• No results found

For CDLb with 30 l receiver module without pump

Order no.

1-year service kit for Legio Zon®CDL5 1042829

3-year service kit for Legio Zon®CDL5 1042831

1-year service kit for Legio Zon®CDL10 1042830 3-year service kit for Legio Zon®CDL10 1042832

Type Order no.

Annual maintenance kit CDLb 06, CDLb 12 1044484

Annual maintenance kit CDLb 22 1044501

Annual maintenance kit CDLb 55 1044509

3-yearly maintenance kit CDLb 06, CDLb 12 1044494

3-yearly maintenance kit CDLb 22 1044502

3-yearly maintenance kit CDLb 55 1044510

Type Order no.

Annual maintenance kit CDLb 06, CDLb 12 1044495

Annual maintenance kit CDLb 22 1044503

Annual maintenance kit CDLb 55 1044511

3-yearly maintenance kit CDLb 06, CDLb 12 1044496

3-yearly maintenance kit CDLb 22 1044504

3-yearly maintenance kit CDLb 55 1044512

Type Order no.

Annual maintenance kit CDLb 06, CDLb 12 1044497

Annual maintenance kit CDLb 22 1044505

Annual maintenance kit CDLb 55 1044513

3-yearly maintenance kit CDLb 06, CDLb 12 1044498

3-yearly maintenance kit CDLb 22 1044506

3-yearly maintenance kit CDLb 55 1044514

Type Order no.

Annual maintenance kit CDLb 06, CDLb 12 1044499

Annual maintenance kit CDLb 22 1044507

Annual maintenance kit CDLb 55 1044515

Annual maintenance kit CDLb 120 1044517

3-yearly maintenance kit CDLb 06, CDLb 12 1044500

3-yearly maintenance kit CDLb 22 1044508

1.1.2013 Product Catalogue 2013 3-9

3 Bello Zon ® Chlorine Dioxide Plants

3

Connection-ready, Bello Zon® CDVc chlorine dioxide systems are used in the production, metering and monitoring of 20 to 2,000 g/h of chlorine dioxide made from dilute base chemicals. A completely newly developed reactor concept ensures the innovative production and metering of chlorine dioxide. PVDF is used for the first time instead of the PVC used hitherto in the industry. This results in improved operating safety and higher purity of the generated chlorine dioxide. The stroke lengths of the latest generation of ProMinent® metering pumps are continuously monitored. Impermissible operating statuses arising from incorrect pump stroke length adjustments can thus be ruled out.

The central system control manages the precise production of chlorine dioxide. DULCOTEST® chlorine dioxide, chlorite, pH or ORP sensors can be directly connected via the twin mA inputs. The chlorine dioxide in the treated water, as well as its main by-product chlorite, can thus be monitored and documented online.

The chlorine dioxide concentrations in the water can be adjusted automatically depending on the measurement using the integrated PID controller. All status messages and measured values are documented in the integrated data logger and visualised in the clear colour display via the screen plotter.

The systems meet all the requirements of the DVGW specifications W 224 and W 624 with regard to design and operation and are designed for operation using the pre-diluted chemicals Bello Zon® chlorite (7.5 % NaClO2) and acid (9 % HCl).

Advantages

쮿 Efficient operation, thanks to production, metering, and monitoring of ClO2 using just one system 쮿 Maximum operating safety and purity of the CIO2 produced by the use of PVDF reactors 쮿 Highest operating safety, thanks to stroke length-monitored pumps

쮿 Perfect quality management, thanks to integrated storage of all operating parameters and measured values

쮿 Automatic monitoring of operating parameters and maintenance dates 쮿 Easy and safe operation thanks to clearly laid-out menu navigation in plain text Features

쮿 Capacity range: 20-2,000 g/h ClO2 쮿 PVDF reactor

쮿 Stroke length monitoring for metering pumps

쮿 Control with large colour display, integrated data logger and screen plotter 쮿 Measurement, documentation, and visualisation of ClO2 and chlorite or ORP

Technical Data

3.5 Bello Zon

®

Chlorine Dioxide Plants Type CDVc

P_PMA_BEZ_0009_SW CDVc 20-120 (figure shows optional configuration)

CDVc 2000 100–2,000 468.0 5 15–40 DN 10 1,900 x 1,400 x 370 120 4.1 3.2

* The metering figures relate to 5 bar back pressure and an ambient temperature of 20 °C. The minimum capacity/per hour is based on the fact that when the system is operating at below 5 % of the nominal power, continuous metering is no longer possible because of the correspondingly low pumping frequency of the metering pumps. When systems are not operating continuously, the reactor contents should be changed at least twice daily. The system should not, therefore, be operated below the stated minimum capacity/day.

** at 35 °C ambient temperature

*** without bypass pump, flushing valve and water supply line

**** 230 V values with bypass pump, 115 V values without bypass pump

3 Bello Zon ® Chlorine Dioxide Plants

3

3.5.1 Identcode Ordering System for CDVc Plants

CDVc System type, metering output ClO2 02 CDVc 20= 20 g/h 04 CDVc 45= 45 g/h 06 CDVc 120= 120 g/h 08 CDVc 240= 240 g/h 10 CDVc 600= 600 g/h 14 CDVc 2000= 2,000 g/h

TypeP ProMaqua Power supply

U 100-230 V ± 10 %, 50/60 Hz A 230 V ± 10 %, 50/60 Hz

B 100-115 V ± 10 %, 50/60 Hz (not available for version with „bypass“ 04 or 06) Bypass version

02 Bypass PVC-U with float flow meter

04 Bypass PVC-U with float flow meter and bypass pump (not CDVc 2000) Calibrating device

0 Without calibration device, but with measuring cylinder 1 With calibration device

Suction lance, suction fitting, chemicals

0 none

1 Suction lance for 5-60 l container (only CDV 20-600) 2 Suction lance for 200 l container (only CDV 20-600)

3 Flexible suction fitting up to 5m with two-phase level switch (only CDV 20-600 g/h)

4 Suction lance for 25 l tank with 2 drip pans 40 l without leakage sensor (only CDV 20-600 g/h) Mechanical design

1 With measuring and control properties (only in connection with version inputs and outputs 1 or 3)

2 With measuring and control properties, data logger and screen recorder (only in connection with version inputs and outputs 1 or 3)

Extended in- and outputs

0 none

1 2 analogue inputs, freely configurable for controller output and flow rate 2 1 analogue output, freely configurable

3 2 analogue inputs and 1 analogue output, freely configurable Communication interfaces

1.1.2013 Product Catalogue 2013 3-11

3 Bello Zon ® Chlorine Dioxide Plants

3

3.5.2 Spare Parts Kits for Bello Zon

®

Chlorine Dioxide Plants Type CDV

The spare parts kits include all parts subject to wear, which need to be replaced in the course of regular maintenance.