Contents
• Principle of cooling load
• Why cooling load & heat gains are different • Design conditions
• Understand CLTD/CLF method • An example
Cooling Load
• It is the thermal energy that must be removed from the space in order to maintain the
desired comfort conditions
• HVAC systems are used to maintain thermal conditions in comfort range
Purpose of Load Estimate
• Load profile over a day
• Peak load (basis for equipment sizing) • Operation Energy analysis
• Enclosure heat transfer characteristics
– Conduction – Convection – radiation
• Design conditions
– Outdoor & indoor
• Heat Gains
– Internal
– External or Solar
• Thermal capacity
Space Characteristics
• orientation
• Size and shape
• Construction material
• Windows, doors, openings • Surrounding conditions
Space Characteristics
• Occupants (activity, number, duration) • Appliances (power, usage)
• Air leakage (infiltration or exfiltration)
Indoor Design Conditions
Basic design parameters • Air temperature – Typically 22-26 C • Air velocity – 0.25 m/s • Relative humidity – 30-70 %
Indoor Design Conditions
• Indoor air quality
– Air contaminants – Air cleaning
• Acoustic requirements
Outdoor Design Conditions
• Weather data required for load calculation
– Temperature & humidity
– Wind speed, sky clearness , ground reflectance etc
• Design outdoor conditions data can be found in ASHRAE Fundamentals Handbook
Outdoor Design Conditions
• ASHRAE Fundamentals 2001
– Design severity based on 0.4%, 1%, & 2% level annually (8760h)
– For example at 1% level, the value is exceeded in 0.01x8760h = 87.6 h in a year
Outdoor Design For Cooling
Criteria: 0.4% DB and MWB Station Cooling DB/MWB Miri Malaysia 0.4% 1% 2% DB (˚C ) MWB ( ˚C ) DB MWB DB MWB 32.2 26.3 31.8 26.3 31.4 26.2Terminology
• Space
- a volume without partition or a groupof rooms
• Room
- an enclosed space• Zone
- a space having similar operatingHeat Gain
• Space Heat gain
– The instantaneous rate at which heat enters into , out of, or generated within a space. The
components are:
• Sensible gain • Latent gain
Heat gains Convective (%) Radiant (%) Solar radiation with internal shading 42 58 Fluorescent lights 50 50 People 67 33 External wall 40 60
Cooling Load
• Space Cooling load
– The rate at which heat must be removed from a space to maintain air temperature and humidity at the design values
• Cooling load differs from the heat gain due to
– delay effect of conversion of radiation energy to heat
Heat Gain = Cooling Load
Extraction Rate
• Space Heat extraction rate
– The actual heat removal rate by the cooling equipment from the space
– The heat extraction rate is equal to cooling load when the space conditions are constant which is rarely true.
The principal terms of heat Gains/Losses are indicated below.
(Source: ASHRAE Handbook Fundamentals 2005)
Coil Load
• Cooling coil load
– The rate at which energy is removed at the cooling coil
– Sum of:
• Space cooling load (sensible + latent)
• Supply system heat gain (fan + supply air duct) • Return system heat gain (return air duct)
• Load due to outdoor ventilation rates (or ventilation load)
External Loads
1. Heat gains from Walls and roofs
– sensible
2. Solar gains through fenestrations
– Sensible
3. Outdoor air
Internal Loads
1. People
– Sensible & latent
2. Lights
– sensible
3. Appliances
Cooling Load Components
• Space cooling load
– Sizing of supply air flow rate, ducts, terminals and diffusers
– It is a component of coil load
– Bypassed infiltration is a space cooling load
• Cooling coil load
– Sizing of cooling coil and refrigeration system – Ventilation load is a coil load
Refrigeration Load
• The capacity of the refrigeration system to produce the required coil load.
Profiles of Offshore Systems Cooling
Loads
Components % Load LQ (L) %Load LQ (U) %Load CCR %Load SG/MCC Solar Transmission 3 4 7 4 Occupants 3 3 3 0 Lights 5 5 8 4 Equipment 10 1 29 21Outdoor air bypassed 7 8 5 6
Outdoor air not bypassed
72 79 48 64
Heat Load Components
Outdoor air &
Electrical Equipment loads (77-85% )
People: 3% Lighting: 4-8%
Solar Transmission: 3-7% Infiltration : 5-8%
Calculation Methods
1. Rule of thumb method
– Least accurate
– eg 100 btu/ft2 for a space
2. Static analysis (Room temperature is constant)
– CLTD/CLF method
3. Dynamic analysis
CLTD/CLF Method
• Cooling load is made up of
– Radiation and conduction heat gain – Convection heat gain
• Convective gain is instantaneous
– No delay
– Heat gain equals cooling load
• Conductive and radiation heat gains are not instantaneous
– Thermal delay
– Heat gain is not equal to cooling load – Use CLTD & CLF factors
CLTD/CLF Method (ASHRAE 1989)
Cooling load due to solar & internal heat gains • Glazing (sensible only)
– Radiation & conduction
– Convection (instantaneous)
• Opaque surface ( wall, floor, roof) load (sensible only)
– Conduction
– Convection (instantaneous)
• Internal loads (sensible & latent)
– Radiation & conduction
Cooling Load Temperature Difference
CLTD
Compare
Q transmission = UA (T o – T i ) Q transmission = UA (CLTD)
• CLTD is theoretical temperature difference
defined for each wall/roof to give the same heat load for exposed surfaces to account for the
combined effects of radiation, conductive storage, etc
– It is affected by orientation, time , latitude, etc – Data published by ASHRAE
Cooling Load Factor (CLF)
• This factor applies to radiation heat gain
• If radiation is constant, cooling load = radiative gain
• If radiation heat is periodical, than Q t = Q daily max (CLF)
CLF accounts for the delay before radiative gains becomes a cooling load
Glazing
• Q = A (SC) (SHGF) (CLF)
A= glass area
SC= shading coefficient
SHGF= solar heat gain factor, tabulated by ASHRAE
CLF= cooling load factor, tabulated by ASHRAE
• Q = U x A x CLTD
U= surface U-factor A= surface area
CLTD= cooling load temperature difference transmitted absorbed reflected Solar ray glass
Opaque Surfaces
• Q 2 = UA (CLTD)
U= surface U-factor A= surface area
CLTD= cooling load temperature difference
• Tabulated or chart values for CLTD can be referred
• Offshore enclosure
– Light weight
– Metal frame with insulation
CLTD for Sunlit Wall Group G
Opaque Surface Calculations
• Use Table for wall CLTD • Use Table for roof CLTD
– Select wall/roof type
– Look up uncorrected CLTD – Correct CLTD
CLTD c=(CLTD+LM)+ (25.5-t r) + (t m-29.4)
• LM= latitude /month correction (Table ) • T r = indoor temperature (22C)
• T m= average temperature on the design day = (35+22)/2 = 28.5 C
Eg. If CLTD=40 C, LM=-1.7 (west face)
Types of Internal Load
• Internal loads are
– People – Lights
– Equipment or appliances
• Consist of convective and radiant components
– Light (mostly radiant)
– Electrical heat (radiant and convective) – People (most convective)
Internal Load- Lighting
Area Light Power
Density W/m2 Office 25 Corridor 10 Sleeping 10 CCR 25 MCC/SG 25 Kitchen 25 Recreation 20
•Heat gain (lighting)
= 1.2 x total wattage x CLF Or based on light power density ranging from 10-25 W/m2
(average density, say=20 W/m2)
•Where light is continuously on, CLF=1
Internal Loads- People
• Q people-s = No x sensible heat gain/p x CLF • Q people-L = No x latent heat gain/p
Internal Load – Equipment Heat
• Cooling of electrical equipment in MCC/SG is an important function of HVAC system offshore. The components
include:
• Transformers • Motors
• Medium/high voltage switchgears • Cables & trays
• Motor starters • Inverters
• Battery chargers • Circuit breakers
• Unit panel board etc
• Heat dissipation from these equipments are mainly based data published by the manufacturers
Typical Outdoor & Indoor Design
Conditions Used Here
Conditions Dry-bulb temperature (C) % RH Moisture content, kg/kg Outdoor air 35 70 0.025 Indoor air 22 55 0.009 Difference 13 0.016
ASHRAE fundamental Handbook published data, at 0.4%, 1% and 2% design level. At 0.4% design level, Miri has only 35h (out of 8760 h a year) at 32.2 DB & 26.3 WB or higher
Infiltration Air is Cooling Load
• Load due to Ventilation air into the space
Sensible load, (W)
= mass flow rate x specific heat x (∆T)
= 1.23 x l/s x (To – T i) or (1.08 x cfm x ∆T) Where To = Outside temperature, C
Ventilation Cooling Load
Ventilation latent load, (W)
= mass flow rate x latent heat of vaporization x (humidity difference)
= 3010 x l/s x (∆ẁ) or (4840 x cfm x ∆ẁ)
Where
∆ẁ = Inside-outside humidity ratio difference of air ( kg/kg)
Total Cooling Load
• This is also call the Grand total load • Sum of
– Space heat gain – System heat gain
– load due to outdoor air supplied through the air handling unit
• Air bypassed the coil
• Air not bypassed the coil
System Heat Gain
• These are sometimes external to the air conditioned space
• HVAC equipment also contributes to heat gain
– Fan heat gain – Duct heat gain
Bypass Factor
Bypass factor is an important coil characteristic on moisture removal performance .
It’s value depends on:
• Number of rows/fins per inch • Velocity of air
Bypass Factor of the coil
• When air streams across the cooling, portion of air may not come into contact with the coil surface
• BPF = un-contacted air flow total flow
BPF is normally selected at 0.1 for offshore cooling and dehumidification.
Typical Coil Bypass Factor
Row Deep 14 fins/inch
Face velocity= 2 m/s 2.5 m/s 3 m/s 1 0.52 0.56 0.59 2 0.274 0.31 0.35 4 0.076 0.10 0.12 6 0.022 0.03 0.04
Effect of Bypass Factor
on Ventilation Load
• Coil load due to outdoor air
SH= (OASH)(1-BPF) LH= (OALH)(1-BPF)
• Effective room load
ERSH=RSH+(OASH)(BPF) ERLH=RLH + (OALH)(BPF)
Cooling Load Classroom Exercise
• Estimate the cooling load of a portal cabin shown here: • Assuming that – Outdoor condition is 35C, 70% RH – Indoor condition is 22C , 55 % RH – U-factor=0.5 W/m2 K – Occupied by 2 persons
– Electrical equipment heat is 3 kW – 100l/s leakage due to pressurization Platform Lower Deck 4 x 4 x 3 h
N
Cooling Load Calculations
Items Procedures
Transmission- sensible Wall- West side
Wall- East side Wall – North Wall- South Roof Floor Total (T1) Q = UA (CLTD)
Internal load- sensible People
Equipment Light
Total (T2)
Safety Factor (5% of T1+ T2)
Fan heat & supply Duct Gain (7 % of T1+T2) RSH (Total of the above)
Coil Load Calculations
Items Procedures
Room Latent Heat (RLH) People
Room Total Heat RSH + RLH
Cooling Load Calculations
Items Procedures
Design conditions Outdoor 35C, 70% RH Indoor 22C, 55 RH Ventilation- sensible
Bypass air (0.1 bypass factor) Sensible heat of bypass air
10% x outdoor air
Ventilation - Latent
Cooling Load Calculations
Items Procedures
Design conditions Outdoor 35C, 70% RH Indoor 22C, 55 RH ERSH
RSH
Sensible heat of air bypass Effective Room Sensible Heat ERLH
People
Latent heat of air bypass Effective Room Latent Heat
Effective Room Total Heat (ERTH) ERSH+ESLH
Coil Load Calculation
Items Procedures
Design conditions Outdoor 35C, 70% RH Indoor 22C, 55 RH Coil Load – Sensible
Effective Room Sensible Heat SH of Outdoor air not bypassed Total (Coil Sensible heat)
Coil Load – Latent
Effective Room Latent Heat LH of Outdoor air not bypassed Total (Coil latent heat)
Sensible Heat Factor (SHF)
SHF
RSHF
ESHF
GSHF
Sensible Heat Factor (SHF)
• Ratio of sensible to total heat
– SHF = Sensible heat/ total heat
= SH/ (SH + LH)
A low value of SHF indicates a high latent heat load, which is common in humid climate.
• In the above example,
– Calculate the SHF of the room (RSHF)
– Calculate the effective room sensible heat factor (ESHF)
Selection of Air Conditioning
Apparatus
• The necessary data required are:
– GTH ( Grand total heat load) – Dehumidified air quantity – Apparatus dew point
These determine the size of the apparatus and refrigerant temperature.