• No results found

The  output  control  relays  provided  on  each  KT‐100,  KT‐200,  KT‐300,  KT‐400  and  KTES  can  be  used  to activate alarms or other devices such as lighting control, ventilation, and air conditioning. These relays can  be  activated  according  to  schedules,  events  reported  by  the  system.  They  can  also  be  activated  to indicate the status of an alarm system or a combination of different logic conditions.

Defining Relays

1 From the Devices definition tab, select the Relay icon.  2 Select the Gateway, the Site and the Controller from the displayed drop‐down lists, then select the relay for which you want to define settings.  3 Specify the Operating mode for the relay:

• Normal:  the  relay  is  normally  de‐energized  (deactivated)  until  it  is  energized  (activated)  by  an operator, an event or any other system schedule.

• Reverse: the relay is normally energized (activated or resting) until it is de‐energized (deactivated) by an operator, an event or any other system function.

4 Specify  the  Automatic  activation  schedule:  when  this  schedule  is  valid,  the  relay  will  be  triggered (activated or deactivated) according to the specified activation mode.

5 Specify the Disable relay action: when this schedule is valid, the relay will be deactivated (or activated) according to the predefined operating mode. 

6 Set  the  Temporary  activation  timer  to  indicate  the  delay  during  which  the  relay  will  be  temporarily triggered following a temporary activation.

NOTE: When the timer is set to zero, the default activation delay is set to five seconds. Maximum time allowed:  9:06:07  (9  hours,  6  minutes  and  7  seconds).  When  you  are  using  the  KT‐400,  the  maximum time allowed is 18:12:15 (18 hours, 12 minutes and 15 seconds).

7 Select a Graphic and Video view associated with the relay, if applicable. 

Input Configuration

Door controllers can monitor the state of input points such as: door contacts, interlocks, alarm points, motion  detectors,  temperature sensors,  any  REX  and  other  devices  with dry  contacts. KT‐100  monitors the state of 4 input points, KT‐200 monitors the state of 16 input points, and KT‐300 monitors the state of 8 on‐board input points, with a maximum capacity of 16. 

• For KT‐200 only. Inputs are normally closed or normally open dry contacts connected in series with one resistor. If the dry contact is connected in series with the green resistor, the input number will be odd. If the dry contact is connected in series with the red resistor, the input number will be even.

• Inputs  1  (door  contact)  and  2  (request  to  exit  device)  are  ideally  reserved  for  Door  1  of  the  controller whereas Input 9 (door contact) and 10 (request to exit device) are ideally reserved for Door 2 of the same controller. The input that is used for the door contact or REX contact SHOULD NOT have a “monitoring” schedule defined in the “Input Definition” menu. • For KT‐100 Controllers. Input 1 is reserved for door contact while input 2 is reserved for a request to exit device. • For KT‐300 Controllers. Input 1 should be reserved for contact on door 1 while input 2 should be used for request to exit device for door 1 of the controller. Input 3 should be reserved for contact on door 2 while input 4 should be used for request to exit device for door 2 of the controller. • For KT‐400 Controllers. Input 1 should be reserved for contact on door 1 while input 2 should be used for request to exit device for door 1 (REX Door #1) of the controller. Input 5 should be reserved for contact on  door  2  while input 6  should be  used  for  request  to  exit  device for door  2 of the controller.  Input 9 should  be  reserved  for  contact  on  door  3  while  input  10  should  be  used  for  request  to  exit  device  for door 3 of the controller. Input 13 should be reserved for contact on door 4 while input 6 should be used for request to exit device for door 4 of the controller.

Defining Input

You may define inputs from the Input button of the Devices toolbar. You can also define inputs using the Express Setup when defining a controller (see "Express Setup Program" on page 568). 1 From the Devices toolbar, select the Input icon.

2 Select  a  specific  gateway  (from  the  Gateway  drop‐down  list),  a  site  (from  the  Site  drop‐down  list),  a controller (from the Controller drop‐down list).

3 From the Input drop‐down list, select the input you want to define. 

4 Assign  a  Monitoring  schedule  to  the  selected  input:  this  is  the  schedule  during  which  the  system  will supervise the condition of the input. When the schedule is valid, a change in input condition generates either an “Input in alarm” or “Input restore” event. NOTE: The input that is used for the door contact, REX contact or interlock contact SHOULD NOT have a monitoring schedule. 5 Specify the Normal condition for the input: it may be Closed or Opened. NOTE: When using single or double EOL resistors, set input Normal Condition to Closed.

6 Specify the Notify abnormal condition for the input: it may be Alarm or Activate.

NOTE: When  configuring  event  parameters  with  Input  in  alarm  or  Input  activated  as  the  selected event, only the inputs corresponding to these criteria are displayed. See "Event Parameters Definition" on page 423 for more information.

7 By default, EntraPass will not select the Suspend status update when not monitored. This is to keep data traffic at a minimum. However, this option can be enabled if necessary.

8 Specify the Input response time. This delay corresponds to a period within which an input must remain in the  same  state  before  a  transition  is  recognized.  This  delay  is  expressed  in  minutes  (mm:ss:cc).  Values range from 10 secs to 10 min:55 secs:35 cc for both the alarm response and alarm restore times.  • Alarm response time (mm:ss:cc):  The  delay  before  the  system  generates  the  input  and  alarm  event.

Default is 50 cc.

Restore response time (mm:ss:cc):  The  delay  before  the  system  generates  the  input  restore  events (Multi‐site Gateways only). Default is 50 cc.

NOTE: Specifying  the  input  response  time  allows  bouncing  time  when  the  contact  changes  state,  and helps to generate only one event for each transition if this time is longer than the bouncing time. For example, a 01:00:00 delay requires that a condition remains stable for at least one minute before it is reported.

9 Specify the Telephone Entry System options (applies to KTES only).

NOTE: To  access  the  modem  call  type  feature,  the  site  connection  type  must  be  set  to  Modem.  For more  information,  see  "Sites  Configuration"  on  page  61.  The modem call type feature is  supported  by Multi‐site Gateways only.Pager call type: You can select Do not call (the relay activation for that event will not be sent to the pager), Call immediately (the relay activation for that event will be sent immediately to the pager) or Call when scheduled (the relay activation for that event will be sent to the pager according to the pager call schedule). See "If you are assigning or defining schedules, make sure that you are selecting the proper category for this schedule. For example, if you are assigning or defining a system schedule (for  workstation,  operators,  event  parameters,  video  triggers)  this  schedule  will  be  available  for selecting components of this category. If you are selecting a schedule for physical components such as  controllers,  doors,  inputs,  their  schedules  will  be  grouped  by  gateway  if  you  are  using  a  Global Gateway  and  by  site  if  you  are  using  a  Multi‐site  Gateway  by  site  if  you  are  using  a  Multi‐site Gateway.  If  you  have  defined  two  sites  in  your  system,  there  will  be  two  separate  groups  of schedules for each site. You can define up to 99 schedules for each site." on page 186. Default value is Do not call.

• Under modem call type, assign the call type option that best suits event reporting. Default value is Do not call

Input  pager  ID:  Enter  the  pager  code  corresponding  to  the  selected  input.  Possible  values  are  201, 202, 203 and 204.

NOTE: To  specify  pager  call  types  for  each  events,  the  Pager  reporting  function  must  be  enabled.  See "Defining the Pager Options" on page 86

10 For KT‐400 and KTES only, check Override default EOL (56K), and then, in the drop‐down menu, select the appropriate item. Default is unchecked. 11 Select a Graphic and Video view associated with the input, if applicable.

Defining Relays and Inputs

1 Select the Relay and input tab to define which relay(s) or input(s) will be activated or shunted when this input is enabled.

2 From  the  Activate  relay  list,  select  a  relay  or  a  relay  group  that  will  be  triggered  when  this  input  is enabled. 

3 Activate  relay  temporarily  will  activate  the  relay  according  to  the  Temporary  activation  parameters defined in the Relay dialog. Default is unchecked.

4 In the Temporary Shunt Timer (h:mm:ss) field, specify the period during which an input is not monitored. Setting the timer to 0:00:00 will instruct the relay to follow the input state. The maximum value for the Shunt delay (hh:mm:ss) is 18:12:15 when you are using the KT‐400 or the KTES. Default is 0s.

NOTE: For  the  system  to  process  properly  the  reset  delay  on  a  temporary  shunt,  the Temporary Shunt Timer option must be set in the definition of the input that will reset the delay. For example, if Input 1 will  temporary  shunt  Input  2,  the  Temporary  Shunt  Timer  must  be  specified  also  in  the  definition  of Input 2.

5 From  the Shunt  input list,  select  the  input that will not be  monitored  when the input  being  defined is enabled.

6 If  applicable  check  Shunt  input  temporarily  and  Reset  delay  for  shunt  temporarily  options.  Default  is unchecked for both. 7 Delay before unshunt: Values range from 1 sec to 18 h:12min:15 secs. NOTE:  When the input is restored or returns to normal condition, the shunted input will also return to normal condition. The event “Input shunted by input” will be generated by the system. When the input returns to normal condition, the event “Input unshunted by input” will be generated.

Defining Tamper and Trouble

1 Select the Tamper and trouble tab to associate a relay or a group of relays to activate in case of an input in trouble or in tamper. This tab is visible for a zone in DEOL (double end‐of‐line) only. 2 From the Activate relay list (Tamper alarm), select a relay or a relay group that will be triggered when this input is in tamper. 

3 Activate  relay  temporarily  will  activate  the  relay  according  to  the  Temporary  activation  parameters defined in the Relay dialog. Default is unchecked.

4 From the Activate relay list (Input in trouble), select a relay or a relay group that will be triggered when this input is in trouble. 

5 Activate  relay  temporarily  will  activate  the  relay  according  to  the  Temporary  activation  parameters defined in the Relay dialog. Default is unchecked.

Defining an Input for an Elevator Door

Related documents