• No results found

Basic Functions

In document 132kv GIS (Page 163-171)

Conventional Substation Automation

4.18.1 Function List

4.18.1.1 Basic Functions

User interface for local control system

S HV-apparatus control from the single line diagram S HV-apparatus position indication

Alarm system

S Process alarms S Logical alarms S System alarms CB operation counter Measured Values

S Electrical current, three-phase S Voltage, three-phase

Interlocking

S Bay interlocking S Apparatus interlocking

S Protection of disconnector and earthing switches against switching under load

S Intermediate position interlocking of the circuit breaker S Electric hand-crank interlocking

S Hand-crank hole interlocking (only ELK-04) S End-position interlocking

S Station wide interlocking

S Interlocking against coupling, sectionalizer and busbar earthing switch S Interlock override with key switch possible

1HDG 518 412 D en 10.05.2005 EXTMEWE 12.05.2005 CHSVOTH 4.18-2 S Time synchronisation

S HMI (human machine-interface) S Selfsupervisor

S Conventional functions

S Antipumping control of circuit breaker (CB)

S Blocking or autotrip of the circuit breaker at too low gas density level in the CB gas compartment

S Blocking or autotrip of the circuit breaker at too low drive force level S Control and supervision of the hydraulic pump

S Protection of the different control voltage circuits S Cubicle lighting

S Socket

S MCBs for protection of the low voltage circuits of voltage transformer

4.18.1.2 Options

The following optional functions can be added on request:

Measurements

S Indications from a protection system S Indications from a transformer

Interface stations system (e.g. MicroSCADA) / remote control system Optional Equipment

S Cubicle anti-condensation heating

S Operating mechanism anti-condensation heating S Transducers

S Coupling relays

S Auxiliary switch contact reproduction S Busbar replication

S Protection system S Trip circuit supervision S Synchrocheck

S Arc detection

1HDG 518 412 D en 10.05.2005 EXTMEWE 12.05.2005 CHSVOTH 4.18-3 Optional Applications

S Additional spare terminals (10% are included as standard) S Customer-specific terminal types

S Ferrules

S Special wirings / cablings

(coloured, halogen-free, heat-resistant)

4.18.2 Functional Description

1  Sensor for electronic key switch 2  Emergency of circuit breaker

(has to be pressed together with button 3 to trip the circuit breaker) 3  OFF button

4  Select button

5  ON button 6  Menu button 7  Enter button 8  Button to scroll up 9  Button to scroll down

4 5 6 7

3 8

1 2 9

Figure 4.18-1: REF542plus

The following list describes all the functions which are available and conventional wir-ing between control cubical and GIS.

1HDG 518 412 D en 10.05.2005 EXTMEWE 12.05.2005 CHSVOTH 4.18-4

4.18.2.1 Basic Functions

User interface for local control

The local control is possible via a display which is connected to the control unit of the REF542plus via a serial interface. The display offers the following functions:

S Single line diagram in accordance with project-specific arrangement with dis-play of the current positions of the switchgear

S Control switchgear devices S Alarm acknowledgement

S OFF / LOCAL / REMOTE / LOCAL&REMOTE switchover (via electronic key switch)

S 3 displays for measurements values

S Individual alarms on LED with full text description

in accordance with project-specific alarm configuration (max. 32) HV apparatus control

The devices can be controlled locally at the display or via the station bus. Control is possible after checking the various interlocking conditions and the switching authority, with one switch impulse via binary output (BO). The circuit breaker will trip immedi-ately when a protection device gives the command to trip.

HV apparatus position indication

Double point indications are picked up by binary inputs (BI) from the auxiliary switch of the high-voltage devices and are displayed on the REF542plus display, and can also be transmitted via the station bus. In the case of intermediate position of the switching devices, an alarm is created and transmitted via the station bus.

Alarm system indication

Alarms are visible on the REF542plus display and transmission via the station bus is possible. The alarms can be acknowledged either manually in the REF542plus menu or automatically.

S Process alarms

(e.g. CB alarms, MCB trip, SF6 gas density from the GIS bay and messages from the protection system via BI)

S Logical alarms

(e.g. intermediate position) S System alarms

(e.g. computer malfunction)

1HDG 518 412 D en 10.05.2005 EXTMEWE 12.05.2005 CHSVOTH 4.18-5 Selection of the switching authority

With the REF542plus it is possible to realise four operating statuses, corresponding to the position of the OFF / LOCAL / REMOTE / LOCAL&REMOTE switch:

S OFF

No switching actions are possible

S LOCAL

Switching actions are only possible from the local control system (REF542plus display)

S REMOTE

Switching actions are only possible from a superordinate device (e.g. Station control system).

S LOCAL&REMOTE

Switching actions possible from local and from a superordinate device.

This selection switch position can be transmitted via the station bus, including a time stamp.

Switching cycle count CB

All switch-off procedures of the circuit breaker are registered via BI, shown on the dis-play as a numerical value in the range 0 to 32767, and transmitted via the station bus.

Operation Measurement

Standard input sizes are 0 – 1 A and 0 – 100 V S Electrical current:

The appropriate values (three-phase measurement) are shown on the dis-play and can be transmitted via the station bus

S Voltage

The appropriate values (three-phase measurement) are shown on the dis-play and can be transmitted via the station bus

Interlocking

All interlockings in the REF542plus are realised by function blocks in the application software.

Interlock bypass

The complete interlocking  with the exception of the end position and hand crank in-terlock  can be bypassed using a key switch.

S Interlock override with key switch

The complete interlocking  with the exception of the handcrank and the end position interlock  is by-passed at this position. The mode can also be trans-mitted via the station bus, including a time stamp.

1HDG 518 412 D en 10.05.2005 EXTMEWE 12.05.2005 CHSVOTH 4.18-6 Bay interlocking

S Device interlocking

Standard interlocking , low voltage side is included in the interlock.

S Interlocking against switching of the disconnector and earthing switches under load

The interlock prevents switching of the disconnector and earthing switches, as long as the appropriate circuit breaker is closed.

S Intermediate position interlock of the circuit breaker

The circuit breaker can only be switched on at a defined ON or OFF position of the disconnector

S Hand crank interlock

When the hand crank is inserted in, the corresponding switching device, all control is blocked. This message is transmitted via the station bus, including time stamp.

S End position interlocking

When a switching device is locked, the corresponding switching device con-trol is blocked.

Station wide locking

S Interlock against coupler, sectionalizer and bus bar earthing switch via trans-mission of the corresponding signals via the station bus.

Time synchronisation

All connected REF542plus can be synchronised via the station bus.

Self supervision

The REF542PLUS checks its hardware components and program execution automati-cally. The bus connections (if available) are also checked continuously.

Fuse protection for the electrical circuits

For reasons of selectivity, there are several electrical circuits in the bay cubicle:

AC:

S Cubicle heating and lighting DC:

S Circuit breaker control and protection trip circuit #1 S Protection trip circuit #2

S REF542plus

S Disconnector and earthing switch control S Disconnector and earthing switch motors S Motor-hydraulic pump

S Interlocking

S Position indications S Indications / Alarms

1HDG 518 412 D en 10.05.2005 EXTMEWE 12.05.2005 CHSVOTH 4.18-7 Cubicle lighting

A bulb is switched on via a door contact switch. Since integrated cubicles are used a shock-proof design is selected because of the switch impact of the circuit breaker.

Cubicle heating (option)

The cubicle heating is switched on automatically by a regulator depending on humidity and temperature.

Antipumping control of circuit breaker

Pump prevention stops the uncontrolled switching (pumping) of the circuit breaker when there is a continuous ON impulse and a simultaneously applied OFF impulse.

A single switching operation (ON / OFF) is permitted. With an applied OFF impulse, it is possible to switch on manually.

OFF blocking of the circuit breaker

The OFF blocking occurs if the drive energy for a trip,or if the SF6 gas density in the C.B. housing is too low.

ON blocking of the circuit breaker

The ON blocking occurs if the drive energy for a Close/Trip sequence or the SF6 gas density in the C.B. gas compartment is too low.

Control and supervision of the hydraulic pump S Control:

The hydraulic pump is activated under the following conditions:

 When the circuit breaker is switched on:

S Spring travel switch contact ‘Motor ON’ closed

 When the circuit breaker is switched off:

S Spring travel switch contact ‘CO blocking’ closed

In this way, varying energy reserves are stored in the operating mechanism depending on the switch status. A circuit breaker OCO cycle is therefore al-ways possible in the ON status, while in OFF status the energy reserve ranges from OCO (newly recharged) to CO cycles.

This ensures that the hydraulic pump does not start up as soon as the circuit breaker is switched off, which is particularly important for the battery layout of an installation, especially when the bus bar protection causes several C.B.

trips.

The control starts up the hydraulic pump after switching on the circuit

breaker. Within approx. 10 seconds, the energy required for an OCO cycle is available again.

This results in staggered start-up times for the hydraulic pump motors. A time relay limits the pump running time in the case of an error.

1HDG 518 412 D en 10.05.2005 EXTMEWE 12.05.2005 CHSVOTH 4.18-8

4.18.2.2 Options

The following optional functions can be added on request:

Measured Values

S Power

 Active power

The respective values are calculated from the electrical current and voltage in the REF542plus, shown on the display and can be transmitted via the station bus.

 Reactive power

The respective values are calculated from the electrical current and volt-age in the REF542plus, shown on the display and can be transmitted via the station bus.

 Apparent power

The respective values are calculated from the electrical current and volt-age in the REF542plus and can be transmitted via the station bus.

S cos phi

The appropriate values are measured and can be transmitted via the station bus.

Indications

S Indications from protection system

 External protection system:

When using the REF542plus together with a protection system from an external supplier, signals can be integrated via BI and transmitted to the station control system via the station bus.

 Protection system with station bus connection:

The messages are transmitted from the protection device to the super-ordinate control system via the station bus.

In this case, the disturbance recordings can be transmitted via the sta-tions bus as well.

S Indications from transformer

The appropriate signals can be connected to the REF542plus using BI and transmitted via the station bus.

Station control interface (e.g. for MicroSCADA) / remote control system By using a plug-in board, the REF542plus can be connected to a bus system (e.g. ABB LON Bus).

It is possible to use this to connect a station control system (e.g. ABB MicroSCADA) or a remote control system.

This bus can be used in the monitoring direction to transmit the position indications of the switchgear and the measured values.

In control direction, commands for the remote control of the bay can be received by REF542plus.

1HDG 518 412 D en 10.05.2005 EXTMEWE 12.05.2005 CHSVOTH 4.18-9

In document 132kv GIS (Page 163-171)

Related documents