110 / Single Core / Single Insulated
Page 22
FR-MI 110 / Single Core / Double Insulated
Page 25
FR-MI 110 / Multicore
Page 28
FR-MI
110
armoured
0.6 / 1 kV
LSOH
BS
6387
C.W.Z.
FR-MI 110 / Multicore / Steel Tape Armour (STA)
Page 31
FR-MI 110 / Multicore / Steel Wire Armour
(SWA)
Page 34
FR-MI
110
300 / 500 V
LSOH
BS
6387
C.W.Z.
FR-MI 110 Comms Cables
Page 37
Safety and Communication Cables
9
FRT-MI
90
0.6 / 1 kV
LSOH
FRT-MI 90 / Single Core / Single Insulated
Page 10
FRT-MI 90 / Single Core / Double Insulated
Page 13
FR-MI 90
0.6 / 1 kV
LSOH
BS
6387
C.W.Z.
FR-MI 90 / Single Core / Single Insulated
Page 16
FR-MI 90 / Single Core / Double Insulated
Page 19
FR-MI
110
0.6 / 1 kV
LSOH
BS
6387
C.W.Z.
FR-MI 110 / Single Core / Single Insulated
Page 22
FR-MI 110 / Single Core / Double Insulated
Page 25
FR-MI 110 / Multicore
Page 28
FR-MI
110
armoured
0.6 / 1 kV
LSOH
BS
6387
C.W.Z.
FR-MI 110 / Multicore / Steel Tape Armour (STA)
Page 31
FR-MI 110 / Multicore / Steel Wire Armour
(SWA)
Page 34
FR-MI
110
300 / 500 V
LSOH
BS
6387
C.W.Z.
FR-MI 110 Comms Cables
Page 37
10
Application
Use
as
replacement
for
conventional
PVC
wiring
to
reduce
hazard-ous
gas
emission
and
avoid
secondary
damage
in
the
event
of
fire
.
Construction
Conductor:
Bare
annealed
copper,
acc.
IEC
60228
class
2
Insulation:
BETAflam
®mineral
copolymer
Core
identification:
Red,
Black
or
Green/Yellow
(other
colours
on
request)
Technical
specification
Rated
voltage:
U
0/U
0,6 / 1 kV
Test
voltage:
3,5 kV
/
50 Hz
Temperature
range:
Operation
temperature
from
– 30 °C
to
+ 90 °C
Laying
temperature
from
– 5 °C
to
+ 70 °C
Short
circuit
temperature
+ 250 °C
(temperature
peak
≤ 5 s)
Bending
radius:
During
laying
> 15 × outer
Fixed
installed
> 10 × outer
Laying
conditions:
For
electrical
installation
in
control
cabinets,
switchboards
or
other
closed
cable
wiring
systems.
Advantages
Halogen
and
silicone
free
Operating
temperature
90 °C
In
compliance
with
RoHS
directive
Mineral
filled
fire
resistant
materials
Space
saving
due
to
small
outer
diameter
Easy
to
handle
and
economical
to
install
FRT-MI 90 / Single Core / Single Insulated
BETAflam
®Fire Retardant Cores & Cables, 0.6 /1 kV, LSOH
Material
properties
Halogen
free:
IEC
60754-1;
BS
EN
50267-2-1;
VDE
0482-267-2-1
No
corrosive
gases:
IEC
60754-2;
BS
EN
50267-2-2;
VDE
0482-267-2-2
No
toxic
gases:
NES
02-713;
NF
C20-454;
BS
EN
50267-2-1
Low
smoke
density:
IEC
61034-1
&
-2;
BS
EN
61034-2;
VDE
0482-1034-1
&
-2
Fire
performance
Flame
retardant:
IEC
60332-1;
BS
EN
60332-1;
VDE
0482-332-1
No
flame
propagation:
IEC
60332-3-24;
EN
60332-3-24;
VDE
0482-266-1
&
-2-4
Safety and Communication Cables
11
= Onrequest g/y = Green/Yellow
1 ACcircuit,max.conductortemperature90 °C 2 Freeinair,spaced
3 Opentray,touching
Cross section
Partno. Core colour Conductor stranding Nominal thickness insulation Nominal diameter core Approx. weight
CurrentRating1 ACVoltageDrop FireLoad
1phase2 3phase3 1phase
system 3phase system mm² LSA n × mm mm mm kg / km A A mV / Am mV / Am kWh / m 1.5 302710 red 7 × 0.53 0.65 2.90 22 19 18 27.85 24.12 0.03 1.5 302485 black 7 × 0.53 0.65 2.90 22 19 18 27.85 24.12 0.03 1.5 302711 g/y 7 × 0.53 0.65 2.90 22 19 18 27.85 24.12 0.03 2.5 302712 red 7 × 0.68 0.70 3.45 33 26 24 17.08 14.79 0.04 2.5 219724 black 7 × 0.68 0.70 3.45 33 26 24 17.08 14.79 0.04 2.5 216456 g/y 7 × 0.68 0.70 3.45 33 26 24 17.08 14.79 0.04 4 302713 red 7 × 0.85 0.75 4.10 50 36 34 10.65 9.23 0.05 4 219818 black 7 × 0.85 0.75 4.10 50 36 34 10.65 9.23 0.05 4 216455 g/y 7 × 0.85 0.75 4.10 50 36 34 10.65 9.23 0.05 6 302715 red 7 × 1.04 0.80 4.60 69 46 43 7.14 6.18 0.06 6 222948 black 7 × 1.04 0.80 4.60 69 46 43 7.14 6.18 0.06 6 302716 g/y 7 × 1.04 0.80 4.60 69 46 43 7.14 6.18 0.06 10 302717 red 7 × 1.32 1.00 6.00 115 66 63 4.27 3.70 0.10 10 222949 black 7 × 1.32 1.00 6.00 115 66 63 4.27 3.70 0.10 10 216453 g/y 7 × 1.32 1.00 6.00 115 66 63 4.27 3.70 0.10 16 302719 red 7 × 1.72 1.10 7.00 174 89 85 2.71 2.34 0.12 16 222950 black 7 × 1.72 1.10 7.00 174 89 85 2.71 2.34 0.12 16 216452 g/y 7 × 1.72 1.10 7.00 174 89 85 2.71 2.34 0.12 25 302720 red 7 × 2.15 1.20 8.50 269 121 115 1.73 1.50 0.17 25 222951 black 7 × 2.15 1.20 8.50 269 121 115 1.73 1.50 0.17 25 302721 g/y 7 × 2.15 1.20 8.50 269 121 115 1.73 1.50 0.17 35 302722 red 7 × 2.52 1.30 9.80 367 152 145 1.27 1.10 0.22 35 222952 black 7 × 2.52 1.30 9.80 367 152 145 1.27 1.10 0.22 35 216450 g/y 7 × 2.52 1.30 9.80 367 152 145 1.27 1.10 0.22 50 302724 red 19 × 1.79 1.40 11.20 487 186 176 0.95 0.82 0.26 50 222953 black 19 × 1.79 1.40 11.20 487 186 176 0.95 0.82 0.26 50 216449 g/y 19 × 1.79 1.40 11.20 487 186 176 0.95 0.82 0.26 70 302725 red 19 × 2.15 1.60 13.30 697 240 230 0.68 0.59 0.36 70 222954 black 19 × 2.15 1.60 13.30 697 240 230 0.68 0.59 0.36 70 217893 g/y 19 × 2.15 1.60 13.30 697 240 240 0.68 0.59 0.36 95 302727 red 19 × 2.52 1.70 15.30 951 300 287 0.51 0.44 0.45 95 302491 black 19 × 2.52 1.70 15.30 951 300 287 0.51 0.44 0.45 95 302730 g/y 19 × 2.52 1.70 15.30 951 300 287 0.51 0.44 0.45 120 302731 red 37 × 2.02 1.80 17.20 1‘205 353 336 0.41 0.36 0.52 120 222955 black 37 × 2.02 1.80 17.20 1‘205 353 336 0.41 0.36 0.52 120 216447 g/y 37 × 2.02 1.80 17.20 1‘205 353 336 0.41 0.36 0.52 150 red 37 × 2.23 1.90 19.00 1‘478 408 387 0.35 0.30 0.63 150 222956 black 37 × 2.23 1.90 19.00 1‘478 408 387 0.35 0.30 0.63 150 g/y 37 × 2.23 1.90 19.00 1‘478 408 387 0.35 0.30 0.63 185 red 37 × 2.49 2.00 21.00 1‘829 474 449 0.29 0.25 0.74 185 302492 black 37 × 2.49 2.00 21.00 1‘829 474 449 0.29 0.25 0.74 185 g/y 37 × 2.49 2.00 21.00 1‘829 474 449 0.29 0.25 0.74 240 red 61 × 2.23 2.20 23.80 2‘401 568 539 0.24 0.20 0.92 240 222957 black 61 × 2.23 2.20 23.80 2‘401 568 539 0.24 0.20 0.92 240 g/y 61 × 2.23 2.20 23.80 2‘401 568 539 0.24 0.20 0.92
Safety and Communication Cables
12
= Onrequest g/y = Green/Yellow
1 ACcircuit,max.conductortemperature90 °C 2 Freeinair,spaced
3 Opentray,touching
Cross section
Partno. Core colour Conductor stranding Nominal thickness insulation Nominal diameter core Approx. weight
CurrentRating1 ACVoltageDrop FireLoad
1phase2 3phase3 1phase
system 3phase system mm² LSA n × mm mm mm kg / km A A mV / Am mV / Am kWh / m 300 red 61 × 2.52 2.40 27.50 3‘098 668 638 0.20 0.18 1.22 300 302493 black 61 × 2.52 2.40 27.50 3‘098 668 638 0.20 0.18 1.22 300 g/y 61 × 2.52 2.40 27.50 3‘098 668 638 0.20 0.18 1.22 400 red 61 × 2.85 2.60 30.90 3‘941 780 747 0.17 0.15 1.49 400 302486 black 61 × 2.85 2.60 30.90 3‘941 780 747 0.17 0.15 1.49 400 222411 g/y 61 × 2.85 2.60 30.90 3‘941 780 747 0.17 0.15 1.49 500 red 61 × 3.20 2.80 34.40 4‘950 902 865 0.15 0.13 1.80 500 302487 black 61 × 3.20 2.80 34.40 4‘950 902 865 0.15 0.13 1.80 500 g/y 61 × 3.20 2.80 34.40 4‘950 902 865 0.15 0.13 1.80 630 red 127 × 2.52 3.00 38.80 6‘364 1‘041 997 0.14 0.12 2.12 630 302488 black 127 × 2.52 3.00 38.80 6‘364 1‘041 997 0.14 0.12 2.12 630 g/y 127 × 2.52 3.00 38.80 6‘364 1‘041 997 0.14 0.12 2.12
Safety and Communication Cables BETAflam® Fire Retardant Cores & Cables, 0.6 /1 kV, LSOH
13
Application
Use
as
replacement
for
conventional
PVC
wiring
to
reduce
hazard-ous
gas
emission
and
avoid
secondary
damage
in
the
event
of
fire.
Construction
Conductor:
Bare
annealed
copper,
acc.
IEC
60228
class
2
Insulation:
BETAflam
®mineral
copolymer
Core
identification:
Black,
White
or
Green-Yellow
(other
colours
on
request)
Sheath:
BETAflam
®mineral
copolymer,
Orange
(Black
on
request)
Technical
specification
Rated
voltage:
U
0/U
0.6 / 1 kV
Test
voltage:
3.5 kV
/
50 Hz
Temperature
range:
Operation
temperature
from
– 30 °C
to
+ 90 °C
Laying
temperature
from
– 5 °C
to
+ 70 °C
Short
circuit
temperature
+ 250 °C
(temperature
peak
≤ 5 s)
Bending
radius:
During
laying
> 15 × outer
Fixed
installed
> 10 × outer
Laying
conditions:
For
fixed
installation
indoor,
in
air,
trays
or
dry
tubes/ducts.
Outdoor
laying
only
when
protected
from
direct
sunlight
and
other
external
impacts.
Advantages
Halogen
and
silicone
free
Operating
temperature
90 °C
In
compliance
with
RoHS
directive
Mineral
filled
fire
resistant
materials
Space
saving
due
to
small
outer
diameter
Easy
to
handle
and
economical
to
install
FRT-MI 90 / Single Core / Double Insulated
BETAflam
®Fire Retardant Cores & Cables, 0.6 /1 kV, LSOH
Material
properties
Halogen
free:
IEC
60754-1;
BS
EN
50267-2-1;
VDE
0482-267-2-1
No
corrosive
gases:
IEC
60754-2;
BS
EN
50267-2-2;
VDE
0482-267-2-2
No
toxic
gases:
NES
02-713;
NF
C20-454;
BS
EN
50267-2-1
Low
smoke
density:
IEC
61034-1
&
-2;
BS
EN
61034-2;
VDE
0482-1034-1
&
-2
Fire
performance
Flame
retardant:
IEC
60332-1;
BS
EN
60332-1;
VDE
0482-332-1
No
flame
propagation:
IEC
60332-3-24;
EN
60332-3-24;
VDE
0482-266-1
&
-2-4
14
= Onrequest g/y = Green/Yellow
1 ACcircuit,max.conductortemperature90 °C 2 Freeinair,spaced
3 Opentray,touching
Cross section
Partno. Core colour Conductor stranding Nominal thickness insulation Nominal diameter core Nominal thickness sheath Nominal diameter cable Approx. weight
CurrentRating1 ACVoltageDrop FireLoad
1phase2 3phase3 1phase
system 3phase system mm² LSA n × mm mm mm mm mm kg / km A A mV / Am mV / Am kWh / m 1.5 white 7 × 0.53 0.65 2.90 0.95 4.80 40 23 21 27.88 24.14 0.11 1.5 302733 black 7 × 0.53 0.65 2.90 0.95 4.80 40 23 21 27.88 24.14 0.11 1.5 g/y 7 × 0.53 0.65 2.90 0.95 4.80 40 23 21 27.88 24.14 0.11 2.5 white 7 × 0.68 0.70 3.45 0.95 5.35 54 31 29 17.11 14.81 0.13 2.5 302734 black 7 × 0.68 0.70 3.45 0.95 5.35 54 31 29 17.11 14.81 0.13 2.5 g/y 7 × 0.68 0.70 3.45 0.95 5.35 54 31 29 17.11 14.81 0.13 4 white 7 × 0.85 0.75 4.10 1.00 6.10 75 41 38 10.68 9.24 0.16 4 302735 black 7 × 0.85 0.75 4.10 1.00 6.10 75 41 38 10.68 9.24 0.16 4 g/y 7 × 0.85 0.75 4.10 1.00 6.10 75 41 38 10.68 9.24 0.16 6 white 7 × 1.04 0.80 4.60 1.05 6.70 99 52 47 7.17 6.20 0.19 6 302736 black 7 × 1.04 0.80 4.60 1.05 6.70 99 52 47 7.17 6.20 0.19 6 g/y 7 × 1.04 0.80 4.60 1.05 6.70 99 52 47 7.17 6.20 0.19 10 white 7 × 1.32 1.00 6.00 1.40 8.80 166 75 70 4.29 3.72 0.31 10 216444 black 7 × 1.32 1.00 6.00 1.40 8.80 166 75 70 4.29 3.72 0.31 10 g/y 7 × 1.32 1.00 6.00 1.40 8.80 166 75 70 4.29 3.72 0.31 16 white 7 × 1.72 1.10 7.00 1.40 9.80 232 99 93 2.73 2.36 0.35 16 302737 black 7 × 1.72 1.10 7.00 1.40 9.80 232 99 93 2.73 2.36 0.35 16 g/y 7 × 1.72 1.10 7.00 1.40 9.80 232 99 93 2.73 2.36 0.35 25 white 7 × 2.15 1.20 8.50 1.40 11.30 338 133 126 1.75 1.51 0.43 25 302738 black 7 × 2.15 1.20 8.50 1.40 11.30 338 133 126 1.75 1.51 0.43 25 g/y 7 × 2.15 1.20 8.50 1.40 11.30 338 133 126 1.75 1.51 0.43 35 white 7 × 2.52 1.30 9.80 1.40 12.60 445 164 154 1.29 1.11 0.49 35 217377 black 7 × 2.52 1.30 9.80 1.40 12.60 445 164 154 1.29 1.11 0.49 35 g/y 7 × 2.52 1.30 9.80 1.40 12.60 445 164 154 1.29 1.11 0.49 50 white 19 × 1.79 1.40 11.20 1.40 14.00 574 200 189 0.97 0.83 0.60 50 216441 black 19 × 1.79 1.40 11.20 1.40 14.00 574 200 189 0.97 0.83 0.60 50 g/y 19 × 1.79 1.40 11.20 1.40 14.00 574 200 189 0.97 0.83 0.60 70 white 19 × 2.15 1.60 13.30 1.45 16.20 803 255 241 0.69 0.60 0.72 70 302739 black 19 × 2.15 1.60 13.30 1.45 16.20 803 255 241 0.69 0.60 0.72 70 g/y 19 × 2.15 1.60 13.30 1.45 16.20 803 255 241 0.69 0.60 0.72 95 white 19 × 2.52 1.70 15.30 1.55 18.40 1‘081 316 295 0.52 0.45 0.91 95 302740 black 19 × 2.52 1.70 15.30 1.55 18.40 1‘081 316 295 0.52 0.45 0.91 95 g/y 19 × 2.52 1.70 15.30 1.55 18.40 1‘081 316 295 0.52 0.45 0.91 120 white 37 × 2.02 1.80 17.20 1.70 20.40 1‘355 371 347 0.43 0.37 1.03 120 302741 black 37 × 2.02 1.80 17.20 1.70 20.40 1‘355 371 347 0.43 0.37 1.03 120 g/y 37 × 2.02 1.80 17.20 1.70 20.40 1‘355 371 347 0.43 0.37 1.03 150 white 37 × 2.23 1.90 19.00 1.70 22.40 1‘652 426 399 0.36 0.31 1.23 150 302742 black 37 × 2.23 1.90 19.00 1.70 22.40 1‘652 426 399 0.36 0.31 1.23 150 g/y 37 × 2.23 1.90 19.00 1.70 22.40 1‘652 426 399 0.36 0.31 1.23 185 white 37 × 2.49 2.00 21.00 1.80 24.60 2‘032 494 461 0.30 0.26 1.47 185 302743 black 37 × 2.49 2.00 21.00 1.80 24.60 2‘032 494 461 0.30 0.26 1.47 185 g/y 37 × 2.49 2.00 21.00 1.80 24.60 2‘032 494 461 0.30 0.26 1.47 240 white 61 × 2.23 2.20 23.80 1.90 27.60 2‘643 589 550 0.25 0.21 1.79 240 302745 black 61 × 2.23 2.20 23.80 1.90 27.60 2‘643 589 550 0.25 0.21 1.79 240 g/y 61 × 2.23 2.20 23.80 1.90 27.60 2‘643 589 550 0.25 0.21 1.79
Safety and Communication Cables BETAflam® Fire Retardant Cores & Cables, 0.6 /1 kV, LSOH
15
= Onrequest g/y = Green/Yellow
1 ACcircuit,max.conductortemperature90 °C 2 Freeinair,spaced
3 Opentray,touching
Cross section
Partno. Core colour Conductor stranding Nominal thickness insulation Nominal diameter core Nominal thickness sheath Nominal diameter cable Approx. weight
CurrentRating1 ACVoltageDrop FireLoad
1phase2 3phase3 1phase
system 3phase system mm² LSA n × mm mm mm mm mm kg / km A A mV / Am mV / Am kWh / m 300 white 61 × 2.52 2.40 27.50 2.00 31.50 3‘391 691 647 0.21 0.18 2.24 300 302746 black 61 × 2.52 2.40 27.50 2.00 31.50 3‘391 691 647 0.21 0.18 2.24 300 g/y 61 × 2.52 2.40 27.50 2.00 31.50 3‘391 691 647 0.21 0.18 2.24 400 white 61 × 2.85 2.60 30.90 2.10 35.10 4‘285 805 756 0.18 0.16 2.55 400 302747 black 61 × 2.85 2.60 30.90 2.10 35.10 4‘285 805 756 0.18 0.16 2.55 400 g/y 61 × 2.85 2.60 30.90 2.10 35.10 4‘285 805 756 0.18 0.16 2.55 500 white 61 × 3.20 2.80 34.40 2.20 38.80 5‘350 931 873 0.16 0.14 3.11 500 302748 black 61 × 3.20 2.80 34.40 2.20 38.80 5‘350 931 873 0.16 0.14 3.11 500 g/y 61 × 3.20 2.80 34.40 2.20 38.80 5‘350 931 873 0.16 0.14 3.11 630 white 127 × 2.52 3.00 38.80 2.40 43.60 6‘855 1‘076 1‘005 0.14 0.12 3.84 630 302749 black 127 × 2.52 3.00 38.80 2.40 43.60 6‘855 1‘076 1‘005 0.14 0.12 3.84 630 g/y 127 × 2.52 3.00 38.80 2.40 43.60 6‘855 1‘076 1‘005 0.14 0.12 3.84
Safety and Communication Cables
16
Application
Single
cores
for
use
in
cable
wiring
systems
with
improved
fire
performance
and
circuit
integrity.
Use
for:
Fire
Alarm
circuits,
Fire
Detection
circuits,
Emergency
signal / Control
circuits,
Fire
fighting
systems
(water
pumps),
Smoke
Exhaust
Systems
etc.
Especially
recommended
in
areas
where
human
and
animal
live
as
well
as
valuable
property
are
exposed
to
high
risk
in
case
of
fire.
Construction
Conductor:
Bare
annealed
copper,
acc.
IEC
60228
class
2
Flame
barrier:
MICA
tape
Insulation:
BETAflam
®mineral
copolymer
Core
identification:
Red,
Black
or
Green-Yellow
(other
colours
on
request)
Technical
specification
Rated
voltage:
U
0/U
0.6 / 1 kV
Test
voltage:
4 kV
/
50 Hz
Temperature
range:
Operation
temperature
from
– 30 °C
to
+ 90 °C
Laying
temperature
from
– 5 °C
to
+ 70 °C
Short
circuit
temperature
+ 250 °C
(temperature
peak
≤ 5 s)
Bending
radius:
During
laying
> 10 × outer
Fixed
installed
> 6 × outer
Laying
conditions:
Use
for
electrical
installations
in
control
cabinets,
switchboards,
or
other
closed
cable
wiring
systems.
Advantages
High
safety
standard:
BS
6387
C.W.Z,
fully
tested
by
LPCB
Halogen
and
silicone
free
Operating
temperature
90 °C
In
compliance
with
RoHS
directive
Mineral
filled
fire
resistant
materials
Space
saving
installation
due
to
small
outer
diameter
FR-MI 90 / Single Core / Single Insulated
BETAflam
®Fire Resistant Safety Cables 0.6 /1 kV, acc. to BS 6387 C.W.Z., LSOH
Material
properties
Halogen
free:
IEC
60754-1;
BS
EN
50267-2-1;
VDE
0482-267-2-1
No
corrosive
gases:
IEC
60754-2;
BS
EN
50267-2-2;
VDE
0482-267-2-2
No
toxic
gases:
NES
02-713;
NF
C20-454;
BS
EN
50267-2-1
Low
smoke
density:
IEC
61034-1
&
-2;
BS
EN
61034-2;
VDE
0482-1034-1
&
-2
Fire
performance
Flame
retardant:
IEC
60332-1;
BS
EN
60332-1;
VDE
0482-332-1
No
flame
propagation:
IEC
60332-3-24;
EN
60332-3-24;
VDE
0482-266-1
&
-2-4
Circuit
integrity:
BS
6387
C.W.Z.
/
≤ 20 mm
IEC
60331-21;
VDE
0472-814
Safety and Communication Cables
17
= Onrequest g/y = Green/Yellow
1 ACcircuit,max.conductortemperature90 °C 2 Freeinair,spaced
3 Opentray,touching
Cross section
Partno. Core colour Conductor stranding Nominal thickness insulation Nominal diameter core Approx. weight
CurrentRating1 ACVoltageDrop FireLoad
1phase2 3phase3 1phase
system 3phase system mm² LSA n × mm mm mm kg / km A A mV / Am mV / Am kWh / m 1.5 301789 red 7 × 0.53 0.60 3.45 25 26 24 25.05 21.60 0.03 1.5 301790 black 7 × 0.53 0.60 3.45 25 26 24 25.05 21.60 0.03 1.5 301791 g/y 7 × 0.53 0.60 3.45 25 26 24 25.05 21.60 0.03 2.5 301792 red 7 × 0.68 0.68 4.00 37 35 33 15.47 13.30 0.04 2.5 301793 black 7 × 0.68 0.68 4.00 37 35 33 15.47 13.30 0.04 2.5 301794 g/y 7 × 0.68 0.68 4.00 37 35 33 15.47 13.30 0.04 4 301795 red 7 × 0.85 0.78 4.65 55 47 44 9.74 8.34 0.05 4 301796 black 7 × 0.85 0.78 4.65 55 47 44 9.74 8.34 0.05 4 301797 g/y 7 × 0.85 0.78 4.65 55 47 44 9.74 8.34 0.05 6 301798 red 7 × 1.04 0.83 5.15 75 61 57 6.61 5.63 0.06 6 301799 black 7 × 1.04 0.83 5.15 75 61 57 6.61 5.63 0.06 6 301800 g/y 7 × 1.04 0.83 5.15 75 61 57 6.61 5.63 0.06 10 301801 red 7 × 1.32 1.05 6.65 121 86 79 4.05 3.42 0.11 10 301802 black 7 × 1.32 1.05 6.65 121 86 79 4.05 3.42 0.11 10 301803 g/y 7 × 1.32 1.05 6.65 121 86 79 4.05 3.42 0.11 16 301805 red 7 × 1.72 1.05 7.50 181 115 105 2.66 2.21 0.12 16 301806 black 7 × 1.72 1.05 7.50 181 115 105 2.66 2.21 0.12 16 301807 g/y 7 × 1.72 1.05 7.50 181 115 105 2.66 2.21 0.12 25 301808 red 7 × 2.15 1.20 9.05 276 156 141 1.79 1.46 0.17 25 301809 black 7 × 2.15 1.20 9.05 276 156 141 1.79 1.46 0.17 25 301810 g/y 7 × 2.15 1.20 9.05 276 156 141 1.79 1.46 0.17 35 301811 red 7 × 2.52 1.20 10.20 369 194 174 1.37 1.10 0.19 35 301812 black 7 × 2.52 1.20 10.20 369 194 174 1.37 1.10 0.19 35 301813 g/y 7 × 2.52 1.20 10.20 369 194 174 1.37 1.10 0.19 50 301814 red 19 × 1.79 1.40 11.90 502 239 212 1.09 0.85 0.26 50 301815 black 19 × 1.79 1.40 11.90 502 239 212 1.09 0.85 0.26 50 301816 g/y 19 × 1.79 1.40 11.90 502 239 212 1.09 0.85 0.26 70 301817 red 19 × 2.15 1.40 13.60 699 304 273 0.84 0.64 0.31 70 301818 black 19 × 2.15 1.40 13.60 699 304 273 0.84 0.64 0.31 70 301819 g/y 19 × 2.15 1.40 13.60 699 304 273 0.84 0.64 0.31 95 301820 red 19 × 2.52 1.60 15.80 959 381 336 0.68 0.50 0.41 95 301821 black 19 × 2.52 1.60 15.80 959 381 336 0.68 0.50 0.41 95
g/y 19 × 2.52 1.60 15.80 959 381 336 0.68 0.50 0.41 120 301822 red 37 × 2.02 1.60 17.50 1‘208 447 395 0.60 0.43 0.46 120 301823 black 37 × 2.02 1.60 17.50 1‘208 447 395 0.60 0.43 0.46 120
g/y 37 × 2.02 1.60 17.50 1‘208 447 395 0.60 0.43 0.46 150 301824 red 37 × 2.23 1.80 19.50 1‘483 517 452 0.54 0.38 0.57 150 301825 black 37 × 2.23 1.80 19.50 1‘483 517 452 0.54 0.38 0.57 150
g/y 37 × 2.23 1.80 19.50 1‘483 517 452 0.54 0.38 0.57 185 301826 red 37 × 2.49 2.00 21.70 1‘845 603 525 0.49 0.33 0.71 185 301827 black 37 × 2.49 2.00 21.70 1‘845 603 525 0.49 0.33 0.71 185
g/y 37 × 2.49 2.00 21.70 1‘845 603 525 0.49 0.33 0.71 240 301828 red 61 × 2.23 2.20 24.50 2‘418 724 627 0.44 0.29 0.88 240 301829 black 61 × 2.23 2.20 24.50 2‘418 724 627 0.44 0.29 0.88 240
g/y 61 × 2.23 2.20 24.50 2‘418 724 627 0.44 0.29 0.88Safety and Communication Cables
18
= Onrequest g/y = Green/Yellow
1 ACcircuit,max.conductortemperature90 °C 2 Freeinair,spaced
3 Opentray,touching
Cross section
Partno. Core colour Conductor stranding Nominal thickness insulation Nominal diameter core Approx. weight
CurrentRating1 ACVoltageDrop FireLoad
1phase2 3phase3 1phase
system 3phase system mm² LSA n × mm mm mm kg / km A A mV / Am mV / Am kWh / m 300 301830 red 61 × 2.52 2.45 28.30 3‘109 856 737 0.41 0.26 1.14 300 301831 black 61 × 2.52 2.45 28.30 3‘109 856 737 0.41 0.26 1.14 300
g/y 61 × 2.52 2.45 28.30 3‘109 856 737 0.41 0.26 1.14 400 301832 red 61 × 2.85 2.65 31.70 3‘948 1‘007 862 0.38 0.24 1.38 400 301833 black 61 × 2.85 2.65 31.70 3‘948 1‘007 862 0.38 0.24 1.38 400
g/y 61 × 2.85 2.65 31.70 3‘948 1‘007 862 0.38 0.24 1.38 500 301834 red 61 × 3.20 2.85 35.30 4‘955 1‘179 1‘008 0.36 0.22 1.66 500 301835 black 61 × 3.20 2.85 35.30 4‘955 1‘179 1‘008 0.36 0.22 1.66 500
g/y 61 × 3.20 2.85 35.30 4‘955 1‘179 1‘008 0.36 0.22 1.66 630 301836 red 127 × 2.52 3.05 39.70 6‘384 1‘385 1‘184 0.34 0.21 2.01 630 301837 black 127 × 2.52 3.05 39.70 6‘384 1‘385 1‘184 0.34 0.21 2.01 630
g/y 127 × 2.52 3.05 39.70 6‘384 1‘385 1‘184 0.34 0.21 2.01Safety and Communication Cables FR-MI 90 / Single Core / Single Insulated
19
Application
Power
cable
0.6 / 1 kV
for
fixed
installation
in
cable
systems
with
improved
fire
performance
and
circuit
integrity.
Use
for:
Fire
Alarm
circuits,
Fire
Detection
circuits,
Emergency
signal
/
Control
circuits,
Fire
fighting
systems
(water
pumps),
Smoke
Exhaust
Systems
etc.
Especially
recommended
in
areas
where
human
and
animal
live
as
well
as
valuable
property
are
exposed
to
high
risk
in
case
of
fire.
Construction
Conductor:
Bare
annealed
copper,
acc.
IEC
60228
class
2
Flame
barrier:
MICA
tape
Insulation:
BETAflam
®mineral
copolymer
Core
identification:
White,
Black
or
Green-Yellow
(other
colours
on
request)
Sheath:
BETAflam
®mineral
copolymer,
Orange
Technical
specification
Rated
voltage:
U
0/U
0.6 / 1 kV
Test
voltage:
4 kV
/
50 Hz
Temperature
range:
Operation
temperature
from
– 30 °C
to
+ 90 °C
Laying
temperature
from
– 5 °C
to
+ 70 °C
Short
circuit
temperature
+ 250 °C
(temperature
peak
≤ 5 s)
Advantages
High
safety
standard:
BS
6387
C.W.Z,
fully
tested
by
LPCB
Halogen
and
silicone
free
Operating
temperature
90 °C
In
compliance
with
RoHS
directive
Mineral
filled
fire
resistant
materials
FR-MI 90 / Single Core / Double Insulated
BETAflam
®Fire Resistant Safety Cables 0.6 /1 kV, acc. to BS 6387 C.W.Z., LSOH
Bending
radius:
During
laying
> 10 × outer
Fixed
installed
> 6 × outer
Laying
conditions:
For
fixed
installation
indoor,
in
air,
trays
or
dry
tubes/ducts.
Outdoor
laying
only
when
protected
from
direct
sunlight
and
other
external
impacts.
Material
properties
Halogen
free:
IEC
60754-1;
BS
EN
50267-2-1;
VDE
0482-267-2-1
No
corrosive
gases:
IEC
60754-2;
BS
EN
50267-2-2;
VDE
0482-267-2-2
No
toxic
gases:
NES
02-713;
NF
C20-454;
BS
EN
50267-2-1
Low
smoke
density:
IEC
61034-1
&
-2;
BS
EN
61034-2;
VDE
0482-1034-1
&
-2
Fire
performance
Flame
retardant:
IEC
60332-1;
BS
EN
60332-1;
VDE
0482-332-1
No
flame
propagation:
IEC
60332-3-24;
EN
60332-3-24;
VDE
0482-266-1
&
-2-4
Circuit
integrity:
BS
6387
C.W.Z.
/
≤ 20 mm
IEC
60331-21;
VDE
0472-814
20
= Onrequest g/y = Green/Yellow
1 ACcircuit,max.conductortemperature90 °C 2 Freeinair,spaced
3 Opentray,touching
Cross section
Partno. Core colour Conductor stranding Nominal thickness insulation Nominal diameter core Nominal thickness sheath Nominal diameter cable Approx. weight
CurrentRating1 ACVoltageDrop FireLoad
1phase2 3phase3 1phase
system 3phase system mm² LSA n × mm mm mm mm mm kg / km A A mV / Am mV / Am kWh / m 1.5 white 7 × 0.53 0.60 3.45 0.95 5.35 46 26 24 24.90 21.52 0.11 1.5 301838 black 7 × 0.53 0.60 3.45 0.95 5.35 46 26 24 24.90 21.52 0.11 1.5 g/y 7 × 0.53 0.60 3.45 0.95 5.35 46 26 24 24.90 21.52 0.11 2.5 white 7 × 0.68 0.68 4.00 1.00 6.00 63 35 33 15.32 13.22 0.13 2.5 301839 black 7 × 0.68 0.68 4.00 1.00 6.00 63 35 33 15.32 13.22 0.13 2.5 g/y 7 × 0.68 0.68 4.00 1.00 6.00 63 35 33 15.32 13.22 0.13 4 white 7 × 0.85 0.78 4.65 1.05 6.75 78 47 44 9.55 8.27 0.16 4 301840 black 7 × 0.85 0.78 4.65 1.05 6.75 78 47 44 9.55 8.27 0.16 4 g/y 7 × 0.85 0.78 4.65 1.05 6.75 78 47 44 9.55 8.27 0.16 6 white 7 × 1.04 0.83 5.15 1.05 7.25 108 61 57 6.47 5.56 0.19 6 301841 black 7 × 1.04 0.83 5.15 1.05 7.25 108 61 57 6.47 5.56 0.19 6 g/y 7 × 1.04 0.83 5.15 1.05 7.25 108 61 57 6.47 5.56 0.19 10 white 7 × 1.32 1.05 6.65 1.40 9.45 177 86 79 3.92 3.35 0.31 10 301842 black 7 × 1.32 1.05 6.65 1.40 9.45 177 86 79 3.92 3.35 0.31 10 g/y 7 × 1.32 1.05 6.65 1.40 9.45 177 86 79 3.92 3.35 0.31 16 white 7 × 1.72 1.05 7.50 1.40 10.30 250 115 105 2.53 2.14 0.35 16 301843 black 7 × 1.72 1.05 7.50 1.40 10.30 250 115 105 2.53 2.14 0.35 16 g/y 7 × 1.72 1.05 7.50 1.40 10.30 250 115 105 2.53 2.14 0.35 25 white 7 × 2.15 1.20 9.05 1.40 11.85 355 156 141 1.66 1.39 0.43 25 301844 black 7 × 2.15 1.20 9.05 1.40 11.85 355 156 141 1.66 1.39 0.43 25 g/y 7 × 2.15 1.20 9.05 1.40 11.85 355 156 141 1.66 1.39 0.43 35 white 7 × 2.52 1.20 10.20 1.40 13.00 456 194 174 1.24 1.03 0.49 35 301845 black 7 × 2.52 1.20 10.20 1.40 13.00 456 194 174 1.24 1.03 0.49 35 g/y 7 × 2.52 1.20 10.20 1.40 13.00 456 194 174 1.24 1.03 0.49 50 white 19 × 1.79 1.40 11.90 1.40 14.70 600 239 212 0.96 0.78 0.60 50 301846 black 19 × 1.79 1.40 11.90 1.40 14.70 600 239 212 0.96 0.78 0.60 50 g/y 19 × 1.79 1.40 11.90 1.40 14.70 600 239 212 0.96 0.78 0.60 70 white 19 × 2.15 1.40 13.60 1.50 16.60 813 304 273 0.71 0.57 0.72 70 301847 black 19 × 2.15 1.40 13.60 1.50 16.60 813 304 273 0.71 0.57 0.72 70 g/y 19 × 2.15 1.40 13.60 1.50 16.60 813 304 273 0.71 0.57 0.72 95 white 19 × 2.52 1.60 15.80 1.60 19.00 1‘101 381 336 0.55 0.43 0.91 95 301848 black 19 × 2.52 1.60 15.80 1.60 19.00 1‘101 381 336 0.55 0.43 0.91 95 g/y 19 × 2.52 1.60 15.80 1.60 19.00 1‘101 381 336 0.55 0.43 0.91 120 white 37 × 2.02 1.60 17.50 1.65 20.80 1‘372 447 395 0.47 0.36 1.03 120 301849 black 37 × 2.02 1.60 17.50 1.65 20.80 1‘372 447 395 0.47 0.36 1.03 120 g/y 37 × 2.02 1.60 17.50 1.65 20.80 1‘372 447 395 0.47 0.36 1.03 150 white 37 × 2.23 1.80 19.50 1.70 22.90 1‘645 517 452 0.41 0.31 1.23 150 301850 black 37 × 2.23 1.80 19.50 1.70 22.90 1‘645 517 452 0.41 0.31 1.23 150 g/y 37 × 2.23 1.80 19.50 1.70 22.90 1‘645 517 452 0.41 0.31 1.23 185 white 37 × 2.49 2.00 21.70 1.80 25.30 2‘021 603 525 0.36 0.27 1.47 185 301851 black 37 × 2.49 2.00 21.70 1.80 25.30 2‘021 603 525 0.36 0.27 1.47 185 g/y 37 × 2.49 2.00 21.70 1.80 25.30 2‘021 603 525 0.36 0.27 1.47 240 white 61 × 2.23 2.20 24.50 1.90 28.30 2‘598 724 627 0.31 0.22 1.81 240 301852 black 61 × 2.23 2.20 24.50 1.90 28.30 2‘598 724 627 0.31 0.22 1.81 240 g/y 61 × 2.23 2.20 24.50 1.90 28.30 2‘598 724 627 0.31 0.22 1.81
Safety and Communication Cables FR-MI 90 / Single Core / Double Insulated
21
= Onrequest g/y = Green/Yellow
1 ACcircuit,max.conductortemperature90 °C 2 Freeinair,spaced
3 Opentray,touching
Cross section
Partno. Core colour Conductor stranding Nominal thickness insulation Nominal diameter core Nominal thickness sheath Nominal diameter cable Approx. weight
CurrentRating1 ACVoltageDrop FireLoad
1phase2 3phase3 1phase
system 3phase system mm² LSA n × mm mm mm mm mm kg / km A A mV / Am mV / Am kWh / m 300 white 61 × 2.52 2.45 28.30 2.00 32.30 3‘440 856 737 0.28 0.20 2.31 300 301853 black 61 × 2.52 2.45 28.30 2.00 32.30 3‘440 856 737 0.28 0.20 2.31 300 g/y 61 × 2.52 2.45 28.30 2.00 32.30 3‘440 856 737 0.28 0.20 2.31 400 white 61 × 2.85 2.65 31.70 2.15 36.00 4‘394 1‘007 862 0.25 0.17 2.65 400 301854 black 61 × 2.85 2.65 31.70 2.15 36.00 4‘394 1‘007 862 0.25 0.17 2.65 400 g/y 61 × 2.85 2.65 31.70 2.15 36.00 4‘394 1‘007 862 0.25 0.17 2.65 500 white 61 × 3.20 2.85 35.30 2.30 39.90 5‘435 1‘179 1‘008 0.23 0.16 3.36 500 301855 black 61 × 3.20 2.85 35.30 2.30 39.90 5‘435 1‘179 1‘008 0.23 0.16 3.36 500 g/y 61 × 3.20 2.85 35.30 2.30 39.90 5‘435 1‘179 1‘008 0.23 0.16 3.36 630 white 127 × 2.52 3.05 39.70 2.40 44.50 6‘965 1‘385 1‘184 0.21 0.14 4.06 630 301856 black 127 × 2.52 3.05 39.70 2.40 44.50 6‘965 1‘385 1‘184 0.21 0.14 4.06 630 g/y 127 × 2.52 3.05 39.70 2.40 44.50 6‘965 1‘385 1‘184 0.21 0.14 4.06
Safety and Communication Cables
22
Application
Single
cores
for
use
in
cable
wiring
systems
with
improved
fire
performance
and
circuit
integrity.
For
use:
Fire
Alarm
circuits,
Fire
Detection
circuits,
Emergency
signal
/
Control
circuits,
Fire
fighting
systems
(water
pumps),
Smoke
Exhaust
Systems
etc.
Especially
recommended
in
areas
where
human
and
animal
live
as
well
as
valuable
property
are
exposed
to
high
risk
in
case
of
fire.
Construction
Conductor:
Bare
annealed
copper,
acc.
IEC
60228
class
2
Flame
barrier:
MICA
tape
Insulation:
BETAflam
®mineral
copolymer,
cross-linked
(other
colours
on
request)
Core
identification:
Red,
Black
or
Green-Yellow
(other
colours
on
request)
Technical
specification
Rated
voltage:
U
0/U
0.6 / 1 kV
Test
voltage:
4 kV
/
50 Hz
Temperature
range:
Operation
temperature
from
– 30 °C
to
+ 110 °C
Laying
temperature
from
– 5 °C
to
+ 70 °C
Short
circuit
temperature
+ 280 °C
(temperature
peak
≤ 5 s)
Advantages
High
safety
standard:
BS
6387
C.W.Z,
fully
tested
by
LPCB
Halogen
and
silicone
free
Operating
temperature
110 °C
In
compliance
with
RoHS
directive
Mineral
filled
fire
resistant
materials
Space
saving
installation
due
to
small
outer
diameter
FR-MI 110 / Single Core / Single Insulated
BETAflam
®Fire Resistant Safety Cables 0.6 /1 kV, acc. to BS 6387 C.W.Z., LSOH
Bending
radius:
During
laying
> 10 × outer
Fixed
installed
> 6 × outer
Laying
conditions:
Use
for
electrical
installations
in
control
cabinets,
switchboards,
or
other
closed
cable
wiring
systems
Material
properties
Halogen
free:
IEC
60754-1;
BS
EN
50267-2-1;
VDE
0482-267-2-1
No
corrosive
gases:
IEC
60754-2;
BS
EN
50267-2-2;
VDE
0482-267-2-2
No
toxic
gases:
NES
02-713;
NF
C20-454;
BS
EN
50267-2-1
Low
smoke
density:
IEC
61034-1
&
-2;
BS
EN
61034-2;
VDE
0482-1034-1
&
-2
Fire
performance
Flame
retardant:
IEC
60332-1;
BS
EN
60332-1;
VDE
0482-332-1
No
flame
propagation:
IEC
60332-3-24;
EN
60332-3-24;
VDE
0482-266-1
&
-2-4
Circuit
integrity:
BS
6387
C.W.Z.
/
≤ 20 mm
IEC
60331-21;
VDE
0472-814
Safety and Communication Cables
23
= Onrequest g/y = Green/Yellow
1 ACcircuit,max.conductortemperature90 °C 2 Freeinair,spaced
3 Opentray,touching
Cross section
Partno. Core colour Conductor stranding Nominal thickness insulation Nominal diameter core Approx. weight
CurrentRating1 ACVoltageDrop FireLoad
1phase2 3phase3 1phase
system 3phase system mm² LSA n × mm mm mm kg / km A A mV / Am mV / Am kWh / m 1.5 218945 red 7 × 0.53 0.60 3.45 25 27 26 25.05 21.60 0.03 1.5 303590 brown 7 × 0.53 0.60 3.45 25 27 26 25.05 21.60 0.03 1.5 218946 black 7 × 0.53 0.60 3.45 25 27 26 25.05 21.60 0.03 1.5 303589 blue 7 × 0.53 0.60 3.45 25 27 26 25.05 21.60 0.03 1.5 301742 g/y 7 × 0.53 0.60 3.45 25 27 26 25.05 21.60 0.03 2.5 218947 red 7 × 0.68 0.68 4.00 37 38 36 15.47 13.30 0.04 2.5 303592 brown 7 × 0.68 0.68 4.00 37 38 36 15.47 13.30 0.04 2.5 218948 black 7 × 0.68 0.68 4.00 37 38 36 15.47 13.30 0.04 2.5 303591 blue 7 × 0.68 0.68 4.00 37 38 36 15.47 13.30 0.04 2.5 220893 g/y 7 × 0.68 0.68 4.00 37 38 36 15.47 13.30 0.04 4 215212 red 7 × 0.85 0.78 4.65 55 51 48 9.74 8.34 0.05 4 303593 brown 7 × 0.85 0.78 4.65 55 51 48 9.74 8.34 0.05 4 215544 black 7 × 0.85 0.78 4.65 55 51 48 9.74 8.34 0.05 4 215142 g/y 7 × 0.85 0.78 4.65 55 51 48 9.74 8.34 0.05 6 215889 red 7 × 1.04 0.83 5.15 75 65 62 6.61 5.63 0.06 6 215214 black 7 × 1.04 0.83 5.15 75 65 62 6.61 5.63 0.06 6 219233 g/y 7 × 1.04 0.83 5.15 75 65 62 6.61 5.63 0.06 10 215800 red 7 × 1.32 1.05 6.65 121 90 85 4.05 3.42 0.11 10 217300 black 7 × 1.32 1.05 6.65 121 90 85 4.05 3.42 0.11 10 220894 g/y 7 × 1.32 1.05 6.65 121 90 85 4.05 3.42 0.11 16 215801 red 7 × 1.72 1.05 7.50 181 121 114 2.66 2.21 0.12 16 301743 black 7 × 1.72 1.05 7.50 181 121 114 2.66 2.21 0.12 16 301744 g/y 7 × 1.72 1.05 7.50 181 121 114 2.66 2.21 0.12 25 216106 red 7 × 2.15 1.20 9.05 276 163 155 1.79 1.46 0.17 25 301745 black 7 × 2.15 1.20 9.05 276 163 155 1.79 1.46 0.17 25 301746 g/y 7 × 2.15 1.20 9.05 276 163 155 1.79 1.46 0.17 35 216758 red 7 × 2.52 1.20 10.20 369 202 190 1.37 1.10 0.19 35 301747 black 7 × 2.52 1.20 10.20 369 202 190 1.37 1.10 0.19 35 301748 g/y 7 × 2.52 1.20 10.20 369 202 190 1.37 1.10 0.19 50 216759 red 19 × 1.79 1.40 11.90 502 245 232 1.09 0.85 0.26 50 301749 black 19 × 1.79 1.40 11.90 502 245 232 1.09 0.85 0.26 50 301750 g/y 19 × 1.79 1.40 11.90 502 245 232 1.09 0.85 0.26 70 301751 red 19 × 2.15 1.40 13.60 699 315 295 0.84 0.64 0.31 70 301752 black 19 × 2.15 1.40 13.60 699 315 295 0.84 0.64 0.31 70 301753 g/y 19 × 2.15 1.40 13.60 699 315 295 0.84 0.64 0.31 95 216760 red 19 × 2.52 1.60 15.80 959 388 365 0.68 0.50 0.41 95 black 19 × 2.52 1.60 15.80 959 388 365 0.68 0.50 0.41 95 301754 g/y 19 × 2.52 1.60 15.80 959 388 365 0.68 0.50 0.41 120 219394 red 37 × 2.02 1.60 17.50 1‘208 455 434 0.60 0.43 0.46 120 black 37 × 2.02 1.60 17.50 1‘208 455 434 0.60 0.43 0.46 120 301755 g/y 37 × 2.02 1.60 17.50 1‘208 455 434 0.60 0.43 0.46 150 219395 red 37 × 2.23 1.80 19.50 1‘483 521 495 0.54 0.38 0.57 150 black 37 × 2.23 1.80 19.50 1‘483 521 495 0.54 0.38 0.57 150 301756 g/y 37 × 2.23 1.80 19.50 1‘483 521 495 0.54 0.38 0.57 185 219396 red 37 × 2.49 2.00 21.70 1‘845 606 572 0.49 0.33 0.71 185 black 37 × 2.49 2.00 21.70 1‘845 606 572 0.49 0.33 0.71 185 301760 g/y 37 × 2.49 2.00 21.70 1‘845 606 572 0.49 0.33 0.71
Safety and Communication Cables
24
= Onrequest g/y = Green/Yellow
1 ACcircuit,max.conductortemperature90 °C 2 Freeinair,spaced
3 Opentray,touching
Cross section Partno. LSA Core colour Conductor stranding Nominal thickness insulation Nominal diameter core Approx. weight
CurrentRating1 ACVoltageDrop FireLoad
1phase2 3phase3 1phase
system 3phase system mm² n × mm mm mm kg / km A A mV / Am mV / Am kWh / m 240 219397 red 61 × 2.23 2.20 24.50 2‘418 723 681 0.44 0.29 0.88 240 black 61 × 2.23 2.20 24.50 2‘418 723 681 0.44 0.29 0.88 240 301761 g/y 61 × 2.23 2.20 24.50 2‘418 723 681 0.44 0.29 0.88 300 300945 red 61 × 2.52 2.45 28.30 3‘109 852 804 0.41 0.26 1.14 300 black 61 × 2.52 2.45 28.30 3‘109 852 804 0.41 0.26 1.14 300 301762 g/y 61 × 2.52 2.45 28.30 3‘109 852 804 0.41 0.26 1.14 400 301763 red 61 × 2.85 2.65 31.70 3‘948 996 929 0.38 0.24 1.38 400 black 61 × 2.85 2.65 31.70 3‘948 996 929 0.38 0.24 1.38 400 g/y 61 × 2.85 2.65 31.70 3‘948 996 929 0.38 0.24 1.38 500 301764 red 61 × 3.20 2.85 35.30 4‘955 1‘164 1‘095 0.36 0.22 1.66 500 black 61 × 3.20 2.85 35.30 4‘955 1‘164 1‘095 0.36 0.22 1.66 500 g/y 61 × 3.20 2.85 35.30 4‘955 1‘164 1‘095 0.36 0.22 1.66 630 301765 red 127 × 2.52 3.05 39.70 6‘384 1‘367 1‘266 0.34 0.21 2.01 630 black 127 × 2.52 3.05 39.70 6‘384 1‘367 1‘266 0.34 0.21 2.01 630 g/y 127 × 2.52 3.05 39.70 6‘384 1‘367 1‘266 0.34 0.21 2.01
Safety and Communication Cables FR-MI 110 / Single Core / Single Insulated