• No results found

ASDUs for process information in control direction

In document INTERNATIONAL STANDARD (Page 100-105)

7.3 Definition and presentation of the specific ASDUs

7.3.2 ASDUs for process information in control direction

Single command

Single information object (SQ = 0)

TYPE IDENTIFICATION

VARIABLE STRUCTURE QUALIFIER Defined in 7.2.3 CAUSE OF TRANSMISSION

Defined in 7.2.4 COMMON ADDRESS OF ASDU

DATA UNIT IDENTIFIER

Defined in 7.1

0 0 1 0 1 1 0 1

Defined in 7.2.5

S/E

INFORMATION OBJECT ADDRESS

INFORMATION

OBJECT

SCO = Single command, defined in 7.2.6.15 QU

0 0 0 0 0 0 0 1

0 SCS

IEC 148/03

Figure 64 – ASDU: C_SC_NA_1 Single command C_SC_NA_1 := CP{Data unit identifier,Information object address,SCO}

CAUSES OF TRANSMISSION used with TYPE IDENT 45 := C_SC_NA_1 CAUSE OF TRANSMISSION in control direction:

<6> := activation

<8> := deactivation in monitor direction:

<7> := activation confirmation

<9> := deactivation confirmation

<10> := activation termination

<44> := unknown type identification

<45> := unknown cause of transmission

<46> := unknown common address of ASDU

<47> := unknown information object address

7.3.2.2 TYPE IDENT 46: C_DC_NA_1 Double command

Single information object (SQ = 0)

TYPE IDENTIFICATION

VARIABLE STRUCTURE QUALIFIER Defined in 7.2.3 CAUSE OF TRANSMISSION

Defined in 7.2.4 COMMON ADDRESS OF ASDU

DATA UNIT IDENTIFIER

Defined in 7.1

0 0 1 0 1 1 1 0

INFORMATION OBJECT ADDRESS

INFORMATION

OBJECT

DCO = Double command, defined in 7.2.6.16

0 0 0 0 0 0 0 1

Defined in 7.2.5

S/E QU DCS

IEC 149/03

Figure 65 – ASDU: C_DC_NA_1 Double command

LICENSED TO MECON Limited. - RANCHI/BANGALOREFOR INTERNAL USE AT THIS LOCATION ONLY, SUPPLIED BY BOOK SUPPLY BUREAU.

C_DC_NA_1 := CP{Data unit identifier,Information object address,DCO}

CAUSES OF TRANSMISSION used with TYPE IDENT 46 := C_DC_NA_1 CAUSE OF TRANSMISSION in control direction:

<6> := activation

<8> := deactivation in monitor direction:

<7> := activation confirmation

<9> := deactivation confirmation

<10> := activation termination

<44> := unknown type identification

<45> := unknown cause of transmission

<46> := unknown common address of ASDU

<47> := unknown information object address

7.3.2.3 TYPE IDENT 47: C_RC_NA_1 Regulating step command Single information object (SQ = 0)

TYPE IDENTIFICATION

VARIABLE STRUCTURE QUALIFIER Defined in 7.2.3 CAUSE OF TRANSMISSION

Defined in 7.2.4 COMMON ADDRESS OF ASDU

DATA UNIT IDENTIFIER

Defined in 7.1

0 0 1 0 1 1 1 1

INFORMATION OBJECT ADDRESS

INFORMATION

OBJECT

RCO = Regulating step command, defined in 7.2.6.17

0 0 0 0 0 0 0 1

Defined in 7.2.5

S/E QU RCS

IEC 150/03

Figure 66 – ASDU: C_RC_NA_1 Regulating step command C_RC_NA_1 := CP{Data unit identifier,Information object address,RCO}

CAUSES OF TRANSMISSION used with TYPE IDENT 47 := C_RC_NA_1 CAUSE OF TRANSMISSION in control direction:

<6> := activation

<8> := deactivation in monitor direction:

<7> := activation confirmation

<9> := deactivation confirmation

<10> := activation termination

<44> := unknown type identification

<45> := unknown cause of transmission

<46> := unknown common address of ASDU

<47> := unknown information object address

LICENSED TO MECON Limited. - RANCHI/BANGALOREFOR INTERNAL USE AT THIS LOCATION ONLY, SUPPLIED BY BOOK SUPPLY BUREAU.

7.3.2.4 TYPE IDENT 48: C_SE_NA_1

Set-point command, normalized value Single information object (SQ = 0)

TYPE IDENTIFICATION

VARIABLE STRUCTURE QUALIFIER Defined in 7.2.3 CAUSE OF TRANSMISSION

Defined in 7.2.4 COMMON ADDRESS OF ASDU

DATA UNIT IDENTIFIER

Defined in 7.1

0 0 1 1 0 0 0 0

Defined in 7.2.5 INFORMATION OBJECT ADDRESS

INFORMATION OBJECT

NVA = Normalized value, defined in 7.2.6.6

QOS = Qualifier of set-point command, defined in 7.2.6.39 S/E

Figure 67 – ASDU: C_SE_NA_1 Set-point command, normalized value C_SE_NA_1 := CP{Data unit identifier,Information object address,NVA,QOS}

CAUSES OF TRANSMISSION used with TYPE IDENT 48 := C_SE_NA_1 CAUSE OF TRANSMISSION in control direction:

<6> := activation

<8> := deactivation in monitor direction:

<7> := activation confirmation

<9> := deactivation confirmation

<10> := activation termination (opt)

<44> := unknown type identification

<45> := unknown cause of transmission

<46> := unknown common address of ASDU

<47> := unknown information object address

7.3.2.5 TYPE IDENT 49: C_SE_NB_1 Set-point command, scaled value Single information object (SQ = 0)

TYPE IDENTIFICATION

VARIABLE STRUCTURE QUALIFIER Defined in 7.2.3 CAUSE OF TRANSMISSION

Defined in 7.2.4 COMMON ADDRESS OF ASDU

DATA UNIT IDENTIFIER

Defined in 7.1

0 0 1 1 0 0 0 1

Defined in 7.2.5 INFORMATION OBJECT ADDRESS

INFORMATION OBJECT

SVA = Scaled value, defined in 7.2.6.7

QOS = Qualifier of set-point command, defined in 7.2.6.39 S/E

Figure 68 – ASDU: C_SE_NB_1 Set-point command, scaled value

LICENSED TO MECON Limited. - RANCHI/BANGALOREFOR INTERNAL USE AT THIS LOCATION ONLY, SUPPLIED BY BOOK SUPPLY BUREAU.

C_SE_NB_1 := CP{Data unit identifier,Information object address,SVA,QOS}

CAUSES OF TRANSMISSION used with TYPE IDENT 49 := C_SE_NB_1 CAUSE OF TRANSMISSION in control direction:

<6> := activation

<8> := deactivation in monitor direction:

<7> := activation confirmation

<9> := deactivation confirmation

<10> := activation termination (opt)

<44> := unknown type identification

<45> := unknown cause of transmission

<46> := unknown common address of ASDU

<47> := unknown information object address

7.3.2.6 TYPE IDENT 50: C_SE_NC_1

Set-point command, short floating point number Single information object (SQ = 0)

TYPE IDENTIFICATION

VARIABLE STRUCTURE QUALIFIER Defined in 7.2.3 CAUSE OF TRANSMISSION

Defined in 7.2.4 COMMON ADDRESS OF ASDU

DATA UNIT IDENTIFIER

Defined in 7.1

0 0 1 1 0 0 1 0

0

INFORMATION OBJECT ADDRESS

INFORMATION OBJECT

IEEE STD 754 = Short floating point number, defined in 7.2.6.8 Defined in 7.2.5

Fraction

QOS = Qualifier of set-point command, defined in 7.2.6.39

S/E QL

IEC 153/03

Figure 69 – ASDU: C_SE_NC_1 Set-point command, short floating point number C_SE_NC_1 := CP{Data unit identifier,Information object address,IEEE STD 754,QOS}

CAUSES OF TRANSMISSION used with TYPE IDENT 50 := C_SE_NC_1 CAUSE OF TRANSMISSION in control direction:

<6> := activation

<8> := deactivation in monitor direction:

<7> := activation confirmation

<9> := deactivation confirmation

<10> := activation termination (opt)

<44> := unknown type identification

<45> := unknown cause of transmission

<46> := unknown common address of ASDU

<47> := unknown information object address

LICENSED TO MECON Limited. - RANCHI/BANGALOREFOR INTERNAL USE AT THIS LOCATION ONLY, SUPPLIED BY BOOK SUPPLY BUREAU.

7.3.2.7 TYPE IDENT 51: C_BO_NA_1 Bitstring of 32 bit

Single information object (SQ = 0)

TYPE IDENTIFICATION

VARIABLE STRUCTURE QUALIFIER Defined in 7.2.3 CAUSE OF TRANSMISSION

Defined in 7.2.4 COMMON ADDRESS OF ASDU

DATA UNIT IDENTIFIER

Defined in 7.1

0 0 1 1 0 0 1 1

Defined in 7.2.5 INFORMATION OBJECT ADDRESS

INFORMATION OBJECT

BSI = Binary state information, 32 bit, defined in 7.2.6.13 Bitstring

Bitstring Bitstring Bitstring

0 0 0 0 0 0 0 1

IEC 154/03

Figure 70 – ASDU: C_BO_NA_1 Bitstring of 32 bit C_BO_NA_1 := CP{Data unit identifier,Information object address,BSI}

CAUSES OF TRANSMISSION used with TYPE IDENT 51 := C_BO_NA_1 CAUSE OF TRANSMISSION in control direction:

<6> := activation

<8> := deactivation in monitor direction:

<7> := activation confirmation

<9> := deactivation confirmation

<10> := activation termination (opt)

<44> := unknown type identification

<45> := unknown cause of transmission

<46> := unknown common address of ASDU

<47> := unknown information object address

LICENSED TO MECON Limited. - RANCHI/BANGALOREFOR INTERNAL USE AT THIS LOCATION ONLY, SUPPLIED BY BOOK SUPPLY BUREAU.

7.3.3 ASDUs for system information in monitor direction

In document INTERNATIONAL STANDARD (Page 100-105)