Changing the Wireless Button ParametersChanging the Wireless Button Parameters
4. Access and configure the parameters in the Door Define menu, as follows:
Access Control: Door Define
Quick Keys Parameter Default Range
9
9 11 11 Partitions
Defines which partitions are assigned to the door.
1. Press [1] and then press .
2. Use the or keys to select a partition number and then use the key to toggle [Y] YES or [N] NO to assign that partition to the door.
3. Press .
NOTE:
The logic that stands behind the partitions that are assigned to the door is to create a walking path. For example, if in a certain office all the partitions are armed and the manager wants to enter only his room, then you can assign the door for the partitions on his way to the office. In this way when he disarms the system by using his access card, he will disarm only the waking path partitions.
9
9 11 22 Door Time Settings
Defines the open delay, door force delay, and the door alarm delay settings.
1. Press [2] and press .
2. Select the required door time settings option:
❖✸ Open Delay
❖✸ Door Force Delay
❖✸ Door Alarm Delay 9
9 11 22 11 Open Delay 4 seconds 1-99 seconds
Determines the amount of time that the door relay is open after a valid entry.
1. Press [2] and to enter the door time settings.
2. Press [1] and .
3. Enter the number of seconds (between 1-99) to define the door open relay time.
4. Press .
Access Control: Door Define
Quick Keys Parameter Default Range
9
9 11 22 22 Door Force Delay NO YES/NO
Determines whether an alarm is activated on relay 3 (of the Access Module) immediately when the door is forced open or is activated according to the time defined in the Door Alarm Delay parameter (described below).
1. Press [2] and to enter the door time settings.
2. Press [2] and .
3. Toggle the key to select the appropriate option, as follows:
❖✸ YES: Activates the door alarm delay according to the Door Alarm Delay parameter (described below).
❖✸ NO: Activates an immediate alarm when the door is forced open.
4. Press . 9
9 11 22 33 Door Alarm Delay 10 seconds 1-99 seconds
Determines the amount of time that the door can remain open before an alarm is activated (triggered on relay 3). This option also determines the amount of time that passes until an alarm is activated when the door is forced open.
1. Press [2] and to enter the door time settings.
2. Press [3] and .
3. Enter the number of seconds (between 1-99) to define the door alarm relay time.
4. Press . 9
9 11 33 Door Fire Settings Open Open/Closed
Determines the status of the door during a fire alarm as either open or closed.
Once a fire alarm is triggered by the ProSYS, the system sends a fire alarm notification to the Access Control module, which sets the door relay to the required position during the fire alarm.
1. Press [3] and .
2. Toggle the key to select the appropriate option, as follows:
❖✸ YES: Keeps the door open during a fire alarm.
❖✸ NO: Keeps the door closed during a fire alarm.
3. Press .
Access Control: Door Define
Quick Keys Parameter Default Range
9
9 11 44 Door Input Settings
Defines the status of the door relay input during operation.
1. Press [4] and .
2. Select the required door relay input:
❖✸ Door Contact
❖✸ Request to Exit (RTE) Button 9
9 11 44 11 Door Contact NO (normally open) NO/NC
This door contact starts a timer in the reader interface that notifies the system when a door is open. Press [4] and to enter the door input settings.
1. Press [1] and .
2. Toggle the key to select the appropriate door contact termination, as follows:
❖✸ NO: Sets the door contact to normally open.
❖✸ NC: Sets the door contact to normally closed.
3. Press . 9
9 11 44 22 RTE Button NO (normally open) NO/NC When pressed, this device sends a command to the door relay.
1. Press [4] and to enter the door input settings.
2. Press [2] and .
3. Toggle the key to select the appropriate RTE button termination, as follows:
❖✸ NO: Sets the RTE button to normally open.
❖✸ NC: Sets the RTE button to normally closed.
4. Press . 9
9 11 55 Door Label
Enables you to assign a door label.
1. Press [5] and .
2. Enter a door label. (Refer to Entering a New Label Using the LCD Keypad, page 5-14.)
3. Press .
9
9 22
Access Control: Card Code Position Access Control: Card Code Position Access Control: Card Code Position Access Control: Card Code Position
Default: 00 Range: 00-37
The Card Code Position menu enables you to specify the position that the system will start to read the 8-digit card code only on Magnetic or Barcode technologies. The position that you define is applicable to all cards in the system.
By default, the system reads the first 8 digits of the card track. If the first 8 digits of the card are identical (this may occur on credit cards where the first digits may be, for example, the bank code or the name of the credit card company), it will be necessary to read 8 digits from a different section of the card track.
NOTES:
The card code position definition does not apply to cards in Wiegand Technology.
If the card code position is changed for cards in Magnetic or Barcode technologies the cards previously defined in the system will not work and will need to be redefined in the system
Refer to the card manufacturer or to your Rokonet service provider for additional details regarding the card code format, if required.
To access the Card Format menu:1. Access the Access Control menu, as described on page 5-111.
2. From the Access Control menu, press [2] to access the Card Format menu options. The following display appears:
3. Enter a number (between 00-37) to define the starting card code position. This position determines where the system will start reading the 8-digit code on the card.
4. Press .
9
9 33
Access Control: Special Code Access Control: Special Code Access Control: Special Code Access Control: Special Code
The Special Code menu enables you to assign codes to the arm cards defined in the system in order to perform operations in addition to opening the doors (such as arming the system).
Users can arm the system only after the Arm Code has been entered, as this code informs the system that its about to be armed. This option is only applicable for readers that include a keypad with the following technology combinations:
✦✸ Keypad and proximity
✦✸ Keypad and magnetic
To access the Special Code menu:1. Access the Access Control menu, as described on page 5-111.
2. From the Access Control menu, press [3] to access the Special Code menu options. The following display appears: