ADDENDUM NO. 2 page
2SPECIFICATIONS
Section 05 1200 – Structural Steel Framing
a. Add section “2.03.C. Painting: Paint all framing components with the specified paint in accordance with the recommendations contained in the SSPC/AISC "Guide to the Shop Painting of Structural Steel". Use a painting system adequate to provide protection equal to or exceeding a zone 1-A defense as defined in the SSPC/AISC "Guide". The paint shall have a minimum dry film thickness of 1.5 mils.”
Section 05 4000 – Cold Formed Structural Steel
a. Delete section 2.04.C. Painting: this does not apply to metal stud framing.
Section 09 2900 – Gypsum Board
a. Add the following to section 2.8.E. Acoustical Sealant: “All sound isolating gypsum board walls should be sealed at the top and bottom with a nonhardening sealant such as
Pecora AIS-919 or AC-20 FTR (fire rated), or equivalent. Spray-on fire sealants such as Hilti Firestop Joint Spray (CFS-SP WB) and Speed Plugs (CP 777) are available forlarger gaps where walls meet metal decks. Hilti Smoke and Acoustic Spray CP 572 is a similar product for non fire-rated applications.”
a. Delete 2.8.F.
b. At 3.3.C.1, delete the last sentence: “Apply Prospec Decibel Drop sealant two cartridges per 32 square feet of area between layers of gypsum board, follow all manufacturers recommendations.”
Section 10 5114 – Metal Lockers
a. Remove reference to Penco Vanguard Locker as Basis of Design.
Replace with “APS Standard Guidelines as Basis of Design: Lockers shall be
constructed of one-piece (Unibody) side frame and locker front. All welded body with no rivets, screws or bolts. Powder coated 2-tiered, 16-gauge doors with louvers, 16-gauge body steel units with high security latch with no moving parts to receive pad lock, one double hook on ceiling and 3 single hooks on walls. Aluminum number plate. Two-tier lockers will be 15” W, 60”H, 15” D. Built-in with furr-out above lockers to ceiling or angled top and built-in solid 4” base or coved sealed 4” base on metal legs.”
Section 33 6333 - Micropiles
a. Add the attached Section 33 6333 Micropiles, total of 4 pages, see Exhibit 01.
Section 23 0900 – Facility Management System
a. CHANGE 1.4.A. Approved Manufacturers: Existing portions of the building are already served by Automated Logic controls therefore Automated Logic is the only approved controls manufacturer.
DRAWINGS AD-101
a. Delete “See Mechanical for more info.” In Computer Lab 103.
ADDENDUM NO. 2 page
3AD-201
a. There is existing “Charles R Spain” Signage on the east face of the exterior Planetarium wall that will need to be removed and replaced for new stucco color coat. On drawing B2/AD-201. KN 15 will apply to this area.
A-103
a. In Computer Lab 103, Delete “See Mechanical for more info.” Add “Patch shall tie into existing access floor, frame in opening and match existing plywood thickness and finish level.”
A-105
a. Add KN 9 “Relocate existing projection screen as shown.”
b. Add KN 10 “Existing projection screen to remain.” Place KN 10 bubble in Cosmetology 112 along west wall where project screen is shown.
c. There are nine (9) keynotes that printed blank on the plan. The keynotes revisions are outlined below:
1. Both soffits (2 locations) outside of Vocational Room 119 shall be KN 4.
2. The west soffit outside of Vocational Room 122 shall be KN 4.
3. Both soffits (2 locations) outside of Cosmetology 112 shall be KN 4.
4. The north soffit outside of Cosmetology 102 shall be KN 4.
5. The soffit outside of Unisex Restrooms 145 and 146 shall be KN 4.
6. The south side of Cosmetology 102 shall be KN 9.
7. Delete the blank keynote in Hall 114, just south of Storage 122D.
A-106
a. Ceiling Elevation markers are incorrect in three (3) instances on A-106 1. The soffit outside of Classroom 233 shall read 10’-2”
2. The soffit outside of Classroom 234 shall read 10’-2”
3. The soffit outside of Classroom 236 shall read 10’-2”
A-201
a. There is existing “Charles R Spain” Signage on the east face of the exterior Planetarium wall that will need to be removed and replaced for new stucco color coat. On drawing B2/A-201. KN 21 will apply to this area.
A-601
d. On the Door Schedule, Door A135, change Door Type “A” to Door Type “F”
A-602
a. Window Type A reduced in size to match block coursing. Dimensions to read 4’-0” x 12’- 8” overall, set at 3’-4” AFF
b. Window Type B reduced in size to match block coursing. Dimensions to read 4’-0” x 6’- 8” overall, set at 3’-4” AFF
Sheet PP-101 – PRESSURE PIPING FLOOR PLAN a. ADD general note K. as follows:
Electrical contractor to provide e-MON Series 5000 water and gas meters. Gas and
Water meters are to be installed in the piping by the plumbing contractor but powered
and integrated to the e-MON server by the electrical contractor in coordination with APS
personnel.
ADDENDUM NO. 2 page
4Sheet P-401 – PLUMBING SCHEDULES
a. ADD Floor drains to Unisex 145 and Unisex 146
b. CHANGE Sanitary routing in Girls 237. Refer to the revised sheet, see Exhibit 02.
Sheet P-701 – PLUMBING SCHEDULES
a. REMOVE Duplicate P1a, American standard Model 3351.101, wall mounted water closet from the schedule.
Sheet MD-101 – MECHANICAL DEMOLITION PLAN
a. ADD keynote #12 indicating the removal of floor supply diffusers from Computer Classroom. Refer to the revised sheet, see Exhibit 03.
Sheet MH-101 – MECHANICAL FLOOR PLAN
a. ADD – keynote #12 indicating the addition of acoustic liner is the ERV duct work. Duct work sizing and routing has also been updated. Refer to the revised sheet, see Exhibit 04.
Sheet MI-602 – MECHANICAL CONTROLS DIAGRAMS
a. REMOVE Building monitoring control diagram. The all building monitoring shall be done through an e-MON server and not via the facility management system. Electrical
contractor to provide e-MON Series 5000 water and gas meters. Gas and Water meters are to be installed by the plumbing contractor but powered and integrated to the e-MON server by the electrical contractor in coordination with APS personnel.
Sheet EL-102 – LIGHTING SECOND FLOOR PLAN
a. CHANGE (5) SR6, (7) SW2, AND (12) SW4 lighting fixtures per revised drawing, see Exhibit 05.
Sheet EP-102 – POWER SECOND FLOOR PLAN
a. CHANGE head wall receptacles in NURSING LAB 242 per revised drawing, see Exhibit 06.
Sheet E-601 – ELECTRICAL DIAGRAMS
a. CLARIFY, APS does all sub-metering through an e-MON server located at the APS Data Center, not through the Facility Management System (FMS). The project requires an internet-connected e-MON Series 5000 sub-meter, which will capture whole-building electrical usage. Electrical contractor to provide e-MON Series 500 water and gas meters. Gas and Water meters are to be installed by the plumbing contractor but powered and integrated to the e-MON server by the electrical contractor.
Sheet E-701 – ELECTRICAL SCHEDULES
a. CHANGE lighting fixture types per sheet EL-102 changes per revised fixture schedule,
see Exhibit 074
ADDENDUM NO. 2 page
5This addendum consists of fifteen (15) pages including six (6) full sized 24” x 36” drawing sheets as exhibits.
Exhibit 01 – Specifications Section 33 6333 - Micropiles Exhibit 02 – Sheet P-401 – Enlarged Plumbing Plans
Exhibit 03 – Sheet MD-101 – Mechanical Demolition Floor Plan Exhibit 04 – Sheet MH-101 – HVAC Floor Plan
Exhibit 05 – Sheet EL-102 – Lighting Second Floor Plan Exhibit 06 – Sheet EP-102 – Power Second Floor Plan Exhibit 07 – Sheet E-701 – Electrical Schedules
Each bidder shall acknowledge receipt of this Addendum No. Two (2) on the Bid Proposal form in the space provided.
END OF ADDENDUM No. 2
Cherry/See/Reames Architects, PC
By________________________________
Tina M. Reames, FAIA, President
APS ECA CEC Modernization, Renovation and Addition
DRILLED MICROPILES 33 6333‐1
ADDENDUM No. 2 EXHIBIT 01
SECTION 33 6333
DRILLED MICROPILES
– GENERAL 1.1 SECTION INCLUDES
A. Include materials, labor, services, and incidentals necessary for completion of this section of work.
B. Extent of cast in place concrete work is shown on Drawings.
C. Notify other trades of the date for placement in ample time for each to install their own work.
1.2 RELATED SECTIONS
A. General and Supplemental General Conditions of the Contract and Division 1.
B. STS 01 21 19 – Testing and Inspecting Allowances.
1.3 REFERENCES
A. Where all or part of a Federal, ASTM, ANSI, New Mexico Standard Specifications for Public Works Construction etc. is incorporated by reference in these specifications, the reference standard shall be the latest edition and revision.
B. Industry Standards, Specifications and Codes:
1. General:
a. Comply with provisions of the following codes and standards except as modified herein.
b. Referenced codes and standards including revisions and commentaries shall be the most currently adopted as of the date of these Contract Documents.
2. American Concrete Institute (ACI):
a. ACI 117 Standard Specifications for Tolerances for Concrete Construction and Materials.
b. ACI 301 Specifications for Structural Concrete.
c. Additional ACI sections are noted in later text.
3. American Society for Testing and Materials (ASTM):
a. Specific ASTM standards are noted in later text.
APS ECA CEC Modernization, Renovation and Addition
DRILLED MICROPILES 33 6333‐2
ADDENDUM No. 2 EXHIBIT 01
1.4 SUBMITTALS
A. Submit in accordance with Division 1 requirements.
B. Complete description of equipment, procedures and techniques for pile installation.
1. Equipment required for installation including, but not limited to: drills, pumps, casing, etc.
2. Pipe and rebar specifications 3. Grout mix design
C. Pile design‐ Design drawings and calculations prepared by a registered professional engineer who has at least 5 years documented experience in the design of micropiles. The design shall include pile design and pile‐footing connection design at existing footings. The design shall conform with applicable provisions of the Building Code, FHWA Micro‐pile Design and Construction Guidelines, and accepted industry practice.
D. Lad Test Equipment ‐ Submit for approval information on the test jack and calibration results. The test jack and pressure gauge shall be calibrated in conformance with ASTM requirements.
1.5 QUALITY ASSURANCE
A. Designer’s and Installer’s Qualifications: The firm that performs the Work of this Section shall have a minimum of 5 years experience in the type of design and construction required for the Work of this Section and shall have designed and installed foundation systems for at least 5 projects of equivalent or greater difficulty as required by this Contract.
1. The firm’s staff shall include at least one Professional Engineer licensed by New Mexico State.
2. The firm’s supervising engineer and site foreman or superintendent for this project shall have at least 5 years of experience in this type of foundation Work.
B. Contractor shall meet with the inspection/testing agency and Engineer at least 24 hours prior to major concrete pour.
‐ PRODUCTS 2.1 MATERIALS
A. Furnish the materials required for the Work of this Section.
B. Pipe reinforcement shall conform to ASTM A252 Grade 2 or approved equal. Mill secondary pipe is acceptable provided coupons are submitted for each truckload. Splicing shall be by threaded and coupled connections or continuous butt welds, using procedures
recommended by the pipe supplier.
C. Reinforcing bar shall conform to ASTM A615 Grade 60 or approved equal. Splicing details
shall be either lap splices or approved couplers.
APS ECA CEC Modernization, Renovation and Addition
DRILLED MICROPILES 33 6333‐3
ADDENDUM No. 2 EXHIBIT 01
D. Grout shall consist of Type I or III Portland Cement and water mix with a minimum 28‐day compressive strength shall be 4000 psi. Potable water shall be used for mixing grout.
E. Regrout tubes, if required, shall be PVC pipe or approved equal. The pipe material shall be nondegradable and compatible with Portland cement. Regrout tubes shall be filled with grout at the completion of work.
– EXECUTION 3.1 GENERAL
A. Piles shall be oriented as shown on the foundation plans. All piles shall be drilled within 4%
of the angle indicated on the plans and within 3 inches of the location shown. Piles installed out of plumb or location shall be cause for rejection or reduced capacity as determined by the Designer.
B. All pile installation shall be performed under the supervision of a qualified geotechnical engineer retained by the Owner.
C. The Contractor shall protect all existing equipment and structures during pile installation.
3.2 INSTALLATION
A. Clean all mixing and transportation equipment. Wet forms thoroughly. Remove all ice, excess water, mud and other debris from within forms and from reinforcement. Notify Engineer prior to placing in ample time for inspection of forms and reinforcing.
B. The minimum drilled hole diameter shall be within ½” of that shown on the plans. Holes shall be temporarily cased, as necessary, to the pile tip elevation or casing refusal materials.
Casing may be terminated prior to the above requirements if the soils encountered can be drilled without caving.
C. If pile capacity dictates extending into refusal materials, continue drilling until an adequate rock socket is obtained as determined by the Designer.
D. Install micro‐pile reinforcing in the center of the hole using centralizers as required.
Measures shall be implemented to permit grout to flow from the pile to the annular spaces between the pile and the casing. Reinforcing bar and pile reinforcement shall be spliced as necessary.
E. Drill hole and casing shall be tremie grouted full length. At Contractor’s option, the pile reinforcing may be installed after grouting.
F. Temporary casing shall be slowly withdrawn and the grout level shall be checked
periodically to ensure that the top of the grout does not fall below the bottom of the casing.
G. Care shall be exercised to prevent damage to previously installed piles. The center to center spacing of subsequently installed piles shall be adjusted based on soil conditions.
H. Piles may be regrouted to increase the bond with the surrounding soils. Piles which are to be regrouted shall be fitted with a regrout tube securely attached to the pile reinforcing.
Regrouting shall be performed within 12 hours of pile installation.
APS ECA CEC Modernization, Renovation and Addition
DRILLED MICROPILES 33 6333‐4
ADDENDUM No. 2 EXHIBIT 01
3.3 FIELD QUALITY CONTROL
A. All pile shall be continuously inspected by the Owner’s representative. A record shall be kept of each pile and shall include as a minimum:
1. Length of pile as installed 2. Depth to rock 3
3. Length of rock socket 4. Theoretical grout volume
5. Actual grout volume for primary and regrouting 6. Grout pressure during casing withdrawal 7. Conditions encountered during drilling 8. Date and time of installation
9. Pile number or location description
B. Load Testing Piles: Test piles in accordance with ASTM D 1143, Quick Load Test Method for Individual Piles with the following modifications:
1. Do not start a load test until the earth is removed to the elevation of the bottom of the pile cap.
2. Perform a load test on one pile in each pile cap group indicted on the Drawings to be load tested.
3. Apply load in 10‐15 percent increments at 2.5 minute intervals to 200 percent of the allowable design load.
4. Hold full test load for a period of one hour.
5. Remove full test load in four 25 percent decrements at 5.0 minute intervals.
6. The net settlement after rebound shall not exceed 0.50 inch.
7. Test piles, if properly located and not exceeding 0.50 inch net settlement, are acceptable as permanent and may be left in place.
8. Submit one copy of load test results, stamped by a New Mexico State licensed professional engineer
END OF SECTION 33 6333
UNISEX 146
WORK / BREAK ROOM
144
UNISEX 145
P6a
FD1
P4 P3 P3
P1a WCO
WCO
P6
WCO P2a
WCO
3" V 3" V
3" V WCO
WCO
3" SAN
4" SAN 4" SAN
4" SAN 4" SAN
3" SAN 2" V
2" V 4" V
P1a FD1
UNISEX 146
UNISEX 145 P6a
P4 ICE
P3
P1a 2" DHW
2" DHW
1 1/2" DCW 1 1/2" DCW
2" DHW 2" DHW
2" DHW
P2a
2"
2" 2" 2" 2"
2"
2" DHW 2" DHW
1 1/2" DCW 1" DCW
P3
P1a
P6
1 1/2"
1 1/4"
1 1/4" DCW WHA
3/4" DCW 3/4" DCW
3/4"
WHA
ACCESS PANEL
ICE
GIRLS 237
BOYS 238
HALL 249 P6a P1a
P1a
P1
P2a
FD1 FD1
P3
P6a 2" V
4" SAN
4" V
4"
3"
3"
4" 3"
1 1/2"
4"
FD1
3"
1 1/2"
ECO P3
P3
P3 3"
1 1/2"
P6a P1a
P1a
P1
P2a
P3
BOYS 238 GIRLS
237
HALL 249 P6a
HB 1 1/2" 2"
2" DCW RISER
3/4" DHW RISER TO BELOW 3/4" DHW RISER FROM BELOW
P3 P3 P3
1" DCW RISER FROM BELOW
H EC VI K
OF
HN F.
ATST E
CO GIN EER
ON L E A
I N
NO.
S E N
ROFES ED M
P EW
12498
I X I
RE
G
J
STE R
O
MARK
PROJECT NO:
5 4
3 2
1
E
D
C
B
A
CAD DWG FILE:
DRAWN BY:
CHECKED BY:
COPYRIGHT: Cherry/See/Reames PC 2013 DATE DESCRIPTION ISSUE:
1
C
CHERRY/SEE/REAMES ARCHITECTS, PC
505 - 842 - 1278 fax 505 - 766 - 9269 www.cherryseereames.com
MANAGEMENT BLOCK
ENLARGED PLUMBING PLANS
507
P-401
E C A @ C E C M o d e rn iz a ti o n , R e n o v a ti o n & A d d it io n 8 0 7 M o u n ta in R o a d N E A lb u q u e rq u e , N M 8 7 1 0 2
TML PHW
01/11/2021 100% CD
GENERAL SHEET NOTES
A. REFER TO ARCHITECTURAL FLOOR PLANS FOR EXACT LOCATION AND HEIGHTS OF ALL PLUMBING FIXTURES BEFORE ROUGH-IN OR INSTALLATION OF PIPE. PLUMBING FIXTURES SHALL BE MOUNTED AT HEIGHTS SHOWN ON ARCHITECTURAL ELEVATION DRAWINGS.
B. ALL PIPING IN FINISHED ROOMS SHALL BE CONCEALED IN FURRED CHASES UNLESS OTHERWISE NOTED ON THIS DRAWING.
C. PROVIDE HINGED ACCESS DOORS FOR VALVES, WATER HAMMER ARRESTERS, ISOLATION BALL VALVES LOCATED IN NONACCESSIBLE CEILINGS AND CHASES.
DOORS FURNISHED PER ARCHITECTURAL SPECIFICATIONS AND PURCHASED AND INSTALLED PER DIVISION 22. ACCESS DOOR RATING SHALL MATCH THE
CLASSIFICATION OF WALLS AND CEILING FIRE RATING. COORDINATE COLOR AND TYPE OF ACCESS DOOR WITH ARCHITECTURAL PRIOR TO PERFORMING WORK.
D. REFER TO ARCHITECTURAL DRAWINGS FOR EXACT LOCATION OF ALL FIRE RATED AND OR SMOKE RATED WALLS AND ASSEMBLIES. PIPING PENETRATIONS OF FIRE AND SMOKE RATED WALLS AND LISTED ASSEMBLIES SHALL BE CAULKED AIRTIGHT TO THE ADJACENT STRUCTURE BY MEANS OF U.L. LISTED FIRE PROOF CAULKING MATERIAL.
E. COORDINATE ALL PLUMBING PIPING WITH ALL OTHER TRADES AND PROVIDE
NECESSARY OFFSETS TO AVOID CONFLICTS AND TO MAINTAIN REQUIRED EQUIPMENT ACCESS AND SERVICEABILITY.
F. PIPING LOCATIONS HAVE BEEN SHOWN FOR CLARITY AND DO NOT NECESSARILY REFLECT THE EXACT LOCATION OF PIPE. COORDINATE ROUTING WITH ALL OTHER TRADES BEFORE INSTALLATION OR MAKEUP OF PIPE. PROVIDE COORDINATION DRAWINGS PER SPECIFICATIONS.
G. REFER TO DRAWING P-701 FOR PLUMBING ROUGH IN REQUIREMENTS.
H. ALL PLUMBING FIXTURES SHALL HAVE WALL CLEANOUTS.
I. ALL P-TRAPS TO FLOOR SINKS AND FLOOR DRAINS SHALL BE SUPPLIED WITH A TRAP SEAL GUARD.
J. ALL SANITARY PIPE IN KITCHEN TO BE CAST IRON. PROVIDE SANITARY PIPE DOWNSTREAM OF THE GREASE INTERCEPTOR PER SPECIFICATIONS.
K. ROUTE ALL WASTE PIPING AT A 1% SLOPE UNLESS OTHERWISE INDICATED.
SCALE: 1/4" = 1'-0"
C2 WASTE & VENT - L1 98'-0" Lecture Hall
SCALE: 1/4" = 1'-0"
C1 PRESSURE PIPING - L1 98'-0" Lecture Hall
SCALE: 1/4" = 1'-0"
A2 W&V - L2 (Anno) - Callout 1
SCALE: 1/4" = 1'-0"
A1 PRSS PIPING - L2 (Anno) - Callout 1
1
1 02/05/2021 ADDENDUM #2
ADDENDUM No. 2
EXHIBIT 02
DN DN DN
DN DN
DN
DN DN
DN
215 23 214
213 20 19 212
16 15 211 210 102 13
103 104 11 209 208 105
9 207 206 205 204
6 107 203 108 202
3 109
1 201 110
J A
20A 20B 20C B 20D
20E
20F 20G C 20H 20J D E F G
2
4
7 5
R
8
12
14
18 17
6
2 5
5
4
4
4
4
4
4
4
4 5
1
5
3
7
8
9 10
9
9
10 9 10
8
8
9
10 11
11
12
18118
NEW ME X
I CO
PR
OF
E SS I ON A L ENGI N EER
R ICK H. WATK T IN
P A S
MARK
PROJECT NO:
5 4
3 2
1
E
D
C
B
A
CAD DWG FILE:
DRAWN BY:
CHECKED BY:
COPYRIGHT: Cherry/See/Reames PC 2013
DATE DESCRIPTION
ISSUE:
1
C
CHERRY/SEE/REAMES ARCHITECTS, PC
505 - 842 - 1278 fax 505 - 766 - 9269 www.cherryseereames.com
MANAGEMENT BLOCK
MECHANICAL DEMOLITION FLOOR
PLAN
507
MD101
EC A @ C EC Mo de rn iza tio n, Re nov atio n & A ddition 80 7 M oun tai n R oad NE Al buque rqu e, NM 87 102
RAH/MTO PHW
01/11/2021 100% CD
SCALE
MD101 3/32" =
1'-0"
A1 MECHANICAL FOURTH FLOOR DEMOLITION PLAN
GENERAL SHEET NOTES
KEYNOTES
1. REMOVE (2) CAST IRON SECTIONAL BOILERS, (2) BASE MOUNTED PUMPS AND THE CONTROLS COMPRESSOR AND AIR DRYER.
REMOVE ALL HYDRONIC PIPING. REMOVE FLUES SERVING EACH BOILER AND THE COMBUSTION AIR DUCTS. REMOVE EXPANSION TANK.
2. NO DEMOLITION IN THE PLANETARIUM SPACE.
3. REMOVE EXHAUST FAN, GRILLES AND DUCTWORK OVER RESTROOM CEILING.
4. REMOVE ALL HVAC EQUIPMENT, PIPING, DUCTWORK AND CONTROLS PIPING.
5. REMOVE ALL HVAC EQUIPMENT, PIPING, DUCTWORK AND
CONTROLS PIPING ABOVE CEILING. CASEWORK BELOW TO REMAIN.
CARE MUST BE TAKEN TO PROTECT CASEWORK AND FURNITURE IN THE SPACE.
6. REMOVE ALL HVAC EQUIPMENT, PIPING, DUCTWORK AND
CONTROLS PIPING ABOVE CEILING. PLUMBING FIXTURES BELOW TO REMAIN.CARE MUST BE TAKEN TO EXISTING PLUMBING FIXTURES IN THE SPACE.
7. EXISTING PLANETARIUM ROOFTOP UNIT TO BE CAREFULLY REMOVED AND REPLACED AS A PART OF THE RE-ROOFING PROCESS.
8. REMOVE EVAPORATIVE COOLING UNIT ON ROOF AND ALL DUCT, GRILLES AND FLEX DUCT ASSOCIATED WITH THE UNIT.
9. REMOVE HYDRONIC FAN COIL FROM ABOVE CEILING AND ALL DUCT, GRILLES AND FLEX DUCT ASSOCIATED WITH THE UNIT. REMOVE HYDRONIC PIPING COMPLETELY.
10. REMOVE EXHAUST FAN ON ROOF AND ALL DUCT, GRILLES AND FLEX DUCT ASSOCIATED WITH THE UNIT.
11. TYPICAL LAYOUT OF HVAC. EACH CLASSROOM IS SERVED BY AN EVAPORATIVE COOLER FOR COOLING AND A HYDRONIC FAN COIL FOR HEATING. HEATING WATER MAINS ARE INSTALLED IN
CORRIDORS ARE TO BE REMOVED.
12. REMOVE APPROXIMATELY THIRTY FLOOR SUPPLY GRILLES IN CLASSROOM. COORDINATE FLOOR PATCHING WITH GENERAL CONTRACTOR.
A. REFER TO DEMOLITION NOTES ON SHEET M-001.
0' 5' 10' 20'
1
1 02/05/2021 ADDENDUM #2
ADDENDUM No. 2
EXHIBIT 03
DN DN DN
DN DN
DN
DN DN
DN
CLASSROOM 116
Unoccupied Unoccupied HUDDLE ROOM
151A
MECH.
149
ELEC.
150
CLASSROOM
115 FLEX TECH
LAB 114 OPEN OFFICE
152
HUDDLE ROOM 152A LECTURE HALL
113
COMPUTER LAB 103
CLASSROOM 105
DIGITAL MEDIA 108 VOC
108B
VOC 108A MDF 103A
HALL H110 COSMETOLOGY
112 ELEC.
112B
MECH.
120
CLASSROOM 118
CLASSROOM 117
OFFICE 112C
STOR.
102B
GIRLS 126
BOYS 125 WOMEN
128
MEN 127
PLANETARIUM 124 STOR.
124A
STOR.
124B
ELEC.
101
STUDENT LOUNGE
123
OFFICE 122A STOR.
122D STOR.
119A
OFFICE 122F STOR.
119B
VOCATIONAL ROOM
184
JAN 183 UNISEX
182
STOR.
181
KITCHEN 177
IDF 178
ELEC 176
STOR.
102D
CLASSROOM 106
CLASSROOM 110
COMM.
110A
FIRE 110B
WORK / BREAK ROOM
144
146 145
STOR.
143
COUNSELOR 142 HEAD SPED
141 HUDDLE
140 CCTV
MONITORING 137
CCTV EQUIP.
138
SECURITY OFFICE
136
ADMIN. STOR.
130
VAULT &
RECORDS 131
REGISTRAR 135 COMPUTER
LAB 104
ASSISTANT PRINCIPAL
134 CONFERENCE
133 PRINCIPAL
132 VEST
A135 JAN.
111
CLASSROOM 193
CLASSROOM 192
CLASSROOM 191
STOR.
189 EMT
188 STOR.
190
VOCATIONAL ROOM
187
EMT 185 STOR.
186
FCU-19
FCU-20 FCU-23 FCU-24
FCU-25 FCU-26
FCU-18
FCU-17 FCU-15
FCU-13
FCU-16 FCU-14
FCU-2
FCU-3 FCU-1
FCU-5
HP-1 HP-4
HP-2
HP-5
HP-3
FCU-21
FCU-22
FCU-6
FCU-7
FCU-8
FCU-12 FCU-11
FCU-4
FCU-9
FCU-10 WORK / BREAK
ROOM 144 WARMING
KITCHEN 123A
215 23 214
213 20 19 212
16 15 211 210 102 13
103 104 11 209 208 105
9 207 206 205 204
6 107 203 108 202
3 109
1 201 110
J A
20A 20B 20C B 20D
20E
20F 20G C 20H 20J D E F G
2
4
7 5
R
8
12
14
18 17
1
1
1
1 1
1
1
2
1 1
1
1
1 1
1
1
1 1
1
1 1
1 1 1
1 1
AC-1 AC-2
2
3
3
3
3
3
1 DWH-1
DWH-2
JAN 121
EG-2 300
8"x8"
8"x8"
EG-2 100 EG-2
100
EG-2 450
EG-2 450
6"x6"
8"x8"
5
UH-1 6
14"x14" 14"x14"
14"x14"
14"x14" 12"x12" 12"x12" 12"x12" 12"x12"
10"x10"
12"x12"
12"x12"
14"x14"
14"x14"
14"x14"
14"x14"
14"x14"
14"x14"
14"x14"
18"x12"
12"x12"
14"x14" 14"x14"
14"x14"
14"x14"
SD-1 235
SD-1 235
SD-1 235
SD-1 235
SD-1 235
SD-1 235
SD-2 145
SD-2 145
SD-2 145
SD-2 145
SD-2 145
SD-2 145
SD-2 145 SD-2
145
SD-1 245
SD-1
245 SD-1
245
SD-1 245 SD-1
245
SD-1 245
SD-2 195
SD-2 195
SD-2 195 SD-2
195
SD-2 100
SD-1 270
SD-1 270
SD-1 270 SD-1
270 SD-1
180
SD-1 180 SD-1
180 SD-1
180
SD-1 180
SD-1 180
SD-2
195 SD-2
195 SD-2
195 SD-2
195 SD-2
195 SD-2
195
SD-2 260
SD-2 260 SD-2
50
SD-2 50
SD-1 270
SD-1 270
SD-1 270
SD-1 270
SD-1 100
SD-1 290
SD-1 290
SD-1 290 SD-1
290
SD-1 220
SD-1 220 SD-1
100
SD-1 220 SD-1
220
SD-1 220
SD-1 220
SD-2 270
SD-2 270 SD-2 100
SD-2 270
SD-2 270
SD-1 195
SD-1 195 SD-1
195 SD-1
195 SD-2
100
SD-2 100
SD-2 230
SD-2 230
SD-2 230
SD-2 230
SD-2 230
SD-2 230
SD-2 195
SD-2 195
SD-2 195
SD-2 440
SD-2 440 SD-2
195
SD-2 270 SD-2
270 SD-2
270
SD-2 270 SD-2
100
SD-2
50 SD-2
150 SD-2
150 SD-2
150
SD-2 50
SD-2 50
SD-2 290 SD-2
290 SD-2
290
SD-2 290
SD-2 220 SD-2
220 SD-2
220 SD-2
220
SD-2 235 SD-2
235 SD-2
235
SD-2 235 SD-2
235 SD-2
235
SD-2 275
SD-2 275 SD-2
275 SD-2
275 SD-2
50
SD-1 350
SD-1 350
SD-1 350
SD-1 350 SD-1
340 SD-1
340 SD-1
200
SD-2 50
SD-2 50
SD-1 235
SD-1 235 SD-1
235
SD-1 235 SD-1
235
SD-1 235 SD-1
340
SD-1 340
SD-1 200 EG-1
696 RG-1
EG-2 142
RG-2
EG-2 250
EG-2
155 EG-2
294 RG-2
RG-2 EG-1
696
RG-1
SD-1 145
RG-2
RG-1
RG-1
RG-1
RG-1
RG-2
RG-2
RG-2
RG-1
RG-2
RG-2
RG-2
RG-2
RG-2
RG-2
RG-2
RG-2 RG-2 RG-2
RG-2 RG-2
RG-2
RG-2
RG-2 RG-2
RG-1
RG-1 RG-1
STOR.
105A
HALL H113 VEST
173
Unoccupied Unoccupied
STOR.
102C
ELEC 103B SD-1
100
16"x16"
10"ø
10"ø
14"ø
SD-2 100 RG-2
EG-1 450
10"x10"
EG-1 450
12"x12"
12"x12"
EG-1 450
EG-1 450
14"x12"
10"x10"
10"ø
8"ø
10"ø 6"ø6"ø 8"ø
16"ø14"ø
6"ø 6"ø
6"ø 6"ø
8"ø 6"ø
12"ø 10"ø
10"ø
16"ø
30"x16"10"ø
18"x16"
14"ø
14"ø
10"ø
12"ø 8"ø
6"ø
10"ø
10"ø
10"ø 8"ø
6"ø
10"ø
10"ø AC-3
48"x14"
36"x14"
40"x14"
36"x14"
24"x14" 24"x14"
44"x14"
RG-1 10"x10"
28"x14"
44"x14"
40"x14"
36"x14"
30"x16"
30"x16"
2 CEF-1
8
9 10
CEF-2 10
9
12"x12"
12"x12"
18"x18"
18"x18"
16"x16"
16"x16"
12"x12"
12"x12"
12"x12"
12"x12"
14"x12"
14"x12"
12"x12"
6"x6"
10"x8"
6"x6"
7
7
7
7
7 7
7
7
7
7 7
7 7
7 7
7
7 7
7 7
7 7
7
7
7
7 7
7
DWH-3 11
10"x10" 10"x10"12"x12"
10"x10"
6"x6"
6"ø
10"ø 14"x12"
14"ø 12"ø
16"ø
16"ø
10"ø 36"x14"
7
24"x14" 7
24"x14" 7
7
12"x10"
24"x14"
7
6"x6"
7 10"x10"
7 7 8"x8"
8"x8" 7
8"x8"
7
6"x6"
EG-1 100 EG-1
100 6"x6"
8"x8"
SD-2 RG-1 50
8"x8"
8"x8"
RG-2 14"x14" 7
8"x8" 7
10"x10"
24"x14"
32"x16"
18"x18"
VOCATIONAL ROOM
119
VOCATIONAL ROOM
122 STOR.
122C
STOR.
122B
18"x14"
EG-1 696
EG-1 696
34"x14" 32"x18"
34"x14"
12"x10"16"x14" 8"x6"8"x8"
20"x14"
8"x8"
8"x6"
12"x10" 18"x14" 12"x10"
14"x12"
34"x14"
34"x14"
12"x10"
HALL H110
RG-1 RG-2
RG-1
RG-1
RG-1
12 18"x14"
18118
NEW ME X
I CO
PR
OF
E SS I ON A L ENGI N EER
R ICK H. WATK T IN
P A S
MARK
PROJECT NO:
5 4
3 2
1
E
D
C
B
A
CAD DWG FILE:
DRAWN BY:
CHECKED BY:
COPYRIGHT: Cherry/See/Reames PC 2013
DATE DESCRIPTION
ISSUE:
1
C
CHERRY/SEE/REAMES ARCHITECTS, PC
505 - 842 - 1278 fax 505 - 766 - 9269 www.cherryseereames.com
MANAGEMENT BLOCK
HVAC FLOOR PLAN
507
MH101
EC A @ C EC Mo de rn iza tio n, Re nov atio n & A ddition 80 7 M oun tai n R oad NE Al buque rqu e, NM 87 102
RAH/MTO PHW
01/11/2021 100% CD
SCALE
MH101 3/32" =
1'-0"
A1 HVAC FLOOR PLAN
GENERAL SHEET NOTES
KEYNOTES
1. CEILING CONCEALED FAN COIL UNIT SUSPENDED FROM STRUCTURE. PROVIDE BALANCING DAMPER ON VENTILATION DUCT AND BALANCE TO THE AIRFLOW SHOWN ON THE FAN COIL SCHEDULE. SEE DETAIL C2 ON SHEET M-501.
2. WALL MOUNTED AIR HANDLING UNIT ABOVE DOOR. PROVIDE AND INTERLOCK CONDENSATE PUMP. PROVIDE WALL CONCEALMENT CHANNEL FOR REFRIGERANT PIPING AND CONDENSATE PUMP. PROVIDE WIRED THERMOSTAT.
3. HEAT RECOVERY HEAT PUMP CONDENSING UNIT ON RECTORSEAL BIGGFOOT STAND SYSTEM. ALL PIPING SHALL BE PROTECTED FROM PEDESTRIAN TRAFFIC.
4. EXHAUST DUCT UP TO DOWNBLAST FAN ON ROOF. PROVIDE 24" ROOF CURB.
5. CABINET EXHAUST FAN SERVING JANITORS CLOSET. PROVIDE 6" ROUND DUCT UP THROUGH ROOF AND TERMINATE WITH GOOSENECK. PROVIDE BIRDSCREEN.
6. UNIT HEATER SUSPENDED FROM WALL FRAMING. PROVIDE FACTORY WALL BRACKET AND UNIT MOUNTED CONTROLS.
7. TRANSFER AIR ELBOW SUSPENDED FROM STRUCTURE. REFER TO M-501 FOR DETAIL.
8. 6" GALVANIZED DRYER VENT UP THROUGH ROOF. TERMINATE WITH GOOSENECK 14"
ABOVE ROOF AND PROVIDE BIRD SCREEN.
9. 6" GALVANIZED EXHAUST DUCT UP THROUGH ROOF. TERMINATE WITH GOOSENECK 14" ABOVE ROOF AND PROVIDE BIRD SCREEN.
10. CEILING EXHAUST FAN SUSPENDED FROM STRUCTURE.
11. 4" AL294C FLUE AND 4" GALVANIZED COMBUSTION AIR DUCT TO WATER HEATER.
TERMINATE AT SIDEWALL WITH WEATHERCAP.
12. 32X16 DROP, DUCT MAIN AND 18X14 VENTILATION DUCT SHALL HAVE 1" ACOUSTIC LINER.
A. REFER TO GRILLE AND DIFFUSER DETAIL C4 ON SHEET M-501.
B. REFER TO LOW PRESSURE DUCT FITTING DETAIL A4 ON SHEET M-501.
0' 5' 10' 20'
1
1
1 02/05/2021 ADDENDUM #2
ADDENDUM No. 2
EXHIBIT 04
OS OS
OS OS
OS
OS OS
OS OS
OS
OS OS OS OS
OS OS
L24
L24 L24
L24
L24 L24
L24 L24
L24 L24
L24 L24
L24 L24
L24
L24 L24
L24
L24 L24
L24
L24 L24
L24 L24
L24 L24 L24
L24 L24 L24
L24 L24 L24
L24 L24 L24
L24 L24 L24
L24 L24 L24 L24
KLS RD2 RD2
RD2 RD2
RD2
RD2 RD2 SR7
SR7 SR4
SR8
SR4
SR7
SR8 SR8
SR7 SR4
SR8
SR4
SR7
SR8
SR8
SR6 SR4
SR4 SR8 SR4 SR4
SR4 SR4
SR7 SR4 SR4 SR4
SR7 SR7
SR4
SR7 SR4
SR4
SR7
SR4 SR7
SR4 SR7
SR4
SR7 L24
L24
L24 L24
L24
L24
SR9
SW6A SW8
SW8 SW6A
SW8 SW6A
SW8 SW6A
SW6A SW8
SR9
L24
L24
L24
L24 L24
L24 L24
L24 L24
L24 L24
L24
L24
L24
L24
L24
L24
L24
L24
L24 L24
L24 L24
SRL MECH.
201 ELEC.
202 IDF 203
WORK ROOM 204
CLASSROOM 209
UNISEX 207
JAN 208 VOCATIONAL
ROOM 211
STOR.
214
STOR.
212
STOR.
213
VOCATIONAL ROOM
215
Unoccupied Unoccupied BOYS
205 GIRLS
206 HALL
216 COMMONS
217
BOYS 238 GIRLS
237 HALL
245
HALL
247 HALL
248
HALL 249 HALL
246 HALL
218
BRIDGE 220
Unoccupied Unoccupied
CLASSROOM
234 CLASSROOM
233
CLASSROOM 232
ROOF DECK
235 CLASSROOM
231
NURSING STAFF HOMEBASE
230
CLASSROOM 236
HUDDLE ROOM 241
NURSING DIRECTOR
239
NURSING LAB 242
NURSING CLASS
243
NURSING CLASS
244
a 3 D
D 3 RD2 RD2
D
D D
EM EM
EM
EM
EM EM
EM
EM
EM
EM EM EM
EM EM EM EM
K
DL
DL a a a a
b b
b b
a a
a a
b b
b b
DL DL
D a
a a
a a
a
b b b
DL DL
D
EM a
a a
a a
a
b b
b
a
a
a a
a
a b
b
a a
a a
a
a b
b
b
L24
L24
b
EX1 EX1
EX1
EX1 EX1
SW2
SW2
SW2
SW2
SW2 SW6
SW6 L24
EM
EM EM
EM
EM
EM
EM
EM EM
EM
EM EM
2L1-1
RD2 RD2
2L1-2
2L1-2
2L1-3 2L1-3
2L1-3 2L1-4
2L1-6
K K
D b D
DT a
K K
D b D
DT
DT DT
DT
EM
DT IR DT
DT
DT DT
DT DT
DT DT DT
3 D a D b
3 Da3
b
a a
a
a a a a a
a
b a b
b b
b b b b
K
K K K
K
K a b D
D K K
a b D
D K K
a b D D
K K
a Db
1 (TYP.) 1
(TYP.)
1 (TYP.)
1 (TYP.)
1 (TYP.)
2 (TYP.)
2 (TYP.) 2 (TYP.)
3 (TYP.) 4
(TYP.)
4 (TYP.)
4 (TYP.)
4 (TYP.)
4 (TYP.)
5 (TYP.)
5 (TYP.) 5
(TYP.)
6 9
7 (TYP.)
7 (TYP.)
7 (TYP.)
8 (TYP.)
8 (TYP.)
8 (TYP.) 8
(TYP.) 8
(TYP.) 8
(TYP.)
9 10
(TYP.)
K 5 (TYP.)
EM
RD2
EX1
PLB
PLB
9
SP8 SP8
SP8 SP8
SP4
+9' A.F.F.
+9' A.F.F.
+9' A.F.F.
+9' A.F.F.
+9' A.F.F.
L24 L24 L24
L24
a a
a a
L24 L24
L24 L24
a a
a a
L24 12
(TYP.)
12 (TYP.)
L24
L24 L24 L24
L24 L24
L24
EX1
b
L24 L24
1
H EC VI K
OF
HN F.
TTA
S E
CO GIN EER
ON L E A
I N
NO.
S E N
ROFES ED M
P EW
12498
I X I
RE
G
J
STE R
O
MARK
PROJECT NO:
5 4
3 2
1
E
D
C
B
A
CAD DWG FILE:
DRAWN BY:
CHECKED BY:
COPYRIGHT: Cherry/See/Reames PC 2013
DATE DESCRIPTION
ISSUE:
1
C
CHERRY/SEE/REAMES ARCHITECTS, PC
505 - 842 - 1278 fax 505 - 766 - 9269 www.cherryseereames.com
MANAGEMENT BLOCK
LIGHTING SECOND FLOOR PLAN
507
EL102
EC A @ C EC Mo de rn iza tio n, Re nov at io n & A ddit ion 80 7 M oun tai n R oad NE Albuq ue rq ue , NM 8 7102
Author Checker
01/11/2021 100% CD
SCALE
EL102 3/32" =
1'-0"
A1 LIGHTING FLOOR PLAN - LEVEL 2
0' 5' 10' 20'
GENERAL SHEET NOTES
KEYNOTES
A. IT WILL BE THE CONTRACTOR’S OBLIGATION TO INCLUDE, IN THEIR BID, THE COSTS FOR INSTALLING JUNCTION BOXES, PROVIDING MISCELLANEOUS COVERS, WORK WITH OTHER DISCIPLINES WHERE THE CONTRACT INVOLVES ELECTRICAL POWER OR CONTROL CONNECTIONS, SWITCHES, ETC. ALL OF THIS WORK SHALL BE PART OF THIS CONTRACT.
B. LOCATION OF EQUIPMENT AND OTHER DEVICES SHOWN ON THE PLANS ARE APPROXIMATE AND SHALL BE FIELD VERIFIED.
C. THE CONDUIT RUNS, AS SHOWN ON PLANS, INDICATE APPROXIMATE ROUTING.
EXACT LOCATION OF CONDUIT RUNS SHALL BE AS FIELD CONDITIONS DICTATE.
D. CONTRACTOR SHALL INSTALL PULL AND JUNCTION BOXES WHEREVER REQUIRED BY N.E.C. OR JOB CONDITIONS. ALL NEW WIRING SHALL BE TAGGED AT ALL PULL BOXES, JUNCTION BOXES, EQUIPMENT BOXES AND CABINETS WITH APPROVED PLASTIC TAGS. ACTION CRAFT, BRADY OR APPROVED EQUAL.
E. THE CONTRACTOR SHALL INSTALL TIE HANDLES OR MULTI-POLE BREAKERS FOR ALL CIRCUITS SHARING A NEUTRAL CONDUCTOR.
F. SHOULD CONTRACTOR AT ANY TIME NOTICE THAT THE ACTUAL FIELD CONDITIONS DO NOT CORRESPOND TO THE INFORMATION GIVEN ON THE DRAWINGS, THEN IT WILL BE THEIR RESPONSIBILITY TO NOTIFY THE ENGINEER FOR CLARIFICATION, PRIOR TO COMMENCING SUCH WORK.
G. REMOVE AND INSTALL CEILING SUPPORTS AND TILES AS REQUIRED FOR THE COMPLETION OF THIS PROJECT. THIS CONTRACTOR SHALL INCLUDE REPLACEMENT OF CEILING TILES DAMAGED IN THE PROCESS OF THIS INSTALLATION WITH NEW MATCHING TILES. THE SAME APPLIES TO DAMAGE DONE TO OTHER KINDS OF CEILINGS.
H. CONTRACTOR SHALL MAKE AS-BUILT DRAWINGS DOCUMENTING ANY AND ALL WIRING AND EQUIPMENT CONDITIONS AND CHANGES WHILE COMPLETING THIS CONTRACT. PROVIDE UPDATED TYPEWRITTEN DIRECTORIES FOR ALL PANELS AND LABEL ALL PANELS WITH PLASTIC LAMINATED NAMEPLATES.
I. INSTALL BLANK DEVICE PLATES ON ALL UNUSED JUNCTION BOXES IN FINISHED AREAS.
J. REFER TO POWER PLANS FOR DETAILED LAYOUTS OF ELECTRICAL GEAR.
K. WHEREVER REQUIRED, FURNISH AND INSTALL ON WALL OR CEILING FREESTANDING UNISTRUT CHANNELS, ANGLE IRONS OR ANY OTHER SUPPORT STRUCTURE WITH THREADED ROD HANGERS AS REQUIRED FOR THE SUPPORT OF ELECTRICAL EQUIPMENT OF ANY KIND TO ENSURE PROPER INSTALLATION.
L. ALL HOME RUN CIRCUITING TO PANELS SHALL BE .75" CONDUIT, MINIMUM.
M. MOUNTING HEIGHTS INDICATED ON THE DRAWINGS ARE APPROXIMATE. THIS CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING WITH OTHER TRADES FOR EXACT HEIGHT REQUIRED. THIS REQUIREMENT ALSO APPLIES TO THE LOCATION OF WALL BOXES FOR HVAC SENSORS, T-STATS, ETC. ANY THIS NOTE APPLIES TO ALL ELECTRICAL SHEETS IN THESE DRAWINGS: OUTLET DEVICES THAT HAVE TO BE RELOCATED DUE TO COUNTERTOP, CHALKBOARD, TACKBOARD, TYPE CONFLICTS WILL BE DONE AT NO ADDITIONAL COST TO THE OWNER.
N. ALL PENETRATIONS THROUGH FIRE RATED ASSEMBLIES SHALL BE SEALED WITH FIRE STOPPING, IE. 3M BRAND CALK, PUTTY, STRIP AND SHEET FORMS, DOW CORNERING 3-6548 SILICONE RTV FOAM
O. ALL LOW VOLTAGE CONDUCTORS SHALL BE RAN IN SEPARATE RACEWAYS AS POWER CONDUCTORS (120VAC OR HIGHER PHASE TO NEUTRAL), NO EXCEPTIONS.
P. PHASE SEQUENCING SHALL BE PROVIDED AND MAINTAINED THROUGHOUT THE ELECTRICAL DISTRIBUTION SYSTEM PER APS STANDARDS.
1. PROVIDE AND INSTALL CEILING MOUNTED OCCUPANCY SENSOR. SET TIME FOR 15 MINUTES. REFER TO LIGHTING CONTROL SEQUENCE OF OPERATION.
2. INDICATES PHOTOSENSOR IN CEILING. PROGRAM TO MAINTAIN 50 FC'S IN
ASSOCIATED CLASSROOM. REFER TO CONTROL DIAGRAMS AND LIGHTING CONTROL SEQUENCE OF OPERATION.
3. PROVIDE AND INSTALL CEILING MOUNTED INFRA-RED OCCUPANCY SENSOR. SET TIME FOR 10 MINS. REFER TO LIGHTING CONTRL SEQUENCE OF OPERATION.
4. COORDINATE MOUNTING HEIGHTS OF EMERGENCY FIXTURES IN CLASSROOMS AND OFFICES WITH ARCHITECTURAL TO AVOID CONFLICTS WITH TEACHING WALL
EQUIPMENT.
5. PROVIDE KEYED MAINTENANCE SWITCH IN CLASSROOMS PER APS DESIGN STANDARDS.
6. PROVIDE KEYED MAINTENANCE SWITCH IN RESTROOMS PER APS DESIGN STANDARDS.
7. PROVIDE 0-10V DIMMING SWITCHES COMPATIBLE WITH LIGHTING FIXTURE MANUFACTURER AND KEYED OVERRIDE SWITCH. REFER TO LIGHTING CONTROL SEQUENCE OF OPERATION. REFER TO CLASSROOM SWITCHBANK DETAIL FOR ADDITIONAL REQUIREMENTS OF ASSOCIATED SWITCHING.
8. CONNECT CORRIDOR LIGHTING THROUGH LIGHTING CONTROL RELAY PANEL. SEE LIGHTING CONTROL SEQUENCE OF OPERATION AND CONTROL DIAGRAM.
9. CONNECT EXTERIOR LIGHTING THROUGH NEW RELAY LIGHTING CONTROLLER.
REFER TO CONTROL DIAGRAMS AND LIGHTING CONTROL SEQUENCE OF OPERATION.
10. EMERGENCY FIXTURE MOUNTED 8' 6" ABOVE STAIRWELL STEP.
11. EMERGENCY FIXTURE MOUNTED TO CEILING ABOVE STAIRWELL LANDING.
12. PROVIDE EACH ROW OF FIXTURES WITH AN INDIVIDUAL REMOTE DRIVER IN NEMA 1 ENCLOSURE SIZED PER MANUFACTURER. DRIVER TO BE LOCATED INSIDE
CORRIDOR ON WALL ABOVE CEILING. COORDINATE EXACT LOCATION PER ARCHITECTURAL DETAILS. PAINT PER ARCHITECT'S INSTRUCTIONS.
1 02/05/2021 ADDENDUM #2
ADDENDUM No. 2
EXHIBIT 05
DN DN
C
C
C
C C
C C
44"
44"
44"
44"
HALL 248 GIRLS
237
BOYS 238
Unoccupied Unoccupied
STAIR 250 HALL
245 HALL
216
215 23 214
213 20 19 212
16 15 211 210 102 13
103 104 11 209 208 105
9 207 206 205 204
6 107 203 108 202
3 109
1 201 110
J A
20A 20B 20C B 20D
20E
20F 20G C 20H 20J D E F G
2
4
7 5
R
8
12
14
18 17
CLASSROOM 236
NURSING STAFF HOMEBASE
230 CLASSROOM
231
NURSING LAB 242 ROOF DECK
235
NURSING CLASS
244 NURSING
CLASS 243
CLASSROOM 232 CLASSROOM
233 CLASSROOM
234
NURSING STOR
240 NURSING DIRECTOR
239 HUDDLE ROOM
241 2L1 2P1
FCU-31
FCU-32
G G
2P1 - 1 2P1 - 2
2P1 - 3
2P1 - 74 2P1 - 5
2P1 - 6
2P1 - 71 2P1 - 8
2P1 - 9
USB
FCU-33
FCU-34
G
2P1 - 10 FCU-35
WG
WG
FCU-30 FCU-29
FCU-28 FCU-27
WG
2P1 - 11 2P1 - 12
2P1 - 13 2P1 - 14 2P1 - 15
2P1 - 16 2P1 - 17
2P1 - 18
2P1 - 19
+7'-0"
+7'-0"
+7'-0"
+7'-0"
+7'-0"
+7'-0" +7'-0"
2P1 - 20 2P1 - 21
2P1 - 47,49
2P1 - 50,52
2P1 - 51,53 2P1 - 54,56
G
2P1 - 69
2P1 - 70
2P1 - 7
1 (TYP.)
2P1 - 72
2P1 - 73
2P1 - 4
1 (TYP.)
1
H EC VI K
OF
HN F.
TTA
S E
CO GIN EER
ON L E A
I N
NO.
S E N
ROFES ED M
P EW
12498
I X I
RE
G
J
STE R
O
MARK
PROJECT NO:
5 4
3 2
1
E
D
C
B
A
CAD DWG FILE:
DRAWN BY:
CHECKED BY:
COPYRIGHT: Cherry/See/Reames PC 2013
DATE DESCRIPTION
ISSUE:
1
C
CHERRY/SEE/REAMES ARCHITECTS, PC
505 - 842 - 1278 fax 505 - 766 - 9269 www.cherryseereames.com
MANAGEMENT BLOCK
POWER SECOND FLOOR PLAN
507
EP102
EC A @ C EC Mo de rn iza tio n, Re nov at io n & A ddit ion 80 7 M oun tai n R oad NE Albuq ue rq ue , NM 8 7102
Author Checker
01/11/2021 100% CD
SCALE
EP102 3/32" =
1'-0"
A1 POWER FLOOR PLAN - LEVEL 2
0' 5' 10' 20'
GENERAL SHEET NOTES
KEYNOTES
1. PROVIDE OUTLETS IN BED HEAD BOARD. REFER TO ARCHITECTURAL ELEVATION FOR OUTLET DETAIL AND REQUIREMENTS.
A. CONTRACTOR SHALL INSTALL PULL AND JUNCTION BOXES WHEREVER REQUIRED BY N.E.C. OR JOB CONDITIONS. ALL NEW WIRING SHALL BE TAGGED AT ALL PULL BOXES, JUNCTION BOXES, EQUIPMENT BOXES AND CABINETS WITH APPROVED PLASTIC TAGS.
ACTION CRAFT, BRADY OR APPROVED EQUAL.
B. THE CONTRACTOR SHALL INSTALL TIE HANDLES OR MULTI-POLE BREAKERS FOR ALL CIRCUITS SHARING A NEUTRAL CONDUCTOR.
C. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO COORDINATE WITH ALL TRADES FOR THE EXACT LOCATION OF EQUIPMENT AND APPURTENANCES THAT REQUIRE ELECTRICAL CONNECTIONS AND PROVIDE ALIGNMENT OF DEVICES.
D. ALL HOME RUN CIRCUITING TO PANELS SHALL BE .75" CONDUIT, MINIMUM.
E. MOUNTING HEIGHTS INDICATED ON THE DRAWINGS ARE APPROXIMATE. THIS CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING WITH OTHER TRADES FOR EXACT HEIGHT
REQUIRED. THIS REQUIREMENT ALSO APPLIES TO THE LOCATION OF WALL BOXES FOR HVAC SENSORS, T-STATS, ETC. ANY THIS NOTE APPLIES TO ALL ELECTRICAL SHEETS IN THESE DRAWINGS: OUTLET DEVICES THAT HAVE TO BE RELOCATED DUE TO COUNTERTOP, CHALKBOARD, TACKBOARD, TYPE CONFLICTS WILL BE DONE AT NO ADDITIONAL COST TO THE OWNER. ALIGNMENT OF ALL DEVICES SHALL BE COORDINATE IN THE FIELD SO THAT ALL DEVICES SHARE A COMMON MOUNTING PLANE.
F. ALL PENETRATIONS THROUGH FIRE RATED ASSEMBLIES SHALL BE SEALED WITH FIRE STOPPING, IE. 3M BRAND CALK, PUTTY, STRIP AND SHEET FORMS, DOW CORNERING 3-6548 SILICONE RTV FOAM G. ALL LOW VOLTAGE CONDUCTORS SHALL BE RAN IN SEPARATE RACEWAYS AS POWER CONDUCTORS (120VAC OR HIGHER PHASE TO NEUTRAL), NO EXCEPTIONS.
H. PHASE SEQUENCING SHALL BE PROVIDED AND MAINTAINED THROUGHOUT THE ELECTRICAL DISTRIBUTION SYSTEM. PHASE ARRANGEMENT ON 3-PHASE BUSES SHALL BE A,B,C FROM FRONT TO BACK, TOP TO BOTTOM, OR LEFT TO RIGHT AS VIEWED FROM THE FRONT OF THE SWITCHBOARD OR PANEL BOARD. (PHASE A SHALL BE MAINTAINED AS PHASE A FROM THE DISTRIBUTION TRANSFORMER TO EACH PANEL BOARD OR SWITCHBOARD).
I. ALL BRANCH AND FEEDER CIRCUIT WIRING SHALL BE COLOR CODED THROUGHOUT THE ENTIRE ELECTRICAL DISTRIBUTION SYSTEM.
KEYPLAN
1
1 02/05/2021 ADDENDUM #2
ADDENDUM No. 2
EXHIBIT 06
H EC VI K
OF
HN F.
TTA
S E
CO GIN EER
ON L E A
I N
NO.
S E N
ROFES ED M
P EW
12498
I X I
RE
G
J
STE R
O
MARK
PROJECT NO:
5 4
3 2
1
E
D
C
B
A
CAD DWG FILE:
DRAWN BY:
CHECKED BY:
COPYRIGHT: Cherry/See/Reames PC 2013
DATE DESCRIPTION
ISSUE:
1
C
CHERRY/SEE/REAMES ARCHITECTS, PC
505 - 842 - 1278 fax 505 - 766 - 9269 www.cherryseereames.com
MANAGEMENT BLOCK
ELECTRICAL SCHEDULES
507
E-701
EC A @ C EC Mo de rn iza tio n, Re nov at io n & A ddit ion 80 7 M oun tai n R oad NE Albuq ue rq ue , NM 8 7102
Author Checker
01/11/2021 100% CD
LUMINAIRE SCHEDULE NOTES:
1. MANUFACTURERS CATALOG NUMBERS REPRESENT MANUFACTURER SERIES. SHOP DRAWING SUBMITTALS WILL INCLUDE ALL PART NUMBERS REPRESENTING ALL ITEMS OF THIS LUMINAIRE SCHEDULE. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO ORDER LUMINAIRES TO INCLUDE ALL PARTS INDICATED ON SCHEDULE FOR EACH LUMINAIRE. SUBMITTAL WILL CALL OUT EACH PART CLEARLY.
2. LUMINAIRE REQUIRES MOUNTING COORDINATION WITH ARCHITECT PRIOR TO COMMENCEMENT OF ANY WORK. THIS LUMINAIRE MAY REQUIRE A HIGHER OR LOWER MOUTING FROM THAT PROVIDED ON THIS SCHEDULE OR NOTES ON PLAN DUE TO ARCHITECTURAL REQUIREMENTS OR CONSTRUCTION CONDITIONS.
3. ALL LUMINAIRES ON THIS LUMINAIRE SCHEDULED ARE APPROVED FOR BID ON THIS PROJECT. IF A LUMINAIRE IS SUBMITTED THAT IS NOT ON THIS SCHEDULE IT WILL BE REJECTED.
Notes:
MTR 172872 VA 100.00% 172872 VA Total Est. Demand: 1635 A
NC 1153446 VA 100.00% 1153446 VA Total Conn.: 1652 A
REC 41100 VA 62.17% 25550 VA Total Est. Demand: 1359007 VA
LTG 5711 VA 125.00% 7139 VA Total Conn. Load: 1373129 VA
Other 0 VA 0.00% 0 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Amps: 1652 A Total Conn. Load: 1373129 VA 20
19 18 17 16 15 14 13 12 11 10 9 8 7
6 EXISTING PANEL "MDP" 3 600 A 600 A 391250 VA
5 EXISTING PANEL "MD" 3 800 A 800 A 737500 VA
4 ERV-2 3 20 A 20 A 10304 VA
3 ERV-3 3 20 A 20 A 10304 VA
2 2L1 3 100 A 100 A 213467 VA
1 ERV-1 3 20 A 20 A 10304 VA
CKT Circuit Description # of Poles Frame Size Trip Rating Load Remarks
Notes:
Enclosure: MCB Rating: 2000 A
Mounting: Wires: 4 Mains Rating: 2000 A
Supply From: Phases: 3 Mains Type: MCB
Location: Space 200 Volts: 480/277 Wye A.I.C. Rating: 65 KAIC
Switchboard: MDS
Notes:
Total Est. Demand Current: 164 A Total Conn. Current: 208 A
REC 41100 VA 62.17% 25550 VA Total Est. Demand: 59246 VA
MTR 9000 VA 100.00% 9000 VA Total Conn. Load: 74796 VA
NC 24696 VA 100.00% 24696 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Amps: 205 A 209 A 211 A
Total Load: 24576 VA 24996 VA 25224 VA
41 -- -- -- 1916... 42
39 -- -- -- 1923... 40
37 2P1 225 A 3 1887... 38
35 Spare 20 A 1 0 VA 36
33 Spare 20 A 1 0 VA 34
31 Spare 20 A 1 0 VA 32
29 Spare 20 A 1 0 VA 30
27 Spare 20 A 1 0 VA 28
25 Spare 20 A 1 0 VA 26
23 REC 20 A 1 900 VA 900 VA 1 20 A REC 24
21 REC 20 A 1 900 VA 900 VA 1 20 A REC 22
19 REC 20 A 1 900 VA 900 VA 1 20 A REC 20
17 REC 20 A 1 900 VA 900 VA 1 20 A REC 18
15 REC 20 A 1 900 VA 900 VA 1 20 A REC 16
13 REC 20 A 1 900 VA 900 VA 1 20 A REC 14
11 REC 20 A 1 600 VA 900 VA 1 20 A REC 12
9 REC 20 A 1 360 VA 600 VA 1 20 A REC 10
7 REC 20 A 1 600 VA 600 VA 1 20 A REC 8
5 REC 20 A 1 600 VA 360 VA 1 20 A REC 6
3 REC 20 A 1 600 VA 600 VA 1 20 A REC 4
1 REC 20 A 1 720 VA 180 VA 1 20 A REC 2
CKT Circuit Description Notes Trip Poles A B C Poles Trip Notes Circuit Description CKT
Notes:
Enclosure: Type 1 Spaces: 84 MCB Rating:
Mounting: Surface Wires: 4 Mains Rating: 225 A
Supply From: TCP1 Phases: 3 Mains Type:
Location: ELEC 103B Volts: 120/208 Wye A.I.C. Rating:
Branch Panel: CP1
ELECTRICAL LUMINAIRE SCHEDULE
Type DESCRIPTION MOUNTING VOLTS MANUFACTURER / MODEL
LUMEN OUTPUT
COLOR TEMP (K)
Apparent
Load NOTES
EM EMERGENCY LED FIXTURE WALL MOUNTED 277
VOLTS
DUAL LITE #EV 4 I 0 0 12 VA
EX1 UNIVERSAL MOUNTED LED EXIT FIXTURE UNIVERSAL 277 VOLTS
DUAL LITE #EVE-U-R-W-E-I 0 0 13 VA
KLS 4' STRIPLIGHT LED LENSED SURFACE/HUNG 277
VOLTS
COLUMBIA #LCL 4 35 ML E 5000 35 48 VA
L22 2X2 LAY-IN/RECESSED LED FIXTURE - ARCH.
GULLWING
LAY-IN/RECESSED 277 VOLTS
FOCAL POINT #FAML 22 ACR 4000HL / 35K 1C UNV / LD1 4000 35 32 VA L24 2X4 LAY-IN/RECESSED LED FIXTURE - ARCH.
GULLWING
LAY-IN/RECESSED 277 VOLTS
FOCAL POINT #FAML 24 ACR 4000L / 35K 1C UNV / LD1 4000 35 43 VA M24 GASKETED 2X4 LAY-IN/RECESSED LED FIXTURE -
ARCH. GULLWING
LAY-IN/RECESSED 277 VOLTS
COLUMBIA #LJT 24-35LW-FAA12-EDU-G1FK24 4000 35 43 VA PLB 6' LINEAR LED WALL MOUNTED FIXTURE FLUSHED
LENS
WALL MOUNTED 277 VOLTS
FOAL POINT #FSM4BW FLFL 625DN 375UP 35K 1C UNV LD1 WM WH 6'
3750 25 VA
RD2 4.5" SQUARE RECESSED LED DOWN LIGHT MED OUTPUT
RECESSED 277
VOLTS
FOCAL POINT #FLC44D ST 1500L / 277V LD1 T 1500 35 19 VA SP4 4' LINEAR LED PENDANT MOUNTED FIXTURE PENDANT 277
VOLTS
ORACLE #OLS-D-LED-2-S-W4-750L-DIM10MVOLT-35K-90-WH 2500 35 30 VA SP8 8' LINEAR LED PENDANT MOUNTED FIXTURE PENDANT 277
VOLTS
ORACLE #OLS-D-LED-2-S-W8-750L-DIM10MVOLT-35K-90-WH 5000 35 30 VA SR4 4' LINEAR LED RECESSED MOUNTED FIXTURE LAY-IN/RECESSED 277
VOLTS
ORACLE #OLS-R-LED-2--S-4-500L-DIM10-MVOLT-35K-90-WH 2000 35 13 VA SR6 6' LINEAR LED RECESSED MOUNTED FIXTURE LAY-IN/RECESSED 277
VOLTS
ORACLE #OLS-R-LED-2--S-6-500L-DIM10-MVOLT-35K-90-WH 3000 35 19 VA SR7 7' LINEAR LED RECESSED MOUNTED FIXTURE LAY-IN/RECESSED 277
VOLTS
ORACLE
#OLS-R-LED-2--CR-7-500L-DIM10-MVOLT-35K-90-WH
3500 35 20 VA
SR8 8' LINEAR LED RECESSED MOUNTED FIXTURE LAY-IN/RECESSED 277 VOLTS
ORACLE #OLS-R-LED-2--S-8-500L-DIM10-MVOLT-35K-90-WH 4000 35 30 VA SR9 9' LINEAR LED RECESSED MOUNTED FIXTURE LAY-IN/RECESSED 277
VOLTS
ORACLE
#OLS-R-LED-2--CR-9-500L-DIM10-MVOLT-35K-90-WH
4500 35 35 VA
SRL LINEAR LED RECESSED FIXTURE - LENGTH PER PLAN FLUSHED LENS
LAY-IN/RECESSED 277 VOLTS
ORACLE
#OLS-R-LED-2--CR---500L-DIM10-MVOLT-35K-90-WH
2250 35 35 VA
SW2 2' LINEAR EXTERIOR LED RECESSED MOUNTED FIXTURE
SURFACE 277
VOLTS
SONARAY #LB-4–060-S–N–F–8–30–BLK–U 1750 35 10 VA
SW6 6' LINEAR EXTERIOR LED RECESSED MOUNTED FIXTURE
SURFACE 277
VOLTS
SONARAY #LB-4–060-L–N–F–8–30–BLK–U 3000 35 20 VA
SW6A 6' LINEAR LED RECESSED MOUNTED FIXTURE LAY-IN/RECESSED 277 VOLTS
SONARAY #LB-4–060-L–N–F–8–30–BLK–U 3000 35 19 VA
SW8 8' LINEAR EXTERIOR LED RECESSED MOUNTED FIXTURE
SURFACE 277
VOLTS
SONARAY #LB-4–060-XL–N–F–8–30–BLK–U 3000 35 20 VA
Notes:
LTG 5711 VA 125.00% 7139 VA Total Est. Demand Current: 240 A
REC 41100 VA 62.17% 25550 VA Total Conn. Current: 257 A
MTR 141960 VA 100.00% 141960 VA Total Est. Demand: 199345 VA
NC 24696 VA 100.00% 24696 VA Total Conn. Load: 213467 VA
Other 0 VA 0.00% 0 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Amps: 258 A 255 A 259 A
Total Load: 71364 VA 70563 VA 71540 VA
41 -- -- -- 2522... 4432... -- -- -- 42
39 -- -- -- 2499... 4432... -- -- -- 40
37 PANEL "CP1" 150 A 3 2457... 4432... 3 25 A HP-3 38
35 Spare 20 A 1 0 VA 4432... -- -- -- 36
33 Spare 20 A 1 0 VA 4432... -- -- -- 34
31 Spare 20 A 1 0 VA 4432... 3 30 A HP-3 32
29 -- -- -- 4432... 4432... -- -- -- 30
27 -- -- -- 4432... 4432... -- -- -- 28
25 HP-1 25 A 3 4432... 4432... 3 30 A HP-2 26
23 -- -- -- 4432... 4432... -- -- -- 24
21 -- -- -- 4432... 4432... -- -- -- 22
19 HP-1 30 A 3 4432... 4432... 3 30 A HP-2 20
17 -- -- -- 4432... 4432... -- -- -- 18
15 -- -- -- 4432... 4432... -- -- -- 16
13 HP-4 25 A 3 4432... 4432... 3 25 A HP-5 14
11 -- -- -- 4432... 4432... -- -- -- 12
9 -- -- -- 4432... 4432... -- -- -- 10
7 HP-4 30 A 3 4432... 4432... 3 25 A HP-5 8
5 LTG ROOF TOP DECK 235 20 A 1 190 VA 1806... 1 20 A LTG NURSING LAB 242 6
3 LTG HALL 249 20 A 1 472 VA 775 VA 1 20 A LTG CLASS ROOM 236 4
1 LTG NURSING STAFF HOMEBASE 230 20 A 1 1720... 748 VA 1 20 A LTG HALL 246 2
CKT Circuit Description Notes Trip Poles A B C Poles Trip Notes Circuit Description CKT
Notes:
Enclosure: Type 1 Spaces: 42 MCB Rating:
Mounting: Recessed Wires: 4 Mains Rating: 400 A
Supply From: MDS Phases: 3 Mains Type:
Location: NURSING STAFF HOMEBASE... Volts: 480/277 Wye A.I.C. Rating:
Branch Panel: 2L1
Notes:
Total Est. Demand Current: 140 A Total Conn. Current: 159 A
REC 23580 VA 71.20% 16790 VA Total Est. Demand: 50486 VA
MTR 9000 VA 100.00% 9000 VA Total Conn. Load: 57276 VA
NC 24696 VA 100.00% 24696 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Amps: 157 A 161 A 160 A
Total Load: 18876 VA 19236 VA 19164 VA
83 84
81 82
79 80
77 78
75 76
73 REC NURSING LAB 242 20 A 1 180 VA 1260... 1 20 A REC NURSING LAB 242 74
71 REC NURSING LAB 242 20 A 1 1260... 900 VA 1 20 A REC NURSING LAB 242 72
69 REC NURSING LAB 242 20 A 1 180 VA 1260... 1 20 A REC NURSING LAB 242 70
67 Spare 20 A 1 0 VA 1500... -- -- -- 68
65 Spare 20 A 1 0 VA 1500... 2 20 A CU-3 66
63 Spare 20 A 1 0 VA 1500... -- -- -- 64
61 Spare 20 A 1 0 VA 1500... 2 20 A CU-2 62
59 Spare 20 A 1 0 VA 1500... -- -- -- 60
57 Spare 20 A 1 0 VA 1500... 2 20 A CU-1 58
55 Spare 20 A 1 0 VA 0 VA -- -- -- 56
53 -- -- -- 0 VA 360 VA 2 20 A NC HALL 249 54
51 NC HALL 248 20 A 2 180 VA 0 VA -- -- -- 52
49 -- -- -- 0 VA 360 VA 2 20 A NC HALL 246 50
47 NC HALL 245 20 A 2 540 VA 792 VA -- -- -- 48
45 -- -- -- 792 VA 792 VA 2 20 A FCU 46
43 FCU 20 A 2 792 VA 792 VA -- -- -- 44
41 -- -- -- 792 VA 792 VA 2 20 A FCU 42
39 FCU 20 A 2 792 VA 792 VA -- -- -- 40
37 -- -- -- 396 VA 792 VA 2 20 A FCU 38
35 FCU 20 A 2 396 VA 792 VA -- -- -- 36
33 -- -- -- 1188... 792 VA 2 20 A FCU 34
31 FCU 20 A 2 1188... 792 VA -- -- -- 32
29 -- -- -- 1188... 792 VA 2 20 A FCU 30
27 FCU 20 A 2 1188... 792 VA -- -- -- 28
25 -- -- -- 792 VA 792 VA 2 20 A FCU 26
23 FCU 20 A 2 792 VA 1188... -- -- -- 24
21 REC NURSING STAFF HOMEBASE 230 20 A 1 900 VA 1188... 2 20 A FCU 22
19 REC CLASS ROOM 231 20 A 1 900 VA 720 VA 1 20 A REC HALL 246 20
17 REC CLASS ROOM 232 20 A 1 900 VA 1080... 1 20 A REC CLASS ROOM 231 18
15 REC CLASS ROOM 233 20 A 1 900 VA 1080... 1 20 A REC HALL 245 16
13 REC CLASS ROOM 234 20 A 1 720 VA 900 VA 1 20 A REC CLASS ROOM 233 14
11 REC HALL 246 20 A 1 180 VA 900 VA 1 20 A REC CLASS ROOM 234 12
9 REC CLASS ROOM 236 20 A 1 180 VA 1080... 1 20 A REC HALL 249 10
7 REC NURSING LAB 242 20 A 1 1260... 1080... 1 20 A REC CLASS ROOM 236 8
5 REC NURSING LAB 242 20 A 1 1260... 1260... 1 20 A REC NURSING LAB 242 6
3 REC NURSING CLASS 243 20 A 1 900 VA 1260... 1 20 A REC NURSING LAB 242 4
1 REC NURSING CLASS 244 20 A 1 1080... 1080... 1 20 A REC NURSING CLASS 244 2
CKT Circuit Description Notes Trip Poles A B C Poles Trip Notes Circuit Description CKT
Notes:
Enclosure: Type 1 Spaces: 84
Mounting: Recessed Wires: 4 Mains Rating: 225 A
Supply From: CP1 Phases: 3 Mains Type:
Location: NURSING STAFF HOMEBASE... Volts: 120/208 Wye A.I.C. Rating:
Branch Panel: 2P1
SPD
3
100 A 60 A
3
SPACE 3 225 A
SPACE 3 225 A
PNM XFRMR PAD/WALL NEMA 3R
10 KAIC MCB 225 A
35 KAIC MLO N/A
10 KAIC MLO 1
1 02/05/2021 ADDENDUM #2