5 Operating principle
8.4 Alarm message to the panel
The following description has been written on the basis of a sample fire alarm message.
8.4.1 Optical and acoustic signals
– The red alarm signal light on the LED display lights up.
– An internal buzzer sounds; see also Section 9.3 Switching off internal buzzer, page 45.
– Depending on the configuration, sounders and/or optical signaling devices (e.g. sirens, strobes) are activated.
If the transmission device to the fire department is activated, the "Transmission Device activated" signal light lights up red.
8.4.2 Displaying the detector zones in alarm state
The number of messages in question is displayed on the status bar.
The individual messages are shown in the display:
– List fields with black background: unacknowledged alarm messages – List fields without distinction: acknowledged alarm messages Logical Zones
If more than four alarm messages have been received, scroll through the list in order to display the next messages (see Section 5.6.1 Scrolling through lists).
Display during an alarm
The buttons located beneath the alarm message on the display can be used to initiate the corresponding actions:
– Acknowledge: Touch this button to acknowledge all of the alarm messages shown on the display; see also Section 9.2 Acknowledging a message, page 44.
– Signals off: Touch this button to switch off activated external signaling devices; see also Section 9.4 Switching external signaling devices on and off, page 45.
– Signals on: Touch this button to switch on deactivated external signaling devices; see also Section 9.4 Switching external signaling devices on and off, page 45.
NOTICE!
First of all, the logical zones in which one or more detectors have triggered an alarm are listed.
To display the individual detectors, select the logical zone you require. See also Section 8.4.6 Displaying the individual detectors in a logical zone, page 43.
NOTICE!
A maximum of four alarm messages can be displayed on the display simultaneously.
Only fields that can be operated are displayed (e.g. Acknowledge and Reset).
NOTICE!
The latest message is always displayed at the end of the list.
Acknowledge Signals off Signals on Reset
42 en | Alarm Panel Controller
8.4.3 Sequence of the alarm messages
The messages are displayed in chronological order.
– The newest alarm message of a logical zone is always displayed at the end of the list.
– The first and oldest alarm message of a logical zone is displayed at the beginning of the list. The next three messages are displayed as you scroll through the list.
8.4.4 Information about logical zones in the alarm state
The alarm message contains information about:
– The element category – The message type
– The address of the detector group
– The number of detectors that have triggered an alarm in the respective logical zone – The message number
– Depending on the configuration, additional information such as the installation location Example:
Message type
The message type Fire is reported.
Depending on the configuration, the message type may be defined more specifically, e.g. Fire PAS for a fire alarm with alarm verification.
Address of logical zone
00005: the fifth logical zone triggered the first fire alarm.
Number of detectors
(6): In the fifth logical zone (00005), six detectors (6) triggered a fire alarm.
For logical zones that only consist of one element, no number of detectors is displayed.
Message number
The alarm messages are numbered chronologically.
The message number in the second line indicates the sequence in which the alarm messages arrived.
#001: The first alarm message that came in.
Depending on the configuration, additional information is displayed in the second line, such as the installation location of the logical zone.
8.4.5 The newest message
The latest message is always displayed at the end of the list.
The message number (e.g. #008) of the latest message indicates the total number of logical zones in which one or more detectors have triggered an alarm.
NOTICE!
30 seconds after the last entry (e.g. after scrolling through the list), the first and oldest alarm is displayed at the beginning of the list again.
Fire Zone 00005
#001 Office 1 (6)
NOTICE!
Depending on the configuration of the system, either the logical or physical address of the detector is displayed.
Panel Controller Alarm | en 43
8.4.6 Displaying the individual detectors in a logical zone
To display the individual detectors in a logical zone, select the logical zone you require.
The alarm messages for the individual detectors are listed.
8.4.7 Information about individual detectors
Each alarm message contains information about:
– The element category – The message type – The detector address – The message number
– Depending on the configuration, additional information such as the installation location Example:
Message type
Refer to Section 8.4.4 Information about logical zones in the alarm state for information on the type of message.
Message address
In this example, the following detector has triggered a fire alarm:
0005 - 004: the fourth detector (004) in the fifth logical zone (00005).
If the detector number, in this case (004), is not displayed, this is the alarm message for the logical zone.
Message number
For information on the message number (#002), see Section 8.4.4 Information about logical zones in the alarm state.
Depending on the configuration, additional information is displayed in the second line, such as the installation location of the detector or the detector type.
To display more information about an alarm message, see Section 8.4.8 Displaying additional information.
8.4.8 Displaying additional information
To display further information about the individual detectors, select the alarm message you require.
The following information is displayed:
– Element category – Message type
Fire Detectors 00005 - 004
#002 Office 1
NOTICE!
Depending on the configuration of the system, either the logical or physical address of the detector is displayed.
NOTICE!
By way of example, an action text can be entered for every detector type in the FSP-5000-RPS programming software.
44 en | Fire alarm Panel Controller
9 Fire alarm
This chapter contains information about the following points:
– Section 9.2 Acknowledging a message, page 44 – Section 9.3 Switching off internal buzzer, page 45
– Section 9.4 Switching external signaling devices on and off, page 45
– Section 9.5 Resetting external signaling devices and transmission devices, page 45 – Section 9.6 Triggering fire verification, page 46
– Section 9.7 Resetting alarm message, page 47 – Section 9.8 Bypassing detectors, page 48 Signaling fire alarms
A fire alarm is signaled optically and acoustically on the panel through:
– Displaying the logical zones on the display – Lighting up the "Alarm" LED display – An internal buzzer sounds on the system.
9.1 Optical and acoustic signals
– The red alarm signal light on the LED display lights up
– An internal buzzer sounds; see also Section 9.3 Switching off internal buzzer, page 45.
– Depending on the configuration, sounders and/or optical signaling devices (e.g. sirens, strobes) are activated.
If the transmission device to the fire department is activated, the Transmission Device activated LED display lights up red: