CNG-HP-32Parameter: Flow

Parameter: Drawing

CNG-HP-32Parameter: Flow

CNG PLANT TAMBAK LOROK Page 38 of 53 HAZOP Node N10

PT ENVIROMATE TECHNOLOGY INDONESIA Appendix B - HAZOP Review Worksheet PT. ISTANA KARANG LAUT

No. Guide Words

Deviation Causes / Concerns Consequences Safeguards Iniating L S L R Comments / Recommendations Action Party Rec. No.

Double-valve provided at drain line of the individual equipments

10.4.1 Reverse Reverse Flow No additional significant issues of concerns identified

10.5.1 Part of Misdirected Flow No additional significant issues of concerns identified

10.6.1 Less Less Level Sump Pump P-400 fails to stop due to LT-1001 failure to function

Loss of liquid level leading to Sump Pump P-400 damage due to cavitation

Pump will be stopped during no signal (FC)

S (-) C(1)

1 S (-) C(L1)

10.7.1 More More Level Pump stopped due to no power supply or pump damage

Overfilling of Sump Tank V-400 and liquid release from vent to environment

LAH 1001 as high level alarm to alert operator

S (-) C(1)

1 S (-) C(L1)

SOP - draining activity is attended by operator Standby portable pump will be provided and connected to available spare nozzle

10.8.1 Less Less Pressure No additional significant issues of concerns identified

10.9.1 More More Pressure Refer to More flow

10.9.2 More More Pressure Blockage of flame arrestor at vent line

Potential

overpressurization of V-400

Bug screen provided

10.10.1 Less Less Temperature No additional significant issues of concerns identified

10.11.1 More More Temperature

No additional significant issues of concerns identified

10.12.1 As Well As Contamination No additional significant issues of concerns identified

10.13.1 Other Than

Composition No additional significant issues of concerns identified

10.14.1 Other Than

Corrosion / Erosion

No additional significant issues of concerns identified

10.15.1 Other Than

Instrumentation No additional significant issues of concerns identified

Parameter: Composition

Parameter: Corrosion / Erosion

Parameter: Instrumentation Parameter: Level

Parameter: Pressure

Parameter: Temperature

Parameter: Contamination

CNG PLANT TAMBAK LOROK Page 39 of 53 HAZOP Node N10

PT ENVIROMATE TECHNOLOGY INDONESIA Appendix B - HAZOP Review Worksheet PT. ISTANA KARANG LAUT

No. Guide Words

Deviation Causes / Concerns Consequences Safeguards Iniating L S L R Comments / Recommendations Action Party Rec. No.

10.16.1 Other Than

Relief No additional significant issues of concerns identified

10.17.1 Other Than

Occupational Safety

No additional significant issues of concerns identified

10.18.1 Other Than

External Factors No additional significant issues of concerns identified

10.19.1 Other Than

Operations No additional significant issues of concerns identified

10.20.1 Other Than

Maintenance No additional significant issues of concerns identified

10.21.1 Other Than

Drawing Parameter: Operation & Maintenance

Parameter: Drawing Parameter: Relief

Parameter: Safety

Parameter: External Factor

CNG PLANT TAMBAK LOROK Page 40 of 53 HAZOP Node N10

PT ENVIROMATE TECHNOLOGY INDONESIA Appendix B - HAZOP Review Worksheet PT. ISTANA KARANG LAUT

Node Abbreviations SOP Standard Operating Procedures

Review date IM Inspection & Maintenance

Client PM Preventative Maintenance

Project USD Unit Shutdown

Facility PSD Process Shutdown

Section ESD Emergency Shutdown

H,M,L

Co Consequence

Pr Probability

Ri Risk

S Safety Risk

C Commercial Risk

Comment Design Intent Design

Conditions: Capacity : 1.5 m3

Opt.

Conditions

Drawing Drawing No. TS78-P-PID-009 Rev:

No. Guide Words

Deviation Causes / Concerns Consequences Safeguards Iniating L S L R Comments / Recommendations Action Party

11.1.1 No No Flow 3" Manual valves at

incoming/outgoing line Fuel Gas filter is inadvertently closed

Loss of fuel gas supply leading to compressor shutdown

PT-0902 as low pressure alarm to alert operator

S (-) C(4)

1 S (-)

C(M4) Provide lock open (LO) for 3"

manual valves at upstream and downstream Fuel Gas Filter 11.1.2 No No Flow PCV-0901A/B stuck closed Loss of fuel gas supply

leading to compressor shutdown

PT-0902 as low pressure alarm to alert operator

S (-) C(4)

1 S (-) C(M4) Standby PCV available

11.2.1 Less Less Flow Pump N4 stop due to failure Less of fuel gas supply leading to compressor shutdown

PDI 0901A/B to monitor differential pressure

S (-) C(2)

1 S (-) C(L2) Back up fuel gas filter

available

PT-0902 as low pressure alarm to alert operator

11.3.1 More More Flow PCV-0901A/B stuck open Potential

overpressurization of downstream equipment

PT-0902 as high pressure alarm to alert operator

S (-) C(1)

1 S (-) C(L1) 11.4.1 Reverse Reverse Flow No additional significant issues of

concerns identified Fuel Gas System

11 17-Jun-13

PT ENVIROMATE TECHNOLOGY INTERNATIONAL Compressed Natural Gas Plant

Tambak Lorok

High, Medium, Risk

To provide fuel to compressor

Pressure : 13.5 barG Temperature: 45 deg C

Pressure : 10 barG Temperature : 21 deg C

PID - Fuel Gas System B

Rec. No.

Parameter: Flow

CNG-HP-33

CNG PLANT TAMBAK LOROK Page 41 of 53 HAZOP Node N11

PT ENVIROMATE TECHNOLOGY INDONESIA Appendix B - HAZOP Review Worksheet PT. ISTANA KARANG LAUT

No. Guide Words

Deviation Causes / Concerns Consequences Safeguards Iniating L S L R Comments / Recommendations Action Party Rec. No.

11.5.1 Less Misdirected Flow No additional significant issues of concerns identified

11.6.1 Less Less Level No additional significant issues of concerns identified

11.7.1 More More Level No additional significant issues of concerns identified

11.8.1 Less Less Pressure Refer to No Flow and Less Flow 11.9.1 More More Pressure Refer to More Flow

11.10.1 Less Less Temperature No additional significant issues of concerns identified

11.11.1 More More Temperature

No additional significant issues of concerns identified

11.12.1 As Well As Contamination No additional significant issues of concerns identified

11.13.1 Other Than

Composition No additional significant issues of concerns identified

11.14.1 Other Than

Corrosion / Erosion

No additional significant issues of concerns identified

11.15.1 Other Than

Instrumentation No additional significant issues of concerns identified

11.16.1 Other Than

Relief No additional significant issues of concerns identified

11.17.1 Other Than

Occupational Safety

No additional significant issues of concerns identified

11.18.1 Other Than

External Factors No additional significant issues of concerns identified

11.19.1 Other Than

Operations No additional significant issues of concerns identified

11.20.1 Other Than

Maintenance No additional significant issues of concerns identified

11.21.1 Other Than

Drawing Parameter: Level

Parameter: Pressure

Parameter: Contamination

Parameter: Corrosion / Erosion

Parameter: Relief

Parameter: External Factor

Parameter: Operation & Maintenance

Parameter: Drawing Parameter: Temperature

Parameter: Composition

Parameter: Instrumentation

Parameter: Safety

CNG PLANT TAMBAK LOROK Page 42 of 53 HAZOP Node N11

PT ENVIROMATE TECHNOLOGY INDONESIA Appendix B - HAZOP Review Worksheet PT. ISTANA KARANG LAUT

Node Abbreviations SOP Standard Operating Procedures

Review date IM Inspection & Maintenance

Client PM Preventative Maintenance

Project USD Unit Shutdown

Facility PSD Process Shutdown

Section ESD Emergency Shutdown

H,M,L

Co Consequence

Pr Probability

Ri Risk

S Safety Risk

C Commercial Risk

Comment Design Intent Design

Conditions: Capacity 183.63 SCFM (each)

Opt.

Conditions Power: 30 kW (each)

Drawing Drawing No. TS78-P-PID-008 Sheet 1 of 2 Rev:

TS78-P-PID-008 Sheet 2 of 2

No. Guide

Words Deviation Causes / Concerns Consequences Safeguards Iniating L S L R Comments / Recommendations Action Party

12.1.1 No No Flow Manual valve upstream of Instrument Air Receiver V-300 inadvertently closed

Loss of instrument air supply potentially leading to PSD

Instrument air supply from Instrument Air Receiver V-300 is provided for 5 minutes in operation

S (-) C(2)

1 S (-) C(L2)

PT-0803 set at 7 barg as low pressure alarm to alert Operator

Potential

overpressurization of upstream piping

NA Confirm availability of high

pressure trip at internal of Air Compressor C300A/B/C package to shut down compressor in the case of block of discharge

12.1.2 No No Flow Any manual valve upstream of Air Dryer Prefilter F300A/B inadvertently closed

Loss of instrument air supply potentially leading to PSD

Instrument air supply from Instrument Air Receiver V-300 is provided for 5 minutes in operation

S (-)

PT ENVIROMATE TECHNOLOGY INTERNATIONAL Compressed Natural Gas Plant

Tambak Lorok

Pressure : 12 barG Temperature: 45 deg C

Pressure : 6 - 10 barG Temperature : AMB - 40 deg C

High, Medium, Risk

PID - Instrument Air System Instrument Air System

To provide instrument air for instrumented system

PID - Instrument Air Network

Rec. No.

B B

Parameter: Flow

CNG-HP-34

CNG PLANT TAMBAK LOROK Page 43 of 53 HAZOP Node N12

PT ENVIROMATE TECHNOLOGY INDONESIA Appendix B - HAZOP Review Worksheet PT. ISTANA KARANG LAUT

No. Guide Words

Deviation Causes / Concerns Consequences Safeguards Iniating L S L R Comments / Recommendations Action Party Rec. No.

Potential

overpressurization of upstream piping

PSV 0801 set at 12 barG release air to atmosphere 12.1.3 No No Flow Any manual valve upstream of Air

Dryer D300A/B inadvertently closed

Loss of instrument air supply potentially leading to PSD

Instrument air supply from Instrument Air Receiver V-300 is provided for 5 minutes in operation Potential

overpressurization of upstream piping

PSV 0801 set at 12 barG release air to atmosphere 12.1.4 No No Flow Any manual valve upstream Air

Dryer after filter F301A/B inadvertently closed

Loss of instrument air supply potentially leading to PSD

Instrument air supply from Instrument Air Receiver V-300 is provided for 5 minutes in operation

S (-) C(2)

1 S (-) C(L2)

Potential

overpressurization of upstream piping

PSV 0802 release air to atmosphere

12.1.5 No No Flow Any manual valve downstream Air Dryer after filter F301A/B inadvertently closed

Loss of instrument air supply potentially leading to PSD

Instrument air supply from Instrument Air Receiver V-300 is provided for 5 minutes in operation Potential

overpressurization of upstream piping

PSV 0802 release air to atmosphere 12.1.6 No No Flow Air Compressors package

trip/broken

Loss of instrument air supply potentially leading to PSD

Auto start of standby compressor by PSLL-0803

S (-) C(2)

1 S (-) C(L2) Nitrogen back up at

downstream F-310A/B

12.1.7 No Flow Manual valve downstream

Instrument Air Receiver V-310 inadvertently closed

Loss of instrument air supply potentially leading to PSD

Instrument air supply from Instrument Air Receiver V-310 is provided for 5 minutes in operation

S (-) C(2)

1 S (-) C(L2)

Lock Open (LO) for manual valve downstream Instrument Air Receiver V-310

Potential

overpressurization of upstream piping 12.2.1 Less Less Flow Air Dryer Prefilter F300A/B

blockage

Less of instrument air supply potentially leading to PSD

PDI 0801 to monitor differential pressure

S (-) C(2)

1 S (-) C(L2) Wet instrument air quality

resulting in

instrumentation damage leading to potential shutdown

Dew Point Meter D0801

Spare Air Dryer Prefilter available

CNG-HP-35

CNG PLANT TAMBAK LOROK Page 44 of 53 HAZOP Node N12

PT ENVIROMATE TECHNOLOGY INDONESIA Appendix B - HAZOP Review Worksheet PT. ISTANA KARANG LAUT

No. Guide Words

Deviation Causes / Concerns Consequences Safeguards Iniating L S L R Comments / Recommendations Action Party Rec. No.

12.2.2 Less Less Flow Air Dryer D-200A/B blockage Less of instrument air supply potentially leading to PSD

PDI 0802A/B to monitor differential pressure

S (-) C(2)

1 S (-) C(L2) Wet instrument air

resulting in

instrumentation damage leading to potential shutdown

Dew Point Meter DE 0801

Spare Air Dryer available 12.2.3 Less Less Flow Air Dryer After Filter F301A/B

blockage

Less of instrument air supply potentially leading to PSD

PDI 0802 to monitor differential pressure

S (-) C(2)

1 S (-) C(L2) Wet instrument air quality

resulting in

instrumentation damage leading to potential shutdown

Dew Point Meter D0801

Spare Air Dryer After filter available

12.3.1 More More Flow All Air Compressor running simultaneously - no adverse consequence

12.4.1 Reverse Reverse Flow No additional significant issues of concerns identified

12.5.1 Part of Misdirected Flow 3/4" manual drain valve at V-300 inadvertently close

High pressure air blowby to sump tank V-400

Sump Tank V-400 is open to Less of instrument air

supply potentially leading to PSD

12.6.1 Less Less Level No additional significant issues of concerns identified

12.7.1 More More Level Water condensation in V-300 and lube oil entrainment from compressors

Low quality of instrument air leading to potential instrument damage and shutdown

SOP to monitor LG 0801 S (-)

C(2)

1 S (-) C(L2)

12.8.1 Less Less Pressure see no flow, less flow, misdirected flow 12.9.1 More More Pressure see no flow

12.10.1 Less Less Temperature No additional significant issues of concerns identified

12.11.1 More More Temperature

No additional significant issues of concerns identified

Parameter: Temperature

Parameter: Contamination Parameter: Level

Parameter: Pressure

CNG PLANT TAMBAK LOROK Page 45 of 53 HAZOP Node N12

PT ENVIROMATE TECHNOLOGY INDONESIA Appendix B - HAZOP Review Worksheet PT. ISTANA KARANG LAUT

No. Guide Words

Deviation Causes / Concerns Consequences Safeguards Iniating L S L R Comments / Recommendations Action Party Rec. No.

12.12.1 As Well As

Contamination No additional significant issues of concerns identified

12.13.1 Other Than

Composition No additional significant issues of concerns identified

12.14.1 Other

Than Corrosion /

Erosion No additional significant issues of concerns identified

12.15.1 Other Than

Instrumentation No additional significant issues of concerns identified

12.16.1 Other Than

Relief No additional significant issues of concerns identified

12.17.1 Other Than

Occupational Safety

No additional significant issues of concerns identified

12.18.1 Other Than

External Factors No additional significant issues of concerns identified

12.19.1 Other Than

Operations No additional significant issues of concerns identified

12.20.1 Other Than

Maintenance No additional significant issues of concerns identified

12.21.1 Other Than

Drawing No additional significant issues of concerns identified

12.21.2 Other Than

Drawing No additional significant issues of concerns identified

Parameter: Composition

Parameter: Drawing Parameter: Corrosion / Erosion

Parameter: Instrumentation

Parameter: Relief

Parameter: Safety

Parameter: External Factor

Parameter: Operation & Maintenance

CNG PLANT TAMBAK LOROK Page 46 of 53 HAZOP Node N12

PT ENVIROMATE TECHNOLOGY INDONESIA Appendix B - HAZOP Review Worksheet PT. ISTANA KARANG LAUT

Node Abbreviations SOP Standard Operating Procedures

Review date IM Inspection & Maintenance

Client PM Preventative Maintenance

Project USD Unit Shutdown

Facility PSD Process Shutdown

Section ESD Emergency Shutdown

H,M,L

Co Consequence

Pr Probability

Ri Risk

S Safety Risk

C Commercial Risk

Comment

Drawing Drawing No. TS78-P-PID-013 Rev:

No. Guide Words

Deviation Causes / Concerns Consequences Safeguards Iniating L S L R Comments / Recommendations Action Party

13.1.1 No No Flow Any of manual valve at fire water

ring inadvertently close/stuck close Lack of fire water supply resulting in inadequate water to extinguishing fire

SOP S (3)

C(3) 1 S (M3) C(M3)

13.1.2 No No Flow Existing fire water pump inoperation Fail to supply fire water in case of fire leading to fire escalation

S (3)

C(3) 1 S (M3) C(M3) 13.2.1 Less Less Flow Any of manual valve at fire water

ring partially close Lack of fire water supply resulting in inadequate water to extinguishing fire

SOP S (3)

C(3) 1 S (M3) C(M3)

13.3.1 More More Flow No additional significant issues of concerns identified

13.4.1 Reverse Reverse Flow No additional significant issues of concerns identified

13.5.1 Part of Misdirected Flow No additional significant issues of concerns identified

13.6.1 Less Less Level No additional significant issues of concerns identified

13 17-Jun-13

PT ENVIROMATE TECHNOLOGY INTERNATIONAL Compressed Natural Gas Plant

Tambak Lorok Fire Water System

Fire water is supplied from existing facility

to provide cooling system and extinguish fire from the process plant and building

Pressure : ATM Temperature: 45 deg C

Pressure : ATM Temperature : ambient

High, Medium, Risk

PID - Fire Water System

Rec. No.

B

Parameter: Flow

Parameter: Level

CNG PLANT TAMBAK LOROK Page 47 of 53 HAZOP Node N13

PT ENVIROMATE TECHNOLOGY INDONESIA Appendix B - HAZOP Review Worksheet PT. ISTANA KARANG LAUT

No. Guide Words

Deviation Causes / Concerns Consequences Safeguards Iniating L S L R Comments / Recommendations Action Party Rec. No.

13.7.1 More More Level No additional significant issues of concerns identified

13.8.1 Less Less Pressure see less flow

13.9.1 More More Pressure No additional significant issues of concerns identified

13.10.1 Less Less Temperature No additional significant issues of concerns identified

13.11.1 More More Temperature

No additional significant issues of concerns identified

13.12.1 As Well As Contamination No additional significant issues of concerns identified

13.13.1 Other Than

Composition No additional significant issues of concerns identified

13.14.1 Other

Than Corrosion / Erosion

No additional significant issues of concerns identified

13.15.1 Other

Than Instrumentation No additional significant issues of concerns identified

13.16.1 Other

Than Relief No additional significant issues of concerns identified

13.17.1 Other

Than Occupational Safety

No additional significant issues of concerns identified

13.18.1 Other Than

External Factors No additional significant issues of concerns identified

13.19.1 Other

Than Operations Review existing Tambak Lorok’s fire

water capacity to be adequate for fire water handling in CNG Plant 13.19.2 Other

Than Operations Consider to provide additional flowmeter

to measure fire water consumption for Tambak Lorok

13.20.1 Other

Than Maintenance No additional significant issues of concerns identified

13.21.1 Other

Than Drawing

Parameter: Instrumentation

Parameter: Relief

Parameter: Corrosion / Erosion Parameter: Pressure

Parameter: External Factor

Parameter: Operation & Maintenance

Parameter: Drawing

CNG PLANT TAMBAK LOROK Page 48 of 53 HAZOP Node N13