Basic Procedure

In document ABB Trf. Protection (Page 66-74)

The procedure for changing settings is basically the same for all the settings. Follow these steps to change settings:

1. From the ECP Main Menu, select “Change Settings”.

2. From the Change Settings menu, select the settings you want to change.

3. A Load Screen appears, prompting you to load the data. Choose one of the following:

• Get Data from TPU2000

• Get Data from Disk

4. The screen for the selected settings appears. Scroll to the function you want and press ENTER.

5. A window appears with either the possible options or a prompt to change the settings by using the arrow keys.

6. Press Enter to accept the new setting or press ESC to close the window without any changes.

7. Select “Return to Menu”.

8. Save your changes.

a. Press ESC.

b. At the window prompting you to save, highlight the option by using the arrow keys and press ENTER.

Function Setting Range Step Size 87T Curve Selection Disable, % slope, HU 30% or HU 35%, 15%

tap, 25% tap, or 40% tap Minimum Operate

Current

0.2 to 1.0 per unit operate current, which is the difference between Winding 1 and 2

0.1

Percent Slope 15 to 60% 5

Restraint Mode Disable, 2nd, 2nd and 5th, or all harmonics Percent Harmonic

Restraint

2nd: 7.5 to 25% of fundamental 5th and All: 15 to 40% of fundamental

2.5%

87H Pickup Setting 6 to 20 per unit operate current 0.1

87T-1 Winding 1 Tap 2 to 9 A or 0.4 to 1.8 A 0.1

51P-1 Curve Selection See Table 1-1

Pickup Amps 1 to 12 A or 0.2 to 2.4 A 0.1 or 0.02 Time Dial/Delay See Table 1-1

OA-1 Current Rating 1 to 12 A or 0.2 to 2.4 A 0.1 or 0.02 50P-1 Curve Selection See Table 1-2

Pickup X 51P 0.5 to 20 times 51P pickup setting 0.1 Time Dial/Delay See Table 1-2

150P-1 Selection Disable or Enable

Pickup X 51P-1 0.5 to 20 times 51P-1 pickup setting 0.1

Time Delay 0 to 9.99 seconds 0.01

46–1 Curve Selection See Table 1-1

Pickup Amps 1 to 12 A or 0.2 to 2.4 A 0.1 or 0.02 Time Dial/Delay See Table 1-1

51N-1 Curve Selection See Table 1-1

Pickup Amps 1 to 12 A or 0.2 to 2.4 A 0.1 or 0.02 Time Dial/Delay See Table 1-1

50N-1 Curve Selection See Table 1-2

Pickup X 51N-1 0.5 to 20 times 51N-1 pickup setting 0.1 Time Dial/Delay See Table 1-2

150 N-1 Selection Disable or Enable

Pickup X 51N-1 0.5 to 20 times 51N-1 pickup setting 0.1

Time Dial/Delay 0 to 9.99 seconds 0.01

Factory Default

Table 5-1. Primary, Alternate 1 and Alternate 2 Settings (Password Protected)

Interfacing with Relay 5-7

Table 5-1. Primary, Alternate 1 and Alternate 2 Settings (Password Protected) (Continued)

Function Setting Range Step Size

OA-2 Current Rating 0.1 or 0.02

50P-2 Curve Selection

Pickup X 51P-2 0.1

Time Dial/Delay

150P-2 Selection

Pickup X 51P-2 0.1

Time Delay 0.01

46–2 Curve Selection

Pickup Amps 0.1 or 0.02

Time Dial/Delay 51G-2 (2w)

51N-2 (3w)

Curve Selection

Pickup Amps 0.1 or 0.02

Time Dial/Delay 50G-2 (2w)

50N-2 (3w)

Curve Selection

Pickup X 51N-2 0.1

Time Dial/Delay 150G-2 (2w)

150N-2 (3w)

Selection

Pickup X 51N-2 0.1

Time Dial/Delay 0.01

87T-2 Winding 2 Tap

51P-2 Curve Selection

0.5 to 20 times 51P-2 pickup setting See Table 1-2

Disable or Enable

0.5 to 20 times 51P-2 pickup setting 0 to 9.99 seconds

See Table 1-1

0.5 to 20 times 51N-2 pickup setting See Table 1-2

Disable or Enable

0.5 to 20 times 51N-2 pickup setting 0 to 9.99 seconds

0.5 to 5.0 times 51P-2 pickup setting 2 to 9 A or 0.4 to 1.8 A

See Table 1-1

1 to 12 A or 0.2 to 2.4 A See Table 1-1

0.5 to 20 times 51P-2 pickup setting

Ext. Inv.

5.0 6.0 (1.2)

6.0 (1.2) 0.1 or 0.02

* Not used when default values are present

is set to disable) (If 51P-2

( ) = Tap range (.2 to 2.4)

Table 5-1. Primary, Alternate 1 and Alternate 2 Settings (Password Protected) (Continued) The following functions are available in the 3 Winding Relay only:

( ) = Tap range (.2 to 2.4)

Disable, 0.1 Disable

Pickup X 51P-3

LDA–3 0.5 to 20 times 51P-3 pickup setting

Function Setting Range Step Size

OA-3

Pickup X 51P-3 0.5 to 20 times 51P-3 pickup setting 0.1 3.0 See Table 1-2

150P-3 Selection Disable or Enable Disable

3.0*

Pickup X 51P-3 0.5 to 20 times 51P-3 pickup setting 0.1

0.1*

Time Delay 0 to 9.99 seconds 0.01

46–3 Curve Selection See Table 1-1 Disable

Pickup Amps 1 to 12 A or 0.2 to 2.4 A 0.1 or 0.02 6.0 (1.2)*

Time Dial/Delay See Table 1-1 5.0*

51N-3 Curve Selection See Table 1-1 Ext. Inv.

Pickup Amps 1 to 12 A or 0.2 to 2.4 A 0.1 or 0.02 6.0 (1.2)

Time Dial/Delay See Table 1-1 5.0

50N-3 Curve Selection See Table 1-2 Standard

Pickup X 51N-3 0.5 to 20 times 51N-3 pickup setting 0.1 3.0 See Table 1-2

150N-3 Selection Disable or Enable Disable

Pickup X 51N-3 0.5 to 20 times 51N-3 pickup setting 0.1 3.0*

0.1*

Time Dial/Delay 0 to 9.99 seconds 0.01

0.1 3.0

Pickup X 51P-3

Disturbance 3 0.5 to 5.0 times 51P-3 pickup setting

Curve Selection See Table 1-1 Ext. Inv.

Time Dial/Delay See Table 1-1 5.0

87T-3 Winding 3 Tap 2 to 9 A or 0.4 to 1.8 A 6.0 (1.2)

Pickup Amps 1 to 12 A or 0.2 to 2.4 A 0.1 or 0.02 6.0 (1.2)

* Not used when default values are present (If 51P-3

is set to disable)

51G Curve Selection See table 1-1 Pickup Amps 1 to 12 or 0.2 to 2.4 Time Dial/Delay See table 1-1

50G Selection Disable or Enable

Pickup 0.5 to 20 times 51G pickup setting Time Dial/Delay See table 1-2

150G Curve Selection Disable or Enable

Pickup 0.5 to 20 times 51G pickup setting Time Dial/Delay 0 to 9.99 seconds

Standard

Interfacing with Relay 5-9

Table 5-2. Two Winding Configuration Settings (Password Protected)

Setting Range Factory Default

Winding 1 Phase CT Ratio 1 to 2000 100

Winding 1 Neutral CT Ratio 1 to 2000 100

Winding 2 Phase CT Ratio 1 to 2000 100

Winding 2 Ground CT Ratio 1 to 2000 100

Winding 1 CT Configuration Wye, Delta(Ia-Ic), or

Delta (Ia-Ib) Wye

Winding 2 CT Configuration Wye, Delta(Ia-Ic), or Delta (Ia-Ib)

Transformer Configuration Wye1-Wye2, Wye1-Delta2,

Delta1-Wye2, Delta1, Delta2 Delta1-Wye2

Phase Compensation 0° to 330° 30°

Phase Rotation ABC or ACB ABC

Alternate 1 Settings Enable or Disable Enable

Alternate 2 Settings Enable or Disable Enable

Cross Blocking Mode Enable or Disable Disable

Trip Failure Mode Diff Trip, OC Trip, Diff and

OC Trip Diff and OC

Trip Failure Time 5 to 60 cycles 60

Trip Failure Dropout 5 to 90% of 51P-1 and 51P-2 5

Target Display Mode Last or All Faults Last

Meter Winding Mode Winding 1 or 2 Wdg 1

Overcurrent Protection Mode Fundamental or RMS Fund.

Overcurrent Reset Mode (51/46) Inst. (2 cycles) or Delayed Instantaneous Remote Edit (local HMI only) Enable or Disable Enable Local Edit (comm. ports only) Enable or Disable Enable

Unit (Relay) Identification 15 alphanumeric characters TPU2000R Demand Meter Time Constant 5, 15, 30, or 60 minutes 15

LCD Contrast Adjustment 0 to 63 16

VT Ratio VT Connection

1 to 2000 100

69V Wye, 120V Delta,

120V Wye, 280V Delta 120 Wye

Wye

Watt Hour Display Kwhr, Mwhr Kwhr

LCD Light Off, On On

Volt Display V ,In VII VIn

Change Test Password? Y or N Y

Table 5-3. Three Winding Configuration Settings (Password Protected)

Setting Range Factory Default

Winding 1 Phase CT Ratio 1 to 2000 100

Winding 2 Phase CT Ratio 1 to 2000 100

Winding 3 Phase CT Ratio 1 to 2000 100

Ground CT Ratio 1 to 2000 100

Winding 1 CT Configuration Wye Wye

Winding 2 CT Configuration Wye

Transformer Configuration Wye1-Wye2-Delta3

Wye1-Delta2-Delta3

Delta1-Wye2-Wye3

Phase Compensation 1-2 0° to 330° 30°

Phase Rotation ABC or ACB ABC

Alternate 1 Settings Enable or Disable Enable

Alternate 2 Settings Enable or Disable Enable

Cross Blocking Mode Enable or Disable Disable

Trip Failure Mode Diff Trip, OC Trip, Diff and

OC Trip Diff and OC

Trip Failure Time 5 to 60 cycles 60

Trip Failure Dropout 5 to 90% of 51P-1 and 51P-2 5

Target Display Mode Last or All Faults Last

Meter Winding Mode Winding 1, 2 or 3 Wdg 1

Overcurrent Protection Mode Fundamental or RMS Fund.

Overcurrent Reset Mode (51/46) Inst. (2 cycles) or Delayed Instantaneous Remote Edit (local HMI only) Enable or Disable Enable Local Edit (comm. ports only) Enable or Disable Enable

Unit (Relay) Identification 15 alphanumeric characters TPU2000R Demand Meter Time Constant 5, 15, 30, or 60 minutes 15

LCD Contrast Adjustment 0 to 63 16

VT Ratio VT Connection

1 to 2000 100

69V Wye, 120V Delta,

120V Wye, 280V Delta 120 Wye

Wye

Watt Hour Display Kwhr, Mwhr Kwhr

LCD Light Off, On On

Volt Display V ,In VII VIn

Change Test Password? Y or N Y

Winding 3 CT Configuration Wye Wye

Wye1-Delta2-Wye3

Delta1-Wye2-Delta3 Delta1-Wye2-Wye3 Delta1-Delta2-Wye3

Phase Compensation 1-3 0° to 300° 30°

Delta1-Delta2-Delta3 Wye1-Wye2-Wye3

Interfacing with Relay 5-11

Duplicate table for Winding 3 exists for the 3 Winding TPU2000R

The Through Faults Counter, the Overcurrent Trip Counter and the Differential Trip Counters will be reset to zero (0) when the “CRI” (counter reset initiate) programmable input is asserted.

Summation Counters can only be reset to zero (0) via the Counter Settings Menu in ECP or the MMI. See Table 5-4.

Calculate Tap Settings (See Section 7 for details) Table 5-4. Counter Settings (Password Protected)

Setting Range Factory Default

Through Faults Counter 0 to 9999 0

Through Fault kAmp Summation Phase A Winding 2 0 to 9999 kA 0 Through Fault kAmp Summation Phase B Winding 2 0 to 9999 kA 0 Through Fault kAmp Summation Phase C Winding 2 0 to 9999 kA 0 Through Fault Cycle (Duration) Summation 0 to 99990 cycle 0

Overcurrent Trip Counter 0 to 9999 0

Differential Trip Counter 0 to 9999 0

Table 5-5. Alarm Settings (Password Protected)

#Denotes 3 Winding Relay only

*Logical output asserts after condition is satisfied and a 60 second time delay

Setting Range Factory Default

Winding 2 Through Fault kAmp Summation Alarm (TFCA) Through Faults Counter Alarm (TFCA)

Through Fault Cycle (Duration) Summation (TFSCA) Overcurrent Trip Counter Alarm (OCTC)

Differential Trip Counter Alarm (DTC)

*Phase Demand Current Alarm (PDA)

*Neutral Demand Current Alarm (NDA)

*Load Current Alarm (LOAD A)

*3 Phase KVAR Demand (Var DA)

*Low Power Factor (LPFA)

*High Power Factor (HPFA)

*Positive KVAR (PVArA)

*Negative KVAR (NVArA)

Positive Kilowatts Winding 1 (Watt 1) Positive Kilowatts Winding 2 (Watt 2)

0 to 9999 1 to 9999 kA

0 to 99990 cycle 0 to 9999 Positive Kilowatts Winding 3 (Watt 3)

# Disable

Winding 3 Through Fault kAmp Summation Alarm (TFKA-3) 1 to 9999 kA

Table 5-6. Communications Settings (Password Protected)

* Check catalog number for available communications port options.

Setting Range Factory Default

FP232 Baud (Front Port) 300, 1200, 2400, 4800, 9600 9600

FP232 Frame N,8,1 or N,8,2 N,8,1

RP232 Baud (Rear Port)* 300, 1200, 2400, 4800, 9600, 19200 9600 RP232 Frame N,8,1; E,8,1; ODD,8,1; N,8,2; E,7,1; ODD,7,1; N,7,2 N,8,1 RP485 Baud (Rear Port)* 300, 1200, 2400, 4800, 9600, 19200 9600 RP485 Frame N,8,1; E,8,1; ODD,8,1; N,8,2; E,7,1; ODD,7,1; N,7,2 N,8,1

INCOM (Rear Port)* 1200, 9600 9600

Unit Address 3 hexadecimal characters (0-9 & A-F) 001

IRIG-B Input Disable or Enable Disable

All of the alarms listed in Table 5-5 can be reset via the Target/Alarm Reset by pushing “C” on the MMI twice or by the Miscellaneous Command Menu in ECP.

Warning: If the counter exceeds the threshold setting and the alarms are reset, the alarms exceeding the threshold setting will be reactivated at the time of the next fault.

The Phase Demand Alarm (PDA) and the Neutral Demand Alarm (NDA) will reset when current drops to 98% of threshold setting.

Miscellaneous Settings (Password Protected)

Under the Miscellaneous Settings Menu, you will find the following:

Communications Configurable Settings – For use with Modbus/Modbus Plus™ Communications. Contact factory for details

Security Mask for Writable 4XXXX Control – For use with Modbus/Modbus Plus™ Communications. Contact factory for details.

User Display Message – For use with User Definable Interface (UDI) Programmable Input. The user can type a 4 line message here. When UDI is asserted, this message will blink on the MMI.

Programmable Inputs/Programmable Outputs – See Section 6 Global Register Mapping/ Register Configuration

For use with Modbus/Modbus Plus™ Communications. Contact factory for details.

User Logical Output Names

The user has the ability to change the names of “ULO1” through “ULO9”. See Section 6 for details on how to use the User Logical Outputs.

ULI/ULO Configuration

This allows the user to connect or disconnect ULIs from corresponding ULOs. The default is all ULIs connected to ULOs. See Section 6 for details on ULIs.

FLI Index and User Names

Programmable Inputs and Outputs 6-1