APU FIRE

In document A320 Notes (Page 59-64)

• Fire detection system comprises two loops “A” & “B”

• FDU operation same as Engine FDU

• Fire protection same as engine

• Test P/B press –

• Squib Lt. ON ( Circuit checks) + DISCH Lt. ON (lamp test)

• Does not check fire sensors, if both loops defective test does happen (red fire P/B will not light)

• APU system warnings

• APU fire push button select out

• Cancel CRC

• Squib Lt. On (arm extinguisher squib)

• Lt. On external power panel

• ECB – APU emergency shut down

• ECAM – messages

• Isolation of by ECB

• Fuel LP SOV close

• APU fuel pump shuts

• Bleed valve and cross bleed valve close

• IDG deenergize

• Auto extinguishing will trigger when APU fire detected on GND. and squib Lt. does not illuminates

• If loop “A” inoperative auto extenuating will not happen as circuit will not sense fire

• System warning

• ECAM messages (fire procedure) + CRC + M/W + Eng. & Fire panel Lts. ON

APU FIRE

PUSH

APU Extinguishing ground test

• APU master Sw ON

• Test P/B press ON Lt. illuminates + APU fire push Lt. come ON

• If APU runs, will shut down

• After 3 sec. T/D, OK Lt. appears + external fire Lt. ON

• Master Sw fault Lt. ON

• External hone sounds

• Press reset

• Hone stops

• OK Lt. OFF

• Fire P/B red Lt. OFF

• After 3 sec. system reset RESET

System operation with APU fire

• Manual extinguisher

In flight

• CRC + Fire P/B + M/W flashers

• Press fire P/B

• CRC stops

• Fuel LP + fuel solenoid OFF ( APU shut down via ECB )

• Squib Lt. ON

• APU fault Lt. ON

• 10 sec T/D to allow reduce air flow

• Agent P/B press

• Both discharge Lt. ON

• When fire extinguishes fire P/B Lt. + M/W OFF

• Fault LT. OFF

On Ground

• CRC + Fire P/B Lt. ON + M/W + External hone ON

• Fuel LP & Solenoid valve close + APU shut down

• CRC stops

• S/C, M/C, M/W appears

• After T/D 3 sec.

• Fire bottle discharges + “DISCH” Lt. ON

• APU fire extinguishes

• Fire P/B Lt. + External fire Lt. + M/W disappears & horn stops

• Master power Sw. fault Lt. ON and M/C remain ON

APU SHUT OFF

Avionics Smoke detection

• Smoke detector installed in the extraction duct of vent line

• During smoke detection

• Smoke detector sends signal to FWC + local warnings + AEVC

• Smoke detector is Ionization type

• Test can be done by CFDS AEVC test, AEVC checks smoke detector

• Smoke Lt. on Gen. 1 P/B triggered by Smoke detector

• When smoke detector activates Fault Lt. illuminates on Blower & Extract P/B OK

ON

SQUIB DISCH

Avionics Smoke procedure

• When Smoke detects

BLOWER M/C + S/C + Gen. 1line P/B smoke Lt. ON + Blower & Extractor Fault Lt. ON

• ECAM shows action to be taken

• Use oxy masks + crew communication not in interphone position to prevent breathing noise

• Sw. OFF cabin fans to prevent smoke get in to the cabin

• To evacuate smoke OVBD by selecting Blower OVRD + Extraction fan P/B to OVRD

• Blower OVRD – Blower stops and use air condition cold air sauce to blow smoke out board

Smoke Lt. ON – Smoke detected in the avionics ventilation duct

SDCU (Located on 94vu)

• Detects each compartment smoke detectors

• When one detector detects, SDCU checks with other status automatically

• If other detector normal, first detector declare as faulty

• If 2nd detector abnormal, 2nd one declared as faulty

• SDCU sends local warnings + ECAM and to Cargo ventilation controller + CFDS

• SDCU monitor bottle pressure + squib circuit condition, if notice any abnormality report to ECAM + CFDS

• If any wiring failure by SDCU - MCDU test facility can find the area of the failure Cargo compartment fire protection

• Smoke detectors

• Qty 2 in FWD cargo

• Qty 2 each in AFT and Bulk cargo

• Cargo smoke detectors connectors to each other and in a loop with Lavatory smoke detectors

• All connected to SDCU

• One Fire bottle located in FWD cargo for both compartments, Qty 2 squibs one for each compartment supply line with one pressure Sw.

• In case of smoke in the FWD or AFT/BULK cargo

• Smoke Lt. on flight deck illuminates

• Cargo vent. Cont. closes isolation valve of effected compartment.

• If smoke detector faulty, signal sends to CFDS + ECAM

• Discharge fire bottle by pressing agent P/B

• Discharge Lt. ON

• After agent discharged both “DISCH” Lt.s appears FWD

Smoke Lt. ON – System detects smoke in the compartment - If both channels detect smoke

- One channel detects smoke if other channel detects fault by SDCU

Disch Lt. ON – Bottle discharged FAULT

• Test (From cargo compartment smoke panel)

• SDCU simulates smoke & bottle pressure drop condition

• Warning Lt. illuminates twice + ECAM msg.

• Ventilation system isolation valves closes

• Amber discharge Lt. ON

• Switch released

• After 2 sec. discharge Lt. OFF

• After 10 sec. ECAM msg. displayed

• ECAM msg. disappear and will be automatically repeat after 6 sec. with warning indication

Cargo and Lavatory smoke detection system

• Connected to both SDCU channels via safety two wire data & supply bus working followed the close loop principle

• When smoke detectors detect Lavatory. Smoke detection warning

• To flight deck via FWC to ECAM + M/W + CRC

• SDCU sends warning to cabin CIDS then

• FWD attendant panel

• Attendant indicator panel

• Area call Lt. (Pink) + Lavatory. caution Lt. flashing

• Programming test panel (PTP)

• Lavatory. Detector faults sends to flight deck cabin for indication on CFDS for maintenance purpose,

• For the cabin – Fwd attendant panel CIDS amber Lt. + PTP indications

• Cargo smoke detected SDCU provide smoke warning to flight deck through FWC 1 & 2 such as M/W, ECAM CRC, Smoke Lt. on cargo control panel

• Cargo smoke detector detects faulty by SDCU automatically isolated, if both detectors fail in the same cavity fault msg. on ECAM and inoperative detector shown in the CFDS

• Fire bottle pressure drop or squib circuit discontinuity SDCU sends signal to ECAM & CFDS + S/C, M/C

• SDCU internal failure detected SDCU fault warning sent to flight deck ECAM + S/C +M/C and failure indicated on CFDS

• Incase of only one channel failure remaining channel will operate Cargo Smoke Detection System

• Warning

• CRC + M/W + ECAM

• Smoke Lt. on cargo panel

• Fault Lt. on isolation valve P/B

• ECAM air condition system page shows isolation valve in amber colour Smoke procedure

• CRC + M/W + smoke Lt. on cargo cont. panel

• Isolation valve fault Lt. ON

• Isolation valve select OFF valve closer confirmed

• Press bottle discharge P/B

• “DISCH” Lt. ON on both FWD and AFT cargo P/B

• After smoke disappear all warnings except DISCH Lt.

• On GND. Cargo fire bottles must not used Lavatory Fire Protection System

• Smoke detector located in the ceiling panel at exttaction duct in each lavatory

• All Lavatory Smoke detectors interconnected to each other as a part of a loop with cargo smoke detectors, sends signals to SDCU

• Smoke detectors inform to SDCU then to flight deck & cabin CIDs directors

• Warning received to SDCU activate ECAM + CIDS + CFDS

• Fire extinguishing by portable fire extinguishers

Lavatory Smoke Warnings

• In flight, CRC + M/W + ECAM activation

• In Cabin,

• Triple chime continuously

• Smoke Lt. On FAP + effected lavatory location written

• Attendant indication panel

• Area call amber Lt. flashing

• Lavatory amber Lt. flashing

• Warning can be reset by reset Sw. at FAP Lavatory waste bin extinguisher

• Auto extinguisher by incase of fire after melting fusible material in the tip of discharge tube when temp.>79 C

In document A320 Notes (Page 59-64)