IES <Virtual Environment> training

Trainee notes

ASHRAE 90.1 Appendix G - PRM Navigator

Version 6.4.0.7

Introduction

These training notes are to be used in conjunction with your ASHRAE 90.1 Appendix G - PRM Navigator training.

In this training session you will be shown how to use the ASHRAE 90.1 Appendix G - PRM Navigator, IES’s sustainable design workflow navigator, available as an option within the IES <Virtual Environment>.

Henceforth in this document we will simply refer to this navigator as the “PRM Navigator”.

Prior to using the PRM Navigator, you will need to use ModelIT or the Model Geometry navigator to create the building geometry from scratch or to edit the geometry. You can also edit geometry which has been imported from SketchUp or Revit (via the IES SketchUp or Revit plugins) or via a gbXML import.

This PRM Navigator training assumes that you have already been trained in ModelIT, ApacheSim and ApacheHVAC.

These notes accompany your training and act as a reference point for your further study. The trainer will show you how to perform various functions as shown in the following pages.

For more detailed help you can use the Help menu within the specific IES application, and also you can refer to the user guides accessible from the <VE> Help menu.

(2)

Background

The PRM (Performance Rating Method) is an assessment method for buildings. It is based on ASHRAE 90.1 Appendix G (Appendix G is compulsory in certain US states) and is based on running costs rather than energy. The PRM can be used in the UK for LEED analysis projects.

The PRM is used to determine credit points awarded for percentage energy cost savings (via LEED EA Credit 1and 2 for new construction, renovation, core and shell or schools projects).

The PRM is based on running costs rather than energy or carbon dioxide emissions. The PRM compares a proposed building against the average of four baseline buildings. The thermal templates for the baseline buildings are not fixed – they can be edited.

For PRM analyses you need full design information - the PRM method is not used for early stage design.

14 energy end uses are reported in the PRM report such as interior lighting, exterior lighting, elevators, pumps and “receptacle” equipment (eg computers).

Opening the model

(3)

Accessing the PRM Navigator

You will first be shown how to access the PRM navigator.

The PRM navigator is divided into a series of main sections, each of these with sub-sections.

Navigator Quality Assurance functions

Each navigator item has a notepad which is useful for recording settings and assumptions. There is a check box (to remind you that you have completed that item) and an optional date/time stamp.

(4)

PRM navigator items

Preliminary data setup

Workflow concept

This item gives general help about the PRM concept and an overview of the PRM navigator.

Site, location and climate

Here you set the location and climate data, Use the wizard, and select the ASHRAE database for the design weather data. Enable the “V 3.0 for PRM” check box. This will select the correct ASHRAE weather percentiles for heating and cooling loads calculations. Select the required climate file for the simulation and the required holiday template.

Prototype data (ASHRAE baseline)

Select the 90_1_2007_IP.mit file. This brings in predefined templates based on the ASHRAE 90.1 2007 user guide and also brings in standard profiles and grouping schemes. This is used as a starting point. You could if you wish, create and use your own profiles for both the proposed and baseline buildings.

(5)

Building geometry

To create and edit the building geometry, or to import the building geometry you need to use the Model Geometry navigator (model geometry creation and editing is covered in separate ModelIT training sessions).

Site obstructions and shading

This is covered in ModelIT and SunCast training (separate training sessions). The building orientation is important. Note that shading objects and SunCast analyses are for the proposed building only and are not relevant for the baseline buildings.

Room/Zone group assignment

This stage is important. This tool assigns rooms to preloaded room groups very quickly. We will use the “Word Search” option to do this. First, click “Extract”, to extract the schemes from the current model. We will use the “Space by space method” grouping schemes in this example when performing the word search. You can then look at the groups in the model browser and see the rooms assigned to them. You could also assign rooms to groups manually if you need to.

Solar Shading calculations

(6)

Envelope thermo-physical properties

ASHRAE baseline constructions

This will import ASHRAE baseline constructions to the project. The climate zone dictates the constructions that are imported as per ASHRAE 90.1 section 5 guidelines.

Proposed building constructions

Improve baseline

Improve your proposed building constructions to be better than the baseline constructions. This imports other opaque ASHRAE wall constructions if required. You will then need to assign the new constructions using the Apply button or assigning them afterwards.

Custom construction type

You can create your own constructions using APcdb and then apply them.

Surface assignment

Above ground

Assign surfaces to the proposed building if required for rooms above Z=0 (you only need to do this if you haven’t clicked Apply when improving your baseline above)

Ground contact

(7)

Room/Zone thermal template data

Space classification

Assigns thermal templates to zones by matching room group names to the template names for both the baseline and proposed buildings. Note: that this won’t work properly if you haven’t set up room groups properly first.

Internal heat gains

Equipment

There should be the same values in the proposed and baseline buildings – you will get a warning if the values are different. Leaving the proposed cells blank assigns the baseline values to the proposed values.

People

Sets the occupancy data for baseline and proposed buildings (the same for both buildings). Lighting

Sets the lighting gains for the proposed buildings. The gains for the baseline building are fixed. The 10% reduction option reduces any current values by 10% each time you use this option.

(8)

ASHRAE 62.1 parameters

These are minimum fresh air ventilation requirements for ASHRAE 62.1. They are the same for proposed and baseline buildings.

Note: This option is only applicable for early stage design and not generally suitable for a full LEED analysis. You would either use this navigator item or the “Air Exchange >Outside Air Ventilation Rate (simple)“ navigator item below. The option of which rates methodology to use is chosen later in the process.

Occupancy and Ventilation tab

The Occupancy and Ventilation tab shows default values for both the the proposed and baseline buildings. The “Default Occupancy Density” column shows values from ASHRAE 62.1. Requirements are shown per person and per m2. You are only able to change the design occupancy and the percentage increase in ventilation for the proposed building. We will set the appropriate occupancy categories for the space types in our model.

Exhaust requirements tab

There are pre-set flow rates for different space categories. Rates are only required for the restrooms in this training example, Use the “toilets – public” category for restrooms (with say 1 unit) and set the categories for other spaces to “none”.

Zone Air Distribution tab

Here we set any local regulations requirements. We will just use the default values, which are typical. Ez is an efficiency factor to account for ventilation losses (eg Ez = 0.8 means that 80% of breathable air is delivered to the space and 20% is lost beforehand.

Air exchange

Outside air ventilation rate (simple)

This starts the building template manager in the System tab, and allows you to enter your own rates in “System outside air supply” if you prefer to use them instead of the ASHRAE 62.1 values above. The values are used later in the sizing calculations (not the simulations). The option of which rates methodology to use is chosen later in the process.

Infiltration

(9)

Other end uses

Exterior lighting

Enter areas/lengths as required. This calculates baseline values, then you can enter your proposed values. External lighting power (but no gains) is applied to the last room in the model browser. “Tradeable” refers to where you can improve the proposed values compared with the baseline values. “Non-tradeable” refers to where proposed values cannot be less than the baseline values, for example lighting on the building facade.

Elevators

Enter peak consumptions per elevator for both proposed and baseline buildings. This will not apply if there are no elevator spaces (ie no elevator thermal templates) in the project.

Service hot water

This starts the building template manager. The default consumption is zero. You need to enter your required consumption rates and profiles.

(10)

HVAC systems

Assign rooms

Use the “assign selected rooms to room groups” facility to apply zones to HVAC systems (eg by air handling units grouping schemes).

System schedules

Sets the times of day for plant operation, and setpoints. This automatically updates profiles (in APpro) for your baseline and proposed schedules. You can either amend the existing schedules or create additional (alternate) schedules using a prefix.

Baseline system

Here you create the HVAC system for the baseline building. Edit current baseline

The first time this option is clicked, the “Import prototype system” window will appear. You can then select the appropriate ASHRAE baseline system as per ASHRAE 90.1 tables G3.1.1A and 1B. For example, the appropriate system for non-residential buildings of 4 or 5 floors and less than 75,000 ft2 is System 5 or 6.

Select the appropriate systems (in this example we will chose System 5, VAV with reheat with a fossil fuel boiler), and these will appear in the ApacheHVAC view (Note: if you subsequently want to import more prototype systems, you will need to click the Import prototype system” icon in the ApacheHVAC toolbar).

We will then edit each multiplex and assign the rooms to the multiplexes using the “assign from Room Group” button and selecting the AHU room groups.

(11)

System parameters

You will see a list of your baseline HVAC systems where you can edit coil temperatures, oversizing factors and define energy saving measures if required. The “System” area in this dialogue box refers to the main AHU coils. The “Zone” area refers to the room level coils. Check to see if economisers are required for the project climate zone (ASHRAE table G3.1.2.6B).

When you click the Apply button, the 3 additional baseline systems (90, 180 and 270 Deg) are also created and this information is passed to the sizing spreadsheets which are located in, for example, Project name\loads data\90 deg baseline

Proposed system

Here you repeat the process as described for the baseline system above, but for your proposed system. You can use any of the first three options below.

Improve upon baseline

When you select this option this will create the “proposed.asp” ApacheHVAC file (which initially will be a copy of the baseline system) and this will be shown in the ApacheHVAC view. You can then improve/change the system to become your proposed system.

Note: if you have performed this step previously, the next time you select this option you will see a message warning you that the current proposed.asp file will be overwritten.

In this example we will use System 9c for the proposed system (active beams which can operate in heating or cooling mode).

We will then edit each multiplex and assign the rooms to the multiplexes using the “assign from Room Group” button and selecting the AHU room groups. This step is only necessary if you have deleted any of the baseline systems in the proposed .asp file and have replaced them with a different system.

Edit current proposed

If you have already generated a proposed system you can use this option to edit it.

Or custom system

(12)

Room conditions (setpoints)

This starts the building template manager in the Room Conditions tab where you can edit the heating/cooling setpoints or heating/cooling profiles if you wish to modify them at this stage, for both the baseline and proposed buildings.

Alternatively, you could select rooms by AHU group and edit this data using the Edit Group Attributes facility. This data is used for ASHRAE load calculations, HVAC system sizing purposes & unmet load hours checks. Note: this data is NOT used in the controllers in the HVAC networks when the PRM simulations are run.

Generally you may not need to use this workflow as default setpoints will have previously been set within the “System Schedules” dialogue. If all of your spaces have the same setpoint and operational hours across all templates then there should be little you need to do here.

However, if different setpoints are being used in the building or where any unconditioned spaces have OFF heating and cooling profiles, this should be set here in the template manager as this would play an important role in the unmet load hours checks.

(13)

Other input data

Renewable energy systems

You can set up renewable energy systems for the proposed building.

Define tariffs data

Here you create advanced tariff data (as opposed to simple flat rate tariffs) which can then be selected later in the Cost workflow. You don’t need to set tariff data prior to simulations. Tariff data can be set at any point prior to generating PRM reports.

Electricity

For this training example, select the “Commercial Unrestricted” tariff. Choose the bills to be made monthly. Select the Basic tariff type and for a standing monthly charge enter a monthly standing charge of £50.

Select “Time of use Rates” and create a regime eg “Annual Tariff”. Check the “Weekday off-peak”, “Weekday on-peak”, “Weekend off-peak” and “Weekend on-peak” checkboxes and enter the appropriate times. Leave the others unchecked. Enter rates for the checked items.

The advanced tariffs shown and created here can be selected later in the Cost>Set Utility Tariff Data>Detailed option>Set Advanced Rate, to show the energy cost improvement (if any) of the proposed building against the baseline building.

Gas Oil

(14)

Generate baseline

Generate the baseline model

This creates the baseline model and assigns all the baseline data you have created. This option will only be enabled if you have completed and checked all the previous navigator steps. Note: if you have already generated the baseline model and then make any changes to it, you must re-generate the baseline model. The baseline model has no shading obstructions.

The glazing percentage for the baseline building is either 40%, or is the same percentage as the proposed building, whichever is the least. Usually the glazing for the baseline building is the same as the proposed building.

You can now view either the real or baseline buildings in the ModelIT view by selecting View>Model>Real, or >PRM baseline.

You can also view either the proposed or baseline buildings in the ASHRAE 90.1 PRM view by toggling the “proposed” or “baseline” option in the top toolbar.

(15)

Sizing runs

Room load calculations

Calculates room loads using the ASHRAE method, then calculates cooling airflow requirements for the proposed and four baseline buildings, and creates the load spreadsheets

Access loads data spreadsheets

Once room load calculations have been done, you can then look at spreadsheets containing the calculated data.

You have the option to amend the data in the spreadsheets for either the proposed or baseline buildings. In the 62.1 OA tab you have the option to override the 62.1 vent rates with your own values set in the VE>Room Data> System tab> System Outside Air Supply.

Assign room sizing data

Assigns the calculated flow rate data from the spreadsheets to the HVAC system. If required, you could edit the flowrates in the HVAC network directly. You will now be able to see calculated flowrate values in the HVAC network in green.

Note: Alternatively, you could copy and paste data from the above spreadsheets into a multiplex in

the proposed building HVAC network, or you could amend the spreadsheet and assign the room sizing data again.

(16)

System load calculations

This runs ASHRAE loads calcs again to calculate room coil loads and boiler/chiller sizes (taking into account oversizing factors) using previously calculated airflow rates, and assigns the sized data to the HVAC networks. You will now be able to see autosized values in the HVAC network in green. DX units are automatically selected based on any coils using DX cooling.

Update fan and coil sizing data

Note: It is only necessary to do this if you have unchecked the “update Apache HVAC system sizes?”

option in the loads calculation dialogue.

Sizing reports

Allows you to review sizes and flow rates if you need to, for the proposed and four baseline bulidngs below. Proposed Baseline 0 Baseline 90 Baseline 180 Baseline 270

(17)

Simulations

Proposed model simulation

If you need to, you can run a simulation just on the proposed building, as a test. Also, if you have simulated the proposed and all four baseline buildings and you subsequently change the proposed HVAC network, you only have to re-simulate the proposed building and not the baseline buildings.

0 deg. baseline model simulation

If you need to, you can run a simulation just on the 0 deg. baseline building, as a test.

Full PRM simulation

This runs the proposed and four baseline simulations.

Note: you must enable the ApacheHVAC link and you must select the proposed HVAC network .asp

file in the Apache simulation control dialogue. Note: if you change the proposed HVAC networ

(18)

Cost

Set utility tariff data

The tariff data that you set is very important as it affects the cost savings in the PRM report.

Simple option Set flat rate

This opens the Tariff Analysis overview dialogue in the Vista view. This shows the fuel costs of the proposed and baseline buildings after the simulations have been performed.

For this training example the “Simple/Flat rate” option is chosen as well as the ASHRAE 90.1 “Energy dataset” option, and we will enter flat rates in cost per kWh for your selected currency. The energy costs of the proposed and baseline buildings will be shown with the percentage cost improvement of the proposed building over the baseline building.

(19)

Detailed option

Set advanced rate

This opens the Tariff Analysis overview dialogue as above, but the “Advance/Variable rate” option is chosen, where advanced rates are available. These advanced rates are the ones from the Other Input Data>Define Tariffs Data workflow and include any that you created in that workflow.

Set currency Set site supply Set utility suppliers

Set up cost analysis assignments

Set proposed results dataset

Check tariff assignments

Review cost analysis

(20)

Results

Set parameters for ‘unmet load hour’ temperature tests.

In this training example we will use the default values. These values are tolerances (similar to a bandwidth either side of the set-point).

The PRM allows a maximum of 300 unmet load hours in both the proposed and baseline buildings, and allows a maximum of 50 hrs difference between the proposed and baseline building.

If you fail this test you could look at the room temperature and setpoints variables in Vista to help you track down where the problems are.

(21)

BPRM report

User details

Enter details for the user, software used and the building. Data for Tables 1.3 and 1.4

Here you enter features and plant descriptions for the proposed and baseline buildings. Correct documentation is important for the BPRM report.

Cost Savings Summary -Table 1.8.2(b) Energy Savings Summary -Table 1.8.2 Baseline Costs - Table 1.8.1(b)

Baseline Energy - Table 1.8.1 Full Report

This generates the full PRM report.

The Performance Rating Table (table 1.8.2) is one of the key tables in the PRM report and shows energy end uses for the proposed and baseline buildings. The values for the baseline building are the average of the values for the four baseline buildings. The table also shows the percentage savings for each end use and the total savings for the whole building.

The most important table is the Energy Cost & Consumption by Energy Type (table 1.8.2 (b)). It shows the energy cost and consumption by energy type for the proposed and baseline buildings, and also shows the energy generated by any renewables used. The table summarises the percentage energy and cost savings of the baseline building over the proposed building.

The tariff data that you previously set is very important as it affects the cost savings in the PRM report.

Detailed simulation reports

These reports display a full breakdown of results (these are needed for submission). Proposed

Baseline 0 Baseline 90

(22)

ASHRAE 62.1

These reports are normally not required (unless you are doing PRM analyses for ASHRAE 62.1 purposes only). Proposed Baseline 0 Baseline 90 Baseline 180 Baseline 270

Display selected reports

References

Related documents

Our findings turned up some surprising results. Part IV will discuss our findings in greater detail, but in very general terms, we found that the model minority stereotype is

That same year, the chief executive of the RAI declared that “we have a dining culture now, which we never had before.” The growing confidence among Irish culinarians is evident in

First, it shows that, even in the absence of inflationary bias, a credible central bank may find it optimal to implement an accommodating monetary policy in response to cost-push

4 (c) shows optical micrographs of friction stir weld AA6061 at heat affected zone from the micrograph it can be observed that grains are slightly elongated. 4

• Follow up with your employer each reporting period to ensure your hours are reported on a regular basis?. • Discuss your progress with

National Conference on Technical Vocational Education, Training and Skills Development: A Roadmap for Empowerment (Dec. 2008): Ministry of Human Resource Development, Department

4.1 The Select Committee is asked to consider the proposed development of the Customer Service Function, the recommended service delivery option and the investment required8. It

● Data sources: Email, Git repositories, IETF DataTracker , ListServ, ….. ● Data science tools: using Scientific