• No results found

08 Generator Protection.pdf

N/A
N/A
Protected

Academic year: 2021

Share "08 Generator Protection.pdf"

Copied!
119
0
0

Loading.... (view fulltext now)

Full text

(1)

Basics of Generator

Basics of Generator

Protection

(2)

2 2

Topic Outline

Topic Outline

I. I. GeGeneneraratotor ir in a n a viview ew of of an an PrPrototecectition on EnEngigineneerer II II.. TTypypicical al GeGeneneraratotor r PrPrototecectitionon

(3)

Topic Outline

Topic Outline

I. I. GeGeneneraratotor ir in a n a viview ew of of an an PrPrototecectition on EnEngigineneerer II II.. TTypypicical al GeGeneneraratotor r PrPrototecectitionon

(4)

3 3

Generator Configuration

(5)
(6)

5

Generator Configuration

(7)
(8)

7

Generator Connections

(9)
(10)

9

Generator Grounding

(11)
(12)

11

Generator Grounding

(13)

Generator Excitation Control and Generator

Capability

Excitation Control Basics

 A generator excitation system provides the energy for the

magnetic field that keeps the generator in synchronism with the power system.

Two types: those using ac generators as power source and those using transformers.

(14)

13

Excitation Control Basics

Generator Excitation Control and Generator

Capability

(15)

Excitation Control Basics

 Aside from maintaining synchronism of the generator, the generator also:

 Affects the amount of reactive power that the generator may absorb or produce.

 Increasing the excitation current results in increase reactive power output.

 Decreasing the excitation current results in decrease

reactive power output, extreme case loss of synchronism will occur.

Generator Excitation Control and Generator

Capability

(16)

15

Generator Watt/VAR Capability

Generator Excitation Control and Generator

Capability

(17)

P-Q Curve

Generator Excitation Control and Generator

Capability

(18)

17

Protection Requirements

To detect faults on the generator

To protect generator from the effects of abnormal

power system operating conditions

To isolate generator from system faults not cleared

remotely

(19)
(20)

19

Sample Generator Protection

(21)
(22)

21

Stator Phase Protection

This is achieved by:

 Differential Relaying (87)

 Turn Fault Protection (for split-phase generators)

 Overcurrent (thermal)

(23)

Differential Protection

 High-Speed protection that can detect three-phase, phase to phase and double-phase to ground faults.

 Single-line to ground faults are not normally detectable unless its neutral is solidly or low-impedance grounded.

 Will not detect a turn-to-turn fault within the same phase

 Both sides of the generator should be of the same ratio, rating, connected burden, and preferably have the same manufacturer.  It could be high-impedance type, low-impedance type and

(24)

23

Differential Protection

(25)
(26)

25

Overcurrent Protection

 For small generators this may be the only protection applied.  With solid earthing, it will provide some protection against earth

faults

 For a single generator, CTs must be connected to neutral end of stator winding.

~

Generator

50/51

(27)

Overcurrent Protection

Some helpful points in setting overcurrent relays: From C37.102-2005:

 Use IOC and TOC unit having an EI characteristic.

 IOC is set to 115% FLC and is used to torque-control TOC unit  TOC unit is set to 75%-100% FLC and a time settings operating

7sec @ 218% FLC or coordinate with downstream relay. From ABC’s of Overcurrent Protection:

 Set protection above FLC and above decrement curve in the lowest decade.

 Set protection below overload curve.

 Set protection to intersect with the decrement curve in the second lowest decade.

(28)

27

Overcurrent Protection

(29)
(30)

29

Stator Ground Protection

This is achieved by (depends on the grounding method):  Differential Relaying (87N)

 100% Stator Ground Fault Protection using voltage relays

(31)

Stator Ground Fault Protection

 Stator grounding determines the generator performance during fault conditions.

 If solidly grounded, it will deliver very high current to a SLG fault at its terminals with no neutral voltage shift, therefore equipment damage is severe.

 If ungrounded, it will deliver a negligible amount current during a SLG fault at its terminals with fill neutral voltage shift which could cause failure of generation equipment insulation.

(32)

31

Stator Ground Fault Protection

 Because of this, stator windings on major generators are grounded in a manner that will reduce fault current and overvoltages and yet provide a means of detecting the ground fault condition quickly enough to prevent burning of core iron.

(33)
(34)

33

Low-Impedance Stator Grounding

(35)

Low-Impedance Grounding

 The grounding resistor or reactor is selected to limit the generator contribution to an SLG fault to range of

currents between 200A and 150% of rated load current.

(36)

35

Low-Impedance Grounding

(37)

High-Impedance Grounding

 High-resistance generator neutral grounding uses a

distribution transformer with a primary rating greater than or equal to the line-to-neutral voltage rating of the

generator and a secondary rating of 120 or 240V.

 Power dissipated in the resistor is approximately equal to the reactive volt-amperes in the zero-sequence capacitive reactive of the generators, windings of any transformers connected to generator terminals.

(38)

37

High-Impedance Grounding

  An SLG fault is generally limited to 3 to 25 primary amperes.

 Others only uses resistor aside from transformers but the fault current is limited to 5A.

(39)

High-Impedance Grounding

(40)

39 39

Overvoltage/Overcurrent Schemes

Overvoltage/Overcurrent Schemes

 59G works on fundamental59G works on fundamental

frequency (3V0)

frequency (3V0)

 TTypically set at ypically set at 5V5V

 Measures maximum atMeasures maximum at

terminal fault and decreases

terminal fault and decreases

at faults moves toward the

at faults moves toward the

neutral

neutral

 Must be coordinated withMust be coordinated with

other protection that works

other protection that works

on ground faults

(41)

100% Stator Ground Fault Protection

100% Stator Ground Fault Protection

 59G can provide protection for only about 80% to 95% of59G can provide protection for only about 80% to 95% of

the stator windings.

the stator windings.

 This is due to generator construction imperfections andThis is due to generator construction imperfections and

subsequent small amounts of zero-sequence current that

subsequent small amounts of zero-sequence current that

will flow in the generator ground.

will flow in the generator ground.

 This small amount of zero-sequence current makes itThis small amount of zero-sequence current makes it

impossible for conventional ground fault detection relays to

impossible for conventional ground fault detection relays to

remain selective when set too

remain selective when set too lowlow..

(42)

41

100% Stator Ground Fault Protection

 Protection can be done using:

 Third-harmonic voltage-based techniques

 Neutral or residual subharmonic voltage injection

 Third-harmonic voltages components are present at the terminals of nearly every machine to varying degrees; they arise due to the nonsinusoidal nature of rotor flux and vary based in machine design and manufacturer.

 These voltages are used in detecting faults on the generator to provide protection.

(43)

100% Stator Ground Fault Protection

 3rd-harmonic voltage is dependent

on operating conditions of the generator.

 There is a point where the 3rd

-harmonic is zero.

 For a ground fault at the neutral, 3rd

harmonic decreases as fault approaches to neutral

 For a ground fault at the terminal, 3rd harmonic decreases as fault

approaches to the terminals.

 The 3rd harmonic levels should be

measured with the generator

connected and disconnected from the transformer before enabling 3rd

(44)

43

100% Stator Ground Fault Protection

(45)

100% Stator Ground Fault Protection

Third-Harmonic Undervoltage

 Since for a fault near the neutral, the level of third-harmonic voltage at the neutral decreases.

 Therefore undervoltage relay at the neutral could be used.

 It is tuned at 180Hertz to measure third harmonic.

 Set to overlap with 59G settings.

 Sometimes, it is supervised with OC relay, real or reactive power and breaker contact.

(46)

45

100% Stator Ground Fault Protection

(47)

100% Stator Ground Fault Protection

Third-Harmonic Overvoltage

 Since for a fault near the neutral, the level of third-harmonic voltage at the terminal increases.

 Therefore overvoltage relay (59T) at the terminal could be used.

 It is tuned at 180Hertz to measure third harmonic.

(48)

47

100% Stator Ground Fault Protection

(49)

100% Stator Ground Fault Protection

(50)

49

(51)

Field Fault Protection

 Field circuit is an isolated DC system.

 Insulation failure at a single point:

 No fault current, therefore no danger

 Increase chance of second fault occurring

 Insulation failure at a second point:

 Shorts out part of field winding

 Heating

 Flux distortion causing violent vibration of rotor

(52)

51

Field Fault Protection

(53)
(54)

53

(55)

System Backup Protection

Backup protection is divided into:

 Phase-fault protection

 (21) Distance relays

 (51V) Voltage controlled/restraint overcurrent relays

 Earth fault protection

 (51G) Ground OC Relays

(56)

55

System Backup Protection

(57)

System Backup Protection

51V

 Use of simple OC relay is not recommended.

 Voltage Restrained

 Operating characteristics is continuously varied. depending on measured volts.

 Voltage Controlled

 Relay switches between fault characteristic and load characteristic depending on measured volts.

(58)

57

System Backup Protection

Distance Phase Backup Protection

 Most common type of phase system backup protection.

 Two zones are applied with mho characteristic.

 If the generator is connected where there is no phase shift ( wye-wye transformer or directly connected), the relay will accurately measure the impedance

 If the generator is connected to delta-wye transformer, where there is phase shift, auxiliary PT is required to compensate the phase shift.

(59)

System Backup Protection

Distance Phase Backup Protection Setting Guidelines

 Set the impedance relay to the smallest of the three following criteria:

 120 percent of longest line (with infeed). If the unit is connected to a breaker-and-a-half bus, this percent is calculated using the length of the adjacent line.

 50 to 66.7 percent of load impedance (200 to 150 percent of the generator capability curve) at the machine-rated

power factor.

 80 to 90 percent of load impedance (125 to 111 percent of the generator capability curve) at the relay maximum

(60)

59

System Backup Protection

(61)

System Backup Protection

Backup Ground Protection

 Backup ground protection is set to pickup for ground faults at the end of all lines out of the station

 Set to coordinate with the slowest ground fault protection on the system.

(62)

61

Abnormal Frequency

Protection (81)

(63)

Abnormal Frequency Protection

 Stable system is when Power Input = Power of all loads + Losses in the system

 When there is a change between the this relationship, abnormal system frequency arises.

 Underfrequency condition occurs as a result of sudden reduction in input power

 Overfrequency condition occurs as a results sudden loss of load or key interties exporting power.

(64)

63

Abnormal Frequency Protection

Major considerations associated with operating a generating plant at an abnormal frequency:

 Protection of equipment from damage that could result from operation at an abnormal frequency.

 Prevention of inadvertent tripping of the generating unit for a recoverable abnormal frequency condition that does not exceed the plant equipment design limits.

(65)

Abnormal Frequency Protection

 Some turbine generators are designed to accommodate frequency voltage characteristics from IEC

60034-3:2007, Rotating Electrical Machines-Part 3.

 This standard requires generators to deliver continuously rated output at the rated power factor over the range of

±5% in voltage and ±2% in frequency. (61.2 Hz and

58.8Hz)

(66)

65

Abnormal Frequency Protection

(67)

Abnormal Frequency Protection

Conformance to IEC 60034:2007

 The standard recommends that operation outside the shaded are “be limited in extent, duration and frequency of occurrence.”

 The manufacturer could therefore impose time

restrictions for example below 95% or above 103% of rated frequency.

 Goal of frequency protection scheme is to return the frequency to the continuous IEC operating frequency

(68)

67

Abnormal Frequency Protection

(69)

Overexcitation and Overvoltage

Protection (24 / 59)

(70)

69

Overexcitation and Overvoltage

 Overexcitation occurs whenever the ratio of the voltage to frequency (V/Hz) applied to the terminal exceeds

design limits. IEEE standards have established the ff. limits:

 Generators, 1.05pu at the output terminals (generator base)

 Transformers, 1.05pu at the terminals at rated load or 1.1pu at no load

(71)

Overexcitation and Overvoltage

Overexcitation and Overvoltage

 When V/Hz ratios are exceeded, saturation of theWhen V/Hz ratios are exceeded, saturation of the

magnetic core of the generator or connected

magnetic core of the generator or connected

transformers can occur, and stray flux will be

transformers can occur, and stray flux will be induced intoinduced into

non laminated components.

non laminated components.

 Note that overexcitation protection on a generator or itNote that overexcitation protection on a generator or itss

connected transformer is different from field

connected transformer is different from field

overexcitation.

overexcitation.

 Excessive overvoltage of a generator will occur when theExcessive overvoltage of a generator will occur when the

level of dielectric field stress exceeds the insulation

(72)

71 71

Overexcitation and Overvoltage

Overexcitation and Overvoltage

 Not all overvoltage condition will be detected by V/HzNot all overvoltage condition will be detected by V/Hz

relay.

relay.

 It is general practice to provide overvoltage relaying toIt is general practice to provide overvoltage relaying to

alarm, or in some cases, trip t

alarm, or in some cases, trip the generators from thesehe generators from these

high dielectric stress levels.

(73)

Overexcitation and Overvoltage

(74)

73

Overexcitation and Overvoltage

(75)
(76)

75

Loss-of-Excitation

Protection (40)

(77)

Loss-of-Field Protection

Causes of loss-of-field:

 Accidental trip of field breaker

Field open circuit

Field short circuit

Voltage regulator system failure

Loss of supply to excitation system

For most generators, the unit will overspeed and

(78)

77

Loss-of-Field Protection

 On loss-of-field, apparent impedance of fully loaded machine travels from loaded value in the 1st quadrant to the 4th quadrant

close to –X axis at value just above the direct –axis transient reactance (about 2-7 seconds).

 Final impedance point depends on initial load, varies between Xd’/2 at full load to direct-axis synchronous reactance Xd at no load.

(79)
(80)

79

Loss-of-Field Protection

For small and less important machines, a single-zone

offset mho is used to detect this condition. For larger

machines, two-zone offset mho is used.

 Smaller Circle (#1)

 Diameter of 1.0 pu impedance on machine base

 “Small” “almost instantaneous” time delay

 Offset equal to –X’d/2

 Larger Circle (#2)

 Diamter of Xd

 Time delay of 30-60 cycles

(81)

Loss-of-Field Protection

(82)

81

Negative-Sequence

Current(46)

(83)

Negative-Sequence Protection

 In the real world, I A does not necessarily equal to IB and IC

 Unbalances are caused by:

 System asymmetries

 Unbalanced loads

 Unbalanced system faults

 Open phases

 Produce negative-sequence currents-induce a double frequency current

(84)

83

Negative-Sequence Protection

 I2 crosses the air gap, appears in rotor as double-frequency current

 Flows in rotor surface, non magnetic wedges

 Severe overheating, melting of wedges into air gap

 Standards permits 5-10% of I2

 Short-time limits expressed as 

2

 = 

, where K is a design constant

(85)
(86)

85

Negative-Sequence Protection

 Short-time

values apply for 120 seconds or less. Beyond 120 seconds, the continuous capability should be used.

(87)
(88)

87

Anti-motoring or Reverse

Power (32R)

(89)

Generator Motoring

Occurs when the energy supply to the prime mover is cut

off while the generator is still on the line. A primary

indication of motoring is the flow of real power into the

generator.

Estimated power required to motor the idling prime mover

is:

(90)

89

(91)

Out-of-Step Protection

 When a fault occurs on the power system, the generator can begin to accelerate due to differences in the mechanical power into the generator and the electrical power at the generator

terminals.

 If the fault is not cleared quickly, this acceleration will result in the generator rotor voltage advancing beyond 90 degrees with respect to the generator terminal voltage.

  At this point, power flow into the generator and the rotor angle will continue to advance until is aligned with the next pole. This

(92)

91

Out-of-Step Protection

(93)

Out-of-Step Protection

 Adverse Effects

 High peak currents and off-frequency operation (slipping)

 Winding stresses

 Pulsating Torques

 Mechanical resonances

 Standard generator protection will not detect loss-of-sychronism

 Standard transmission line protection will not detect loss-of-synchronism

(94)

out-of-93

Out-of-Step Protection

Determination of Electrical Center

 Electrical center is the point in the system where the impedance between the sources is equal.

(95)
(96)

95

Out-of-Step Protection

(97)
(98)

97

(99)

Inadvertent Energization

When an offline generator is energized (w/o field) on turning gear or coasting to a stop, the generator behaves as an induction motor and can be damaged within a few seconds

Causes:

 Operating Errors

 Open Breaker Flashovers

(100)

99

Inadvertent Energization

When an offline generator is energized (w/o field) on turning gear or coasting to a stop, the generator behaves as an induction motor and can be damaged within a few seconds

Causes:

 Operating Errors

 Open Breaker Flashovers

(101)

Inadvertent Energization

The following protection elements may detect or can be set to detect inadvertent energizing:

 Loss of Field Protection

 Reverse Power

 Negative-sequence overcurrent

 Breaker Failure

(102)

101

Inadvertent Energization

Inadvertent energization protection needs to be in service when the generator is out of service.

Dedicated protection:

 Directional Overcurrent

 Frequency Supervised Overcurrent

 Distance Relay

 Voltage Supervised Overcurrent

  Auxilliary Contact-Enabled Overcurrent

(103)
(104)

103

Loss-of-Potential

 Loss of the voltage transformer (VT) signal can occur because of a number of cases, most commonly fuse failure.

 It could be VT or wiring failure, an open circuit in the draw-out assembly, an open contact due to corrosion or blown fuse

 Such loss can cause protective relay misoperation or failure or generator voltage regulator runaway, which can lead to

generator overexcitation

 It is important to detect loss-of-potential condition, sometimes called, fuse loss (60FL)

(105)
(106)

105

Synchronism Check and

Auto Synchronizing (25)

(107)

Synchronism Check and Auto

Synchronizing

 Synchronism Check

 Checks the generator system frequency, voltage magnitude, and phase angle be in alignment

 Typical parameters call for no more than 6RPM error, 2% voltage magnitude difference, and no more than 10 deg phase angle error before closing the breaker

(108)

107

Synchronism Check and Auto

Synchronizing

 Auto Synchronizing (25A)

 Checks the generator system frequency, voltage magnitude, and phase angle be in alignment

 It involves sending voltage and speed raise and lower commands to the voltage regulator and prime governor.

 When the system is in synchronism, the autosync relay is sometimes designed to send a close command in

advance of the zero phase angle error to compensate for breaker close

(109)

Synchronism Check and Auto

Synchronizing

(110)

109

(111)

Tripping Modes

 Simultaneous Tripping

 Provides the fastest means of isolating the generator

 Used for all internal generator faults and severe abnormalities in the generator protection zone.

 Generator Tripping

 Does not shutdown the prime mover and is used where it may be possible to correct the abnormality quickly,

permitting a rapid reconnection of the machine to the system.

(112)

111

Tripping Modes

 Unit Separation

 Initiates only the opening of generator breakers

 Recommended when maintaining the unit auxiliary loads connected to the generator is desirable.

 Sequential Tripping

 Used for prime mover problems where high-speed tripping is not a requirement.

 1. turbine valves, 2. generator breakers 3. field breaker and load transfer of loads.

(113)

Tripping Modes

 These tripping scheme must be review and applied according to the present generator application

 Selection would depend on the ff:

 Type of prime mover

 Impact of the sudden loss of output power on the electrical system and prime mover

 Safety to personnel

 Operating experience

(114)

113

Tripping Modes

(115)
(116)

115

(117)
(118)

117

Sample Logic

(119)

References

Related documents

Home Software Hardware Benchmarks Services Store Support Forums About Us.. Home » CPU Benchmarks »

Many companies, with the approval of shareholders, retained discretion on salary and salary increases and flexibility on recruitment policies.. It will be interesting to see

BMI: Body mass index; ESRD: End-stage renal disease; HD: Hemodialysis; hypoAlb: Hypoalbuminemic; iPTH: Intact parathyroid hormone; LS: Least- square; NhypoAlb:

the design are consistent across the SoS Clm8 Security requirements are identified adequately across the SoS Clm10 Verification/validation of SoS security features is adequately

To determine whether increased OATP1A2 protein expression following BMP-9 treatment correlates with enhanced OATP-mediated statin transport, we measured cellular accumulation of

Norsk-engelsk økonomisk-juridisk ordbok (Hansen & Lind 2010) contains five use-related sections namely, a preface and a user guide, both in Norwegian, then

Now that we have fi nished se ng up Selenium Remote Control we can have a look at running our fi rst set of tests in a number of diff erent browsers1. Pop quiz – setting up

In a widely cited study, the probability of pros- tate cancer at biopsy among men with a PSA value of 4.0 to 10.0 ng per milliliter and normal findings on digital rectal