GENERATOR PROTECTION
ENGINEERING
Knowledge Management System
ELECTRICAL ENGG.
Key Words
:
Stator Protection, Relay Grouping, CT Parameters, Lead Resistance, Fault Stability, Differential Protection.
Presentation by : Pramod Kumar, DGM(PE-Elect),CC, 9868390543, [email protected]
Generator protection
By
PRAMOD KUMAR
Classification of Generator
protection
Stator Protection
Abnormal operating conditions System back up protections Rotor protection
GT protections UT protections
Over view of type of fault Vs protection
O/V relay Volt/Hz relay U/F relay
Insulation failure,Heating of core failure of blades
O/V,O/F,U.F
LFPR/Rev power Inter lock Motoring
Loss of field Induction gen operation
Absorb MVAR from
system/damage to rotor wdg Loss of field
2 stage rotor E/F protection Damage to shaft/bearing
Rotor fault
Differential prot
100% E/F prot/95% E/f Inter turn prot
Wdg burn out
Welding of core lamination Stator faults
ph to ph/ Ph to E
Inter turn
Over load/negative phase sequence relay
Unbalanced loading stress External
fault
Thermo couples/ Over current relays Over heating of stator
wdg/insulation failure Thermal over loading PROTECTION EFFECT FAULT/ABN ML CONDN
GCB/NON GCB SCHEMES
•
A)
Unit scheme:
(NON GCB SCHEME)
•
In this scheme
no
switchgear is provided
between the generator and
generator transformer, which
are treated as a unit; a unit
transformer is tapped off the
interconnection for supplying
of power to auxiliary plant.
GCB SCHEME
B)
Generator circuit breaker
scheme:
In this scheme a generator
circuit breaker is provided
between the generator and
generator transformer. unit
transformer is tapped off before
the GCB for supplying of
TRIP LOGIC OF GENERATOR PROTECTION
•
TWO INDEPENDENT CHANNELS WITH INDEPENDENT
CT/VT INPUTS/DC SUPPLY/TRIP RELAY
CLASS A TRIPS
• ALL ELECTRICAL TRIP
• TRIP TURBINE , FIELD, GENERATOR,GT,UT
CLASS-B TRIP
• MECHANICAL TRIPS
• AVOID OVER SPEEDING OF TURBINE DUE TO STEAM ENTRAPPED IN TURBINE. TURBINE TRIP SIGNAL IS GIVEN FIRST AND THE ACTIVE POWER, SENSED BY THE LOW FORWARD RELAY (32G) GIVES THE TRIP SIGNAL TO THE UNIT BREAKER & FIELD BREAKER AFTER A TIME DELAY.
• IN GCB SCHEME, ONLY GCB AND FIELD IS TRIPPED,KEEPING UAT CHARGED THROUGH GT
• IN NON GCB SCHEME, HV CB,FIELD,UT LCV CB ARE TRIPPED.
• Class C
Typical Generator
protection
scheme
RELAY GROUPING.
PROTECTION FUNCTION REMARK ON GROUPING OF PROTECTION
1. Generator Differential Protection, 3 pole (87 G) having operating time of 25 milli sec. or lower at five times the current rating.
2. Overall Differential Protection (87GT).
87 G AND 87 GT SHALL BE ON TWO DIFFERENT CHANNELS OF
PROTECTION. 3. Generator Transformer Restricted
Earth Fault protection (64RGT)
64RGT SHALL BE IN A DIFFERENT CHANNEL THAN 87 GT
4. Stator Earth Fault Protection covering 100% of winding (64G1), operating on low frequency signal injection principle suitable for continuous monitoring of stator insulation even during machine shut down.
5. Stator Standby Earth Fault Protection covering 95% of winding (trip) (64 G2) with adjustable time delay
64 G1 AND 64 G2 SHALL BE ON TWO DIFFERENT CHANNELS OF
PROTECTION.
6. Inter-turn Fault Protection (95G1), through comparison of zero sequence voltage on generator phase and neutral side.
7. DUPLICATED Loss of field protection (40G1/2 ).
40G1 AND 40 G2 SHALL BE ON TWO DIFFERENT CHANNELS OF PROTECTION.
8. Back up Impedance Protection, 3 pole (21G) along with suitable timer for Co-ordination with line protections
9. Backup Earth Fault Protection on Generator Transformer H V neutral (51NGT)
21 G AND 51 NGT BE IN DIFFERENT CHANNELS
RELAY GROUPING
1. Negative Sequence Current Protection, alarm and I 22t element for trip (46G) matching with the machine
characteristics.
2. Duplicated Low -Forward Power / reverse power Interlock for steam turbine generator (37 /32G1 & 37/32 G2), each having two stages, short time delayed interlocked with turbine trip and long time delayed independent of turbine trip.
37/32 G1 AND 37/32 G2 SHALL BE IN TWO
DIFFERENT CHANNELS OF PROTECTION
3. Two Stage Rotor Earth Fault Protection (alarm & tri p) operating on principle of continuously monitoring rotor insulation value even during machine shut down period (64F).
4. Definite Time Delayed Over -Voltage Protection (59G) for alarm and trip.
5. Generator Under Frequency Protection with alarm and stage tripping (81G)
with df/dt elements.
6. Over Fluxing Protection (99) for Generator / Generator Transformer having inverse time characteristics suitable for Generat or /Generator Transformer over fluxing capability.
Over Flux FUNCTION (99) SHALL BE IN A
DIFFERENT CHANNEL THAN O/V AND U/F FUNCTIONS
7. Accidental Back Energisation protection for accidental closure/flashover of EHV breaker or EHV disconnecting switch (50GDM)
8. Instantaneous and time delayed Over Current protection to be used on H V side of excitation transformer.
RELAY GROUPING
1. Generator Pole slipping protection
2. Generator under voltage relay for interlocks
3. Unit Transformer Differential Protection, 3 pole (87UT)
4. Unit Transformer LV back-up earth fault protection
( 51NUT).
5. Unit Transformer LV REF (64 UT LV) 6. Unit transformer back -up over current
protection (51UT).
87 UT & 51 NUT CAN BE IN ONE CHANNEL AND 64 UT LV & 51UT SHALL BE IN ANOTHER
CHANNEL.
DUPLICATED PROTECTIONS TO BE CONNECTED TO
TRIP RELAYS OF RESPECTIVE GROUPS .SINGLE
PROTECTION TO BE CONNECTED TO TRIP RELAYS OF
BOTH THE GROUPS.
GENERATOR PROTECTIONS IN DETAIL
DIFFERENTIAL PROTECTION
COVERS PHASE FAULTS
(E/F NOT COVERED DUE TOHIGH IMPEDANCE EARTHING RESULTING IN LOW E/F CURRENT.)
EFFECTS:
• HIGH CURRENTS
• POTENTIAL DAMAGE TO MACHINES
• EXPENSIVE OUTAGE/REPAIR DUE TO DAMAGE.
FEATURES:
• UNIT TYPE PROTECTION
• INSTANTANEOUS IN OPERATION.
• COVERS THE STATOR WDG FOR PHASE TO PHASE FAULTS. • DUPLICATED DIFFERENTIAL PROT GIVEN USED FOR GCB
SCHEME
• TWO TYPES: HIGH IMPEDANCE TYPE/BIASED TYPE. • STABLE FOR THROUGH FAULTS.
HIGH IMP TYPE RELAY contd
• CT PARAMETERS
Vk = 2 If (Rct+2Rl)
Vk – Min. Knee point voltage of the CT
If - Maximum fault current in the system
(converted to sec side)
Rct- Secondary resistance of the CT
Rl – lead resistance of the sec connection
(typ 8.73 ohms per km for 2.5 sq mm cu cable)
HIGH IMPEDANCE TYPE DIFF RELAY
• USE TWO SETS OF IDENTICAL DEDICATED CTs
• PS CLASS CTs WITH STRINGENT PARAMETERS TO BE USED
• TWO CTs PARALLED OUT SIDE THE RELAY AND SINGLE INPUT TO THE RELAY • VERY SENSITIVE
• THROUGH FAULT STABILITY ACHIEVED BY USING STABILISING RESISTORS IN THE RELAY CIRCUILT.
BIASED TYPE DIFF RELAY
• CTS CAN BE SHARED WITH OTHER PROTECTIONS • PS CLASS CTs REQUIRED.
• LESS STRINGENT CT PARAMETERS.
• INDIVIDUAL CT INPUTS GIVEN TO THE INDIVIDUAL BIAS COILS. • THROUGH FAULT STABILITY ACHIVED THROUGH BIASING.
• CT MISMATCH (TYP OF THE PRDER OF 1:5 ) CAN BE ACCOMODATED. • MORE SUITABLE FOR NUMERICAL INTEGRATED PROTECTION SYSTEMS
AS THE CTs CAN BE SHARED FOR MANY FUNCTIONS.
Biased Differential protection
Typ bias setting: 10% of rated current.
Modern numerical relays have flexible settings for
Id, b (point of slope change) and the slopes.
• STATOR EARTH FAULT PROTECTION
• E/F CURRENT IS LIMITTED TO 10A
• THIS MINIMIZES THE DAMAGE
• FIRST FAULT LESS CRITICAL
• NEEDS CLEARANCE AS
IT MAY DEVELOP INTO A PH TO PH FAULT
SECOND FAULT WILL RESULT IN VERY
HIGH CURRENT
• TWO TYPES:
• 100 % E/F
• 95 % E/F
• 95 % SEF
• RESULTS IN VOLTAGE SHIFT OF GEN NEUTRAL
W.R.T GROUND
• DETECTED BY VOLTAGE RELAY CONNECTED
ACROSS GROUNDING RESISTOR OR FROM
THE GENERATOR TERMINAL THROUGH OPEN
DELTA VT
• PROTECT APPROX 95% OF STATOR WDG
• TYP SETTING:
– For IDMT type relays
– Minimum tap
– TIME DELAY OF MORE THAN 1 SEC
(GEN IDMT RELAY WITH PMS 5.4 AND TMS 1 USED) – For Def time delay type: 5%of 110 V ie, 5.5 V at 1 sec
100 % Stator E/F Protection
THIRD HARMONIC PRINCIPLE
– A RELAY WHICH RESPONDS TO THE REDUCTION OF
THE 3
RDHARMONIC COMPONENT
– A STATOR PHASE-TO-GROUND FAULT OCCURS AT OR
NEAR THE GENERATOR NEUTRAL, THERE WILL BE AN
INCREASE IN THIRD HARMONIC VOLTAGE AT THE
GENERATOR TERMINALS, WHICH WILL CAUSE RELAY
OPERATION.
– DISADVANTAGES
DUE TO DESIGN VARIATIONS, CERTAIN GENERATING
UNITS MAY NOT PRODUCE SUFFICIENT THIRD
HARMONIC VOLTAGES
THIS METHOD DOES NOT PROTECT THE M/C DURING
STAND STILL CONDITIONS.
100% SEF BASED ON THIRD HARMONICS
MEASUREMENTS
100% STATOR EARTH FAULT PROT
100 % stator E/F protection
•
SETTINGS TYP FOR 500 MW UNIT
• Trip : 10 Ohm / 1 sec
• Alarm : 20-30 ohm /10 sec
• SETTINGS ARE TO BE FINALISED
DURING COMMISSIONING TEST IN
LINE WITH INSTRUCTIONS OF RELAY
CATALOGUE.
ROTOR EARTH FAULT PROTECTION
•
FIRST ROTOR E/F DOES NOT CAUSE IMMEDIATE
DAMAGE
•
SECOND E/F RESULTS IN A WDG SC OF ROTOR
•
CAUSE MAGNETIC UNBALANCE/MECH FORCES
/DAMAGE
•
METHODS OF DETECTION
– POTENTIOMETER METHOD
• A CENTRE TAPED RESISTOR IS CONNECTED ACROSS THE MAIN FIELD WINDING
• THE CENTRE TAP IS CONNECTED TO EARTH THROUGH A VOLTAGE RELAY
• AN EARTH FAULT ON THE FIELD WINDING WILL PRODUCE VOLTAGE IN THE RELAY, MAXIMUM VOLTAGE OCCURRING FOR END FAULTS
• A BLIND SPOT EXISTS AT THE TAPPING POINT, TO AVOID THIS , THE TAPPING POINT IS VARIED WITH A PUSH BUTTON OR SWITCH , AND IS TESTED PERIODICALLY TO DETECT BLIND ZONE
§LOW FREQUENCY INJECTION METHOD
MODERN ROTOR EARTH FAULT PROT ECTION
RELAY OPERATES ON THE PRINCIPLE OF LOW
FREQUENCY INJECTION INTO THE FIELD
WINDING VIA CAPACITORS.
CORRESPONDING CURRENT OR RESISTANCE
DURING E/F IS SENSED
TYP SETTING (500 MW)
ALARM 40 K OHM TIME = 10 SEC
TRIP 5 K OHM TIME = 1 SEC
ACTUAL VALUES OF SETTING SHALL BE DECIDED AT
SITE DURING COMMISSIONING TO ACCERTAIN THE
HEALTHY VALUE OF THE PARTICULAR M/C.
SEF/REF USING INJECTION PRINCIPLE
TYPICAL CONNECTION
TYPICAL CONNECTION DIAGRAM OF SEF/RF
USING INJECTION PRINCIPLE
NGT
FIELD
relay accessoryI
NTER TURN PROTECTION
•
CURRENT BASED SYSTEM
• FOR GENERATORS WITH SPLIT NEUTRALS WITH ALL SIX TERMINALS BROUGHT OUT ON NEUTRAL SIDE
• DELAYED LOW-SET O/C RELAY WHICH SENSES THE CURRENT IN THE CONNECTION BETWEEN THE NEUTRALS OF THE STATOR WINDINGS
•
VOLTAGE BASED SYSTEM
RELAY COMPARES THE NEUTRAL NGT SEC VOLTAGE AND GEN TERMINAL OPEN DELTA VOLTAGE
BALANCE DURING E/F OR NORMAL CONDITION
DURING INTER TURN FAULT OPEN DELTA VOLTAGE WILL BE DEVELOPED AND NGT SEC VOLTAGE WILL BE ZERO,RESULTING IN A DIFFERENTIAL VOLTAGE WHICH MAKES THE RELAY
OPERATE
IDMT RELAYS WITH 5.4 PMS AND 1 TMS ARE ADOPTED.
DEF TIME TYPE RELAYS: MINIMUM SETTING WITH I Sec
O/V PROTECTION
.
TYP SETTINGS OF A 3 STAGE O/V RELAY IS AS FOLLOWS
ALARM 110 % 2 SEC
TRIP 120 % 1 SEC
140 % INSTANTANEOUS
U/F O/F PROTECTION
TYPICAL SETTING:
U/F
O/F
ALARM - 47.8HZ 1 SEC 51 Hz 1 SEC
TRIP - 47.4 HZ 2 SEC
51.5Hz 2.5 SEC
SETTING NEED TO BE CO-ORDINATED WITH THE
RESPECTIVE GRID AGENCY AND THE ISLANDING
SCHEME SETTINGS AND THE M/C CAPABILITY.
Negative sequence protection
• NEGATIVE SEQUENCE PROTECTION FOR GENERATOR PROTECTS THE GENERATOR FROM EXCESSIVE HEATING IN THE ROTOR RESULTING FROM UNBALANCED STATOR CURRENTS
• CAUSED DUE TO
– ONE POLE OPEN IN LINE
– ONE POLE OPEN OF A CIRCUIT BREAKER – CLOSE IN UNCLEARED UNBALANCED FAULTS
• THE NEGETIVE SEQUENCE PROTECTION RELAYS SHALL BE SET TO THE NPS CAPABILITY OF THE MACHINE WHICH IS
• K = I22X T
• TYP FOR 500 MW
PERMISSIVE NEG SEQ CURRENT = 5 – 8 % OF STATOR CURRENT PERMISSIVE I2
2X T = 5 – 10
SETTINGS ADOPTED FOR NTPC I2 = = 7.5 %
Loss of field protection
•
ACTS AS AN INDUCTION GENERATOR
•
INDUCED EDDY CURRENTS IN THE FIELD WINDING,
ROTOR BODY, WEDGES AND RETAINING RINGS
•
MW FLOW IN TO THE SYSTEM/ MVAR FLOWS IN TO THE
MACHINE.
•
THE APPARENT IMP TRAVELS TO THE FORTH
QUADRANT OF X-Y PLANE
•
METHOD OF DETECTION:
MINIMUM IMPEDANCE WITH U/V
SOME RELAYS ARE SET IN THE ADMITTANCE PLANE
MATCHING WITH THE CAPABILITY CURVE OF THE
MACHINE
TRIP CHARACTERISTICS OF
LOSS OF FIELD PROTECTION
LOSS OF EXCITATION CHARACTERISTICS FOR VARIOUS TYPE OF MACHINES. BIG M/C WITH GOOD AVR SMALL MACHINES
POWER CHART
OUT OF STEP PROTECTION
• MACHINE RUNS OUT OF SYNCHRONISM WITH THE NETWORK • CYCLIC VARIATION OF ROTOR ANGLE
• CURRENT INCREASES HEAVILY
• FREQUENCY DEPEND ON THE RATE OF SLIP • RESULT IN THE WINDING STRESS
• IT MAY ALSO DAMAGE THE AUXILIARIES OF THE AFFECTED UNIT
• DETECTED BY SENSING THE VARIATIONS IN IMP
• DISTINGUISH BETWEEN THE RECOVERABLE SWING AND THE IRRECOVERABLE SWING
– BLINDERS + A SUPERVISORY MHO ELEMENT,TRIP WHEN IMP IS INSIDE THE MHO AND CROSE THE BLINDERS WITH THE SPECIFIED TIME.
– MINIMUM IMPEDANCE(MULTIPLE ZONE) + COUNTING NO OF SWINGS
TYPICAL POLE SLIPPING RELAY
CHARACTERISTICS
TYP SETTING:
MHO RELAY SETTING
:
FORWARD: ZT+Z SYS, REVERSE : GEN XD’ OVER CURRENT SETTINGTYP 115%
DISTANCE BETWEEN THE BLINDERS = HALF OF VECTOR SUM OF ZG,ZT,ZSYS (APPROXIMATELY) TIME TYP 50-55 MSEC
ACCIDENTAL BACK ENERGISATION
• CAUSE:
• FLASH OVER OF THE GENERATOR BREAKER
• INCORRECT CLOSING OF THE GENERATOR BREAKER • EFFECTS
• CAUSE OPERATION AS AN INDUCTION MOTOR • DAMAGEMACHINE AND TURBINE
• THE RAPID HEATING IRON PATHS NEAR THE ROTOR SURFACE DUE TO STATOR INDUCED CURRENT.
• DETECTED BY
• OVER CURRENT + CB AUXILIARY CONTACTS
CHECKS FOR THE CURRENT WHEN THE GEN BREAKER CONTACTS ARE OPEN SET BELOW THE RATED CURRENT(90%)
• O/C AND U/V MEASUREMENTS O/C 1.2 TIMES
ACCIDENTAL BACK ENERGISATION
USING CB AUX CONTACTS & O/C
• Backup impedance protection
• FOR UNCLEARED SYSTEM FAULT
•
THE BACKUP PROTECTION IS TIME DELAYED
TO COORDINATE WITH THE ZONE 3 SETTING
OF LINES
• DETECTED BY
– OVER CURRENT
– DISTANCE
– DISTANCE PREFFERED AS THE LINE IS PROVIDED
WITH DISTANCE RELAYS
• SETTING SHOULD BE MADE TO COVER THE GT
IMP AND THE LONGEST LINE IMP
• SETTING SHOULD TAKE CARE OF THE INFEED
FROM OTHER GENERATORS CONNECTED TO
THE SAME BUS ALSO
REVERSE /LOW FORWARD
POWER INTERLOCK
LOW FORWARD AND REVERSE POWER
INTER LOCK
• To allow entrapped steam in the turbine to be
utilized to avoid damage of the turbine blade.
• To protect the machine from motoring action
• Trip under class B after a
short time
delay in
case the turbine is already tripped ( typ set at 2
sec)
• Trip under class A, after a long time delay if
turbine is not tripped (typically set at 10 sec)
• Power setting typ 0.5 % of rated power
GEN TRFR PROTECTION
• DIFFERENTIAL
BIASED DIFFERENTIAL
– 10 % BIAS SETTING (TO COVER TAP RANGE AND CT MISMATCH IF ANY)
– TIME: INSTANTANEOUS
BACK UP EARTH FAULT
DEF TIME OR IDMT RELAY 20 % WITH 2 SEC TIME DELAY
UT PROTECTION
• DIFFERENTIAL
– BIASED DIFF USED
– BIASED SETTING 10%
BACK UP OVER CURRENT
– 2-3 TIMES THE FULL LOAD CURRENT
– DELAY 0.9 SEC
– TAKE CARE OF ANY LARGE MOTOR STARTING CASE
RESTRICTED E/F
– HIGH IMP DIFF
COMMONLY USED GEN/GEN TRFR RELAYS
Low frequency injection type preferred over 3 rd harmonic principle 7UE22 7UM SERIES GIX REG 216 PVMM MICOM P343 PG871 100% E/FOpen delta of gen sec VT 7UM SERIES VDG 95% E/F Minimum impedance 7UM 516 RAKZB REG YCG15 MICOM SERIES BACK UP IMP Impedance / admittance 7UM SERIES RAGPC(DI R O/C+U/V) YCGF LOSS OF FIELD
Directional power relays 7 UM SERIES PPX RXPE POWER RELAYS 7 UT RADSB RET 316 MBCH MICOM P 633 BIASED DIFF In case of duplicated diff, one low imp & one high imp preferred For trfr biased relay preferred 7UM SERIES RADHA REG 216 CAG 34 MICOM P343 HIGH IMP DIFF REMARK SIEMENS ABB ALSTOM PROTEC TION
7UR 22 7 UM SERIES REG SERIES VDG MICOM SERIES ROTOR E/F HIGH IMP PREFFERED 7UM SERIES RADHD CAG/FAG REF MEASUREMENT OF
I
2 7UM SERIES RARIB CTN NEG PH SEQcomp of open delta 0n gen term+ngt sec voltage 7UM SERIES REG VDG MICOM INTER TURN O/C +CB AUX CONTACT CURRENT ELEMENT+U/V 7UM SERIES RAGUA CTIG ACC. BACK ENERG IMPEDANCE IMP+ DIR O/C
IMP+NO OF POWER SWINGS 7UM 516 RXZF+RXPE ZTO+YTG M15 POLE SLIPPING IDMT 7RW RATUB RALK GTTM OVER FLUXING Remarks SIEMENS ABB ALSTOM PROTEC TION
1 &2 1 &2 1 & 2 1 /2 1/2 1 / 2 1&2 1 2 Alarm 1&2 1 &2 1 2 1 2 1&2 Channel >100 MW Recommenda tion 95G Inter turn 64G1 64G2 Stator Earth Fault
64F Rotor E/F 50GDM Accidental energisation 21G System back up 59/99 81G1/81G1 O/V,O/F U/F 32 G1/2 / 37 G1/G2 Motoring 98G Out of step 40G1 40G2 Loss of excitation 51G Over load 46G unbalance 87 G1 87G2 87 GT Short circuit Protection Type of fault
Generator transformer/unit transformer protections
1 2 1/2 1/2 1 1 1/2 1 2 2channel
Recomm
endation
87 UT 51UT Short circuit(UT) 51 NGT 64GT(3 Ph GT) 64T Earth Fault(GT) 51 NUT 64 UT Earth Fault UT 87T 87 HV 51 GT Short ckt (GT)Device no
Fault
Numerical integrated generator protection systems
•
Many functions in the same relay
•
Takes multiple CT/VT inputs.
•
Minimum of 2 nos to be used.
•
All the prot functions are to be divided in to 2 groups .
•
Built in DR(fast scan)/SOE functions
•
Self supervision
•
Communicable
•
Has programmable logic gates which simplifies the auxiliary circuits.
COMMON RELAYS ARE
REG series OF ABB
7UM SERIES OF SIEMENS
MICOM SERIES OF AREVA.
GENERATOR DISTURBANCE RECORDER
• RECORD THE GRAPHIC FORM OF INST.VALUES OF POWER SYSTEM QUANTITIES
• FAST SCAN (1-5 KHz) AND SLOW SCAN (5/10 Hz) FEATURES • SUFFICIENT ANALOGUE/DIGITAL INPUTS.
• TRIGGERING FROM DIGITAL INPUTS AND THRESHOLD/RATE OF CHANGE OF ANALOGUE VALUES.
• ADEQUATE MEMMORY
• GOOD FREQUENCY RESPONSE
• INDIVIDUAL ACQUISITION UNITS AND COMMOM EVALUATION UNIT FOR A STATION
Islanding scheme
n DEPENDS ON TYPE OF GENERATING SYSTEM
n GRID CONNECTED GENERATING STATIONS
• GENERATOR IS CONNECTED TO THE GRID THROUGH EHV TRANSMISSION LINES.
• CAPTIVE GENERATING STATION
• DEDICATED GENERATOR(S) SUPPLIES POWER TO A PARTICULAR UTILITY/ESTABLISHMENT.