• No results found

A Three-Phase Line Interactive UPS system with active power line conditioning using SRF method

N/A
N/A
Protected

Academic year: 2021

Share "A Three-Phase Line Interactive UPS system with active power line conditioning using SRF method"

Copied!
10
0
0

Loading.... (view fulltext now)

Full text

(1)

Sérgio Augusto Oliveira da Silva* Rodrigo Augusto Modesto** Lúcio dos Reis Barbosa***

* Universidade Norte do Paraná (UNOPAR). Universidade Tecnológica Federal do Paraná (UTFPR).

** Universidade Estadual de Londrina (UEL). *** Universidade Norte do Paraná (UNOPAR).

Universidade Estadual de Londrina (UEL).

A Three-Phase Line Interactive UPS system with active power line conditioning using SRF method

Um sistema UPS Line-Interactive trifásico com condicionamento ativo de potência usando o

método SRF

Abstract

This paper presents an application of an active compensation method, applied to a three-phase line-interactive uninterruptible power supply (UPS) system with series and parallel active power line conditioning capabilities. The control strategy, employed to achieve the reference currents for the UPS system, is based on the synchronous reference frame (SRF) method. The reference currents, obtained from the SRF algorithm, are used to compensate the reactive power and to eliminate harmonic currents generated from non-linear loads. The reference currents of the SRF-based controller does not have the task of compensating fundamental zero sequence component of the neutral current, due to unbalanced loads or unbalance source voltages conditions. Thus, the efficiency of the three-phase UPS system is increased when it is feeding unbalanced single-phase non-linear loads. Besides, a mode to control the active power flow through the series and parallel active power filters of the UPS system is presented.

Keywords: UPS. Harmonics. Active power flow. Active power filter. Resumo

Este trabalho apresenta a aplicação de um método de compensação ativa, aplicado a um sistema de energia ininterrupta (SEI) line-interactive trifásico, com capacidade de condicionamento ativo de potência série e paralelo. A estratégia de controle, empregada para a obtenção das referências de corrente do SEI, é baseada no sistema de referência síncrona (SRF). As referências de corrente obtidas a partir do algoritmo SRF, são usadas para compensar a potência reativa e eliminar harmônicos gerados por cargas não lineares. As correntes de referência do controlador SRF, não possuem a tarefa de compensar a componente fundamental de seqüência zero da corrente de neutro, presentes no sistema devido a cargas ou tensão da rede elétrica desequilibradas. Assim, a eficiência do SEI trifásico é aumentada quando a mesma alimenta cargas não lineares monofásicas desequilibradas. Além disso, é apresentado um modo para controlar o fluxo de potência ativa através dos filtros ativos de potência série e paralelo do SEI.

Palavras-chave: SEI. Harmônicos. Fluxo ativo de potência. Filtro ativo de potência.

1 Introduction

The use of non-linear loads by residential, commercial and industrial customers has contributed to reduce the power factor and to increase the THD (Total Harmonic Distortion) of the input line voltages. The problem increases when single-phase non-linear loads are connected in three-phase, four-wire systems. In this case, even perfectly balanced single-phase loads, a very large

third component and its multiples can flow through the

neutral wire. Besides, the neutral current amplitude can

exceed the amplitude of the line currents (GRUZS, 1990). The excessive neutral current can cause damage both in

the neutral conductor and in the transformer to which the

non-linear loads are connected (QUINN; MOHAN, 1992).

Now, if non-linear loads are unbalanced, the neutral current will contain both the fundamental and harmonic components.

Active Power Filters (APF) have been used to compensate the currents drawn from utility Quinn and

Mohan (1992); Quinn; Mohan and Mehta (1993); Thomas,

et al. (1996). Uninterruptible Power Supply (UPS) systems

have enabled the improvement of power source quality, providing clean and uninterruptible power to critical loads such as industrial process controls, computers, medical equipment, data communication systems, and protection against power supply disturbances or interruptions (SILVA et al., 2002; 2003, 2004).

In Silva et al., (2002), the UPS system has been used for three-phase, three-wire system and in Silva et al. (2004), the UPS system has been used for three-phase, four-wire system. In both Silva et al. (2002; 2004), the source currents have been controlled to be sinusoidal and balanced providing negative and zero sequence components compensation.

In this paper a three-phase line-interactive UPS system is used to feed single-phase non-linear loads. The implemented algorithm generates the reference currents to compensate the reactive power and to eliminate harmonic currents generated from non-linear loads, without the function of compensating fundamental

(2)

zero sequence component of the neutral current, due to unbalanced loads or unbalance source voltages

conditions. Thus, the efficiency of the three-phase UPS

system is increased when it is feeding unbalanced single-phase non-linear loads. Besides, a mode to control the

active power flow through the UPS system is presented.

2 Operation of the Line-Interactive UPS Topology

The topology of the line-interactive UPS system is shown in Figure 1. Two PWM converters, coupled with a common dc-bus, are used to perform the series active

filter and parallel active filter functions. The series active filter is connected in series with the line and the load

through three single-phase linking transformers.A battery bank is placed in the dc-bus and a static switch ‘sw’ is incorporated to the circuit to provide a fast disconnection between the UPS system and the power supply when an occasional interruption of the incoming power occurs.

The series active power filter acts as a sinusoidal

current source. It has high impedance, which is enough to isolate the line from the load with respect to harmonic currents. An SRF-based controller is used to control the

series active power filter making the line currents (isa, isb, and isc) sinusoidal with low THD.

The parallel active power filter acts as a sinusoidal

voltage source with constant rms output voltages (vfa, vfb, and vfc) and low THD. It has low impedance, which is enough to absorb the harmonic currents of the load.

The output UPS voltages and the line currents are individually controlled to be in phase with respect to the line voltages (vsa, vsb, and vsc) respectively. Both the pa-rallel

and the series filter use three independent controllers

acting on half-bridge inverters. In this line-interactive UPS system, an effective power factor correction is carried out.

Figure 1.

Line-interactive UPS system topology.

A. SRF-Based Controller for Current Compensation

(Standby Mode)

transformation (1). Then, these quantities are transformed from a two-phase stationary reference frame (dq)s into a

(3)

Figure 2. Block Diagram of the Current SRF Based Controller (Conventional strategy).

Now, only the dc component current of the synchro-nous rotating reference frame must be transformed into the stationary reference frame (dq)s to obtain the

fundamental references currents

Thus, the reactive and harmonic components of the load currents were eliminated. As the currents

are balanced, the compensation of the negative and zero sequence components has been performed.

The inverse transformation matrix from two-phase

synchronous reference frame to two-phase stationary

reference frame is given by (3). The matrix that provides

the linear transformation from two-phase system to three-phase stationary reference frame system is given by (4).

B. SRF-Based Controller Applied to Unbalanced

Loads

The previous presented synchronous reference frame method generates balanced reference currents because it is based on the consideration of balanced three-phase loads. Thus, additional power rate must be handled through the converters to perform the current

compensation, decreasing the efficiency of the series

and parallel converters.

Applying a single-phase strategy, in which each phase is treated separately, is possible to get three-phase load currents by the acquisition of only one of them, as shown in Figure 3. By software implementation, the acquired load current is phase delayed by 120 and 240 degrees, producing the other two load currents.

As can be waited, the phase delays introduced by the algorithm produce an increasing in the transient time and the dynamic response is slower than the response obtained from the conventional method. However, the dynamic response can be improved by using the stra-tegy presented in (OLIVEIRA et al., 2001), in which the

conventional filtering of the synchronous reference frame

method can be suppressed.

Based on SRF method applied to a single-phase strategy shown in Figure 3, the new reference currents can be achieved by (5). Now the currents

are unbalanced, thus the compensation of the negative and zero sequence components has not been performed.

(4)

Figure 3. SRF-Based Controller applied to a single-phase strategy.

3 Active Power Flow of the Three-Phase UPS System

Depending on the difference between the utility voltage

and the output voltage, the active power flow of the UPS

system can change its direction. When the rms utility voltage Vs is greater than the rms output voltage Vf , the

active power flows from the power supply to the dc-bus

via series converter and from the dc-bus to the load via parallel converter, as shown in Figure 4 (a). When Vs is less than Vf , the active power flows from the power supply

to the dc-bus via the output of the parallel converter and from the dc-bus to the line via series converter, as shown in Figure 4 (b). Therefore, controlling the amplitudes of the series reference currents

the dc-bus furnishes and absorbs power to make the “balance” of the active power. If the line voltage Vs is equal to the output voltage Vf and the UPS is feeding

a linear resistive load, there isn’t any active power flow

through both the series and the parallel converters, as shown in Figure 4 (c).

The direction of the power flow of the UPS system

must be taking into account when the reference currents are been calculated. Therefore, the amplitude of them will be ever changing.

Although power compensation can be performed us-ing a dc bus controller, an alternative algorithm can be implemented applying a constant “k” in the SRF algorithm

(5)

Figure 5. Line interactive UPS system feeding unbalanced non-linear loads. Fundamental unbalanced voltages of ±15% and

har-monic contents have been included in the input voltages as shown in Figure 6 (a). Figure 6 (b) shows the controlled

output voltages of the line interactive UPS system. They are balanced and have low harmonic contents.

(6)

The uncompensated non-linear load currents , , and

are shown in Figure

7 (a). The com-pensated line currents , , and that follow the reference currents , , and obtained from the current SRF-based controller of Figure 3, are shown in Figure 7 (b). The implemented algorithm generates the re-ference currents to compensate the reactive power and to eliminate the harmonic currents generated by non-linear loads. As can be noted the fundamental zero sequence components of the neutral current were not compensated.

In Figure 8 the transition modes from the standby mode to backup mode (40ms) and from backup to standby mode (65ms) are shown. The phase “a” output voltage ( ) is shown in Figure 8 (a) and the compensated input current ( ) is shown in Figure 8 (b). In Figure 8 (c), phase “a” parallel inverter current ( ) is shown.

It can be noted that the parallel active filter is providing

compensation harmonic of the load currents when the UPS is operating in the standby mode until 40ms. After 40ms the parallel converter assumes the full power to feed the load.

Seamless voltages transitions from the standby mode to backup mode (40ms) and vice-versa (65ms) are obtai-ned as can be observed in the Figure 8 (a).

Figure 9 (b) shows the compensation constant k

cal-culated from equation (8). This constant is used in the

current SRF controller of Figure 3 to control the amplitude of the reference currents so that the dc value of the input power and the dc value of the output power

become equals, as shown in Figure 9 (a). Therefore,

controlling the amplitudes of the currents ( ), ( ), and ( ), the dc-bus can furnishes and absorbs power to make the “balance” of the active power.

Additional simulations are realized considering three single-phase unbalanced resistive loads as can be shown by Figures. 10 (a) and 11 (a). In Figure 10 (b) the conven-tional strategy is used to calculate the balanced reference currents using the algorithm of Figure 2. As can be noted the compensation of the fundamental zero sequence component is realized by the active parallel converter,

shown by Figure 10 (c), decreasing its efficiency. Figure

11 shows the single-phase strategy using the algorithm of Figure 3. As can be seen the reference currents of Figure 11 (b) are unbalanced, but the compensation currents of Fig. 11 (c), are null in steady state. Thus, the fundamental zero sequence components of the load currents are not compensated by the parallel converter and its efficiency

is increased. Figure 12 shows the instantaneous active powers of the load (p), parallel converter with conventional strategy ( ) and parallel converter with single-phase strategy ( ), respectively.

(7)
(8)
(9)

5 Conclusions

An application of an SRF-based method, applied to a three-phase line-interactive uninterruptible power supply system with series and parallel active power line conditioning capabilities has been presented.

The reference currents, obtained from the SRF-based controller, can be used to compensate only the reactive power and to eliminate harmonic currents generated from non-linear loads.

Applying a single-phase strategy, in which each phase is treated separately, was possible to get three-phase load currents from the acquisition of only one single-phase load current.

Thereby, negative and zero sequence components at fundamental frequency of the three-phase system were despised. Thus, the power rate of the series and

paral-lel converters decreases and the efficiency of the UPS

system increases when it is feeding unbalanced single-phase non-linear loads. Besides, a mode to control the

active power flow through the UPS system was presented.

References

GRUZS, T. M. A Survey of neutral currents in three-phase

computer power systems. IEEE Transactions on Industry

Applications, v. 26, n. 4, p. 719-725, Jul./Aug. 1990.

OLIVEIRA, L. et al. Improving theddynamic response of active power filters based on the synchronous reference

frame method. In: PROCEEDINGS OF THE 6TH BRA

-ZILIAN POWER ELECTRONICS CONFERENCE, 2001

QUINN, C. A.; MOHAN, N. Active filtering of harmonic cu

-rrents in three-phase, four-wire systems with three-phase and single-phase non-linear loads. In: APPLIED POWER

ELECTRONICS CONFERENCE AND EXPOSITION,

1992, Boston. APEC'92. Conference Proceedings 1992.

Boston, 1992. p. 829-836.

QUINN, C. A.; MOHAN, N.; MEHTA, H. A four-wire, current-controlled converter provides harmonic neutralization in three-phase, four-wire systems. In: APPLIED POWER ELECTRONICS CONFERENCE AND EXPOSITION,

1993, San Diego. APEC'93. Conference Proceedings

1993. San Diego, CA, 1993. p. 841-6.

SILVA, S. A. O. et al. A three-phase line-interactive UPS system implementation with series-parallel active power-line conditioning capabilities. IEEE Transactions on

Indus-try Applications, v. 38, n. 6, p. 1581-1590, Nov./Dec. 2002.

______. et al. Performance analysis of three-phase line-interactive UPS system with active power-line condition-ing. In: ANNUAL CONFERENCE OF THE IEEE INDUS-TRIAL ELECTRONICS SOCIETY, 29., 2003. IECON'03. Roanoke, Virgínia: IEEE Industrial Electronics Society, 2003. v. 1, p. 353-60.

______. et al. A line-Interactive UPS system implemen-tation with series-parallel active power-line conditioning for three-phase, four-wire systems. Electrical Power and

Energy Systems, v. 26, n. 6, p. 399-411, 2004.

THOMAS, T. et al. Performance evaluation of three-phase

three and four wire active filters. In: CONFERENCE

RECORD OF THE IEEE INDUSTRY APPLICATION

SOCIETY, 31., 1996, San Diego. IAS'96, 1996 Annual

(10)

Sérgio Augusto Oliveira da Silva*

Doutor em Engenharia Elétrica pela Universidade Federal de Minas Gerais (UFMG). Docente do Curso de Engenharia da Computação da Universidade Norte do Paraná (UNOPAR) e do Curso de Engenharia Elétrica da Universidade Tecnológica Federal do Paraná (UTFPR).

e-mail: <[email protected]> Rodrigo Augusto Modesto

Tecnólogo em Automação Industrial pela Universidade Tecnológica Federal do Paraná (UTFPR). Mestrando em Engenharia Elétrica na Universidade Estadual de Londrina (UEL).

e-mail: <[email protected] > Lúcio dos Reis Barbosa

Doutor em Engenharia Elétrica pela Universidade Federal de Uberlândia (UFU). Docente do Curso de Engenharia da Computação e Engenharia Elétrica da Universidade Norte do Paraná (UNOPAR). Docente do Curso de Engenharia Elétrica da Universidade Estadual de Londrina (UEL).

Figure

Figure 1. Line-interactive UPS system topology.
Figure 2. Block Diagram of the Current SRF Based Controller (Conventional strategy).
Figure 3. SRF-Based Controller applied to a single-phase strategy.
Figure 5. Line interactive UPS system feeding unbalanced non-linear loads.
+2

References

Related documents

How do we actually run or execute this program? C++ is a compiled language, meaning that before we can run the program we must translate it to “machine language,” a form in which

The trade-off theory is a development of the MM proposition. In addition to MM, this theory considers the extra risk that debt implies. In comparison with the MM proposition,

Tripp Lite's SmartPro Compact Rackmount Uninterruptible Power Supply (UPS) offers line interactive voltage regulation, network grade surge suppression and long lasting battery

In Albania should critically be assessed the implementation of standards regarding the way the prison system is organized, how are distinguished the categories of prisoners

It is this feature that is exploited in imaging techniques; if a sample is placed in a non-uniform magnetic field then the resonance imaging techniques; if a sample is placed in

We might want to indicate several areas of progress which seem to be crucial, in particular the analysis ofthe'l'6tat filmique', distinct for Metz from the dream state, but

Catalog of the parental allelic proportions and gene expression level of all analyzed 91 candidate imprinted genes across gestation (first, second, and third trimester normal

Work with the community and regional sport groups, University of Victoria and Camosun College, Greater Victoria Library Board, School Districts 61 &amp; 63 and other