• No results found

Cycle function parts

In document DVM PLUS3 1 Outdoor Units (Page 36-64)

8-1. RD080/100/120VQXG T

DVI compressor Oil separator

High pressure sensor Low pressure sensor

Accumlator

PWM valve

Ambient air temp. sensor

Liquid service valve Low pressure gas service valve Cond_out temp. sensor

EVI EEV

Liquid bypass valve

Turbo intercooler

FVI compressor

Hot gas bypass valve

High pressure switch Discharge temp. sensor

Oil valve

Sump temp. sensor

Oil service valve

Outdoor units

No Cycle parts Functions

1 DVI compressor Digital Vapor Injection)

DVI compressor coupled with vapor injection controls the capacity 10 to 100% of its ca-pacity.

It enhances cooling and heating performance and COP with using vapor injection.

2 FVI compressor

(Fixed Vapor Injection) FVI compressor coupled with vapor injection is fixed compressor. It enhances cooling, heating performance and COP with using vapor injection.

3 PWM valve |t is used for variation of digital compressor’s capacity. When the valve is open, the DVI compressor keeps the unloading state, otherwise loading state.

4 Discharge temp. sensor It measures the temperature of compressor outlet. The main function of it is to protect compressor from overheating.

5 Oil separator It separates oil and refrigerant discharged from the compressor and returns the oil into compressor again.

6 High pressure switch It protects the system from abnormal high pressure. (Open : 4.1Mpa, Close : 3.5 Mpa) 7 Hot gas bypass valve When the suction pressure becomes abnormal low pressure, it opens.

During the oil balance operation, it makes high pressure for the shell of compressor 8 High pressure sensor The main function of it controls the capacity of compressor in pursuit of target of high

pressure in heating operation by measuring the value of the system.

9 4way valve It enables to change operating mode into cooling and heating mode.

10 Ambient air temp. sensor It measures the temperature of ambient.

11 Cond_out temp. sensor It has application to know subcooling and the complete point of defrost.

12 Main EEV 1, 2 It controls the amount of refrigerant entering outdoor’s heat exchanger in heating operation.

13 Liquid bypass valve When the compressor is overheating, it opens to make discharge temperature low.

14 EVI EEV It enables to secure sufficient subcooling and control the amount of vapor entering into vapor port of compressor.

15 Turbo intercooler Through turbo intercooler, heat is exchanged each other between saturated liquid refrigerant and a little expanded refrigerant.

16 EVI_in temp. sensor

These temperature sensors enable to control EVI EEV’s step to secure superheat.

17 EVI_out temp. sensor

18 Liquid tube temp. sensor It is used to know subcooling.

(Subcooling = The saturated temp. of high pressure - Liquid tube temp.) 19 EVI bypass valve This valve closes during application of vapor injection.

20 Suction temp. sensor This is applied to know superheat in heating mode with the low pressure sensor.

21 Accumulator Ambient air temperature sensor (Tair)

22 Oil valve When oil balance operation happens, this valve opens.

23 Low pressure sensor The main function of it is to control the capacity of compressor in pursuit of target of low pressure in cooling operation by measuring the low pressure.

24 Sump(Base) temp. sensor With checking sump temperature of compressor, it prevents the compressor from liquid back and overheating.

25 Oil temp. sensor While the oil balance is operating, it make a self-diagnosis of the oil valve.

26 Main cooling valve Through this valve, the high pressure gas of refrigerant is discharged into indoor unit which needs heating operation in main cooling operation.

DVM PLUS III

Installation

III. Installation

1 Outdoor unit combinations ...38

2 Space requirements ...39

3 Placing the outdoor units ...43

4 Electric specifications ...44

5 Wiring works...46

6 Refrigerant piping works ...48

7 Option switches & function keys ...54

8 Error codes ...56

1 Outdoor unit combinations

1-1. Basic model

1-2. Compact combinations

Classification Capacity (Ton) Capacity (HP) Model Total capacities of the connectable indoor units (kW)

Maximum number of connectable indoor

units

Single unit

6.4 8 RD080VQXGA 11.2 ~ 29.1 10

8.0 10 RD100VQXGA 14.0 ~ 36.4 10

9.5 12 RD120VQXGA 16.8 ~ 43.6 14

Classification Capacity (Ton) Capacity

(HP) RD080VQXGA RD100VQXGA RD120VQXGA Total capacities of the connectable Indoor

units(kW)

Maximum number of connectable Indoor units

Compact combinations

12.8 16 2 22.4 ~ 58.2 16

14.4 18 1 1 25.2 ~ 65.5 18

16.0 20 2 28.0 ~ 72.8 20

17.5 22 1 1 30.8 ~ 80.0 24

19.0 24 2 33.5 ~ 87.1 28

20.8 26 2 1 36.4 ~ 94.6 30

22.4 28 1 2 39.2 ~ 101.9 32

24.0 30 3 42.0 ~ 109.2 34

25.5 32 2 1 44.8 ~ 116.4 36

27.0 34 1 2 47.5 ~ 123.5 40

28.5 36 3 50.3 ~ 130.7 43

Installation

2-1. Single installation

2-2. Group installation

300 or

more(S2) 300 or more

200 or more 500 or

300 or more

200 or more

400 or Wall height unrestricted

Wall height unrestricted

Front wall height 1500 mm and less

Rear wall height 500 mm and less

Side wall height Height unrestricted

Front : S1 + h1/2, Rear : S2 + h2/2

(Unit: mm)

(Unit: mm)

If the height of the wall exceeds the above value, more space should be added to the front and rear space individually.

2 Space requirements

2-3. Installing duct for horizontal exhaust discharge

It is necessary to install an air-discharge duct (field supply) to direct exhaust from the fan horizontally if it is difficult

to provide a minimum space of 2m between the air-discharge duct outlet and a nearby obstacle.

Installation

excessive wind and snow should be taken to ensure the unit's correct operation. Snow-proof duct (field supply)

should be fitted to the unit and direct exposure to the wind should be avoided as much as possible. When the unit is expected to operate in cooling mode in condition under 10ºC, in snowy areas, in environments subject to strong winds or rain, install air inlet and outlet ducting as shown in the below example

 The frame/foundation should be higher than expected snowfall.

 The foundation must be solid and the unit must be secured with anchor bolts.

 Be sure to install unit in a place strong enough to withstand its weight.

 When installing on a roof subject to strong wind, countermeasures must be taken to prevent the unit form being overturned.

 Any lack of strength may cause unit to fall down, resulting in a personal injury.

 For more detail information about installation, refer to installation manual.

Caution

2 Space requirements

2-5. Dimensional drawing of snow-proof duct

1) RD080/100/120VQXGA

(Unit: mm)

Installation

3-1. Anchor bolts position

3-2. Removing fasteners of compressor’s leg

A

(Unit: mm)

B

Anchor bolt(4-ø15)

67 745

67

(1) Open the front cabinet near the bottom.

The compressors are fastened with nuts at 6 places.

(2) Remove nut washer, washer and stopper nut from compressors with a tool.

(3) Refasten them with the nut washer only.

Stopper Nut Washer Nut Washer

Remove

 Pay your attention not to touch the copper pipes as detaching the fasteners.

Caution

Model A B

RD080/100/120VQXGA 1200 1058

Electric specifications 4

4-1. Basic models

Classification Capacity (Ton) Capacity (HP) Model MCCB(A) ELB

Single unit

6.4 8 RD080VQXGA 25 25A, 30mA 0.1 Second or less

8.0 10 RD100VQXGA 30 30A, 30mA 0.1 Second or less

9.5 12 RD120VQXGA 40 40A, 30mA 0.1 Second or less

Model Units Power supply Comp. OFM

Hz Volts Min. Max. MCA MFA RLA kW FLA

RD080VQXGA 50 380~415 380 415 25 1.1 4.9

RD100VQXGA 50 380~415 380 415 30 1.1 4.9

RD120VQXGA 50 380~415 380 415 40 1.1 4.9

 All wiring, components and materials to be procured on the site must comply with the applicable local and national codes.

Installation

Model Units Power supply Comp. OFM

Hz Volts Min. Max. MCA MFA RLA kW FLA

RD160VQXGA 50 380~415 380 415 50 2.2 9.8

RD180VQXGA 50 380~415 380 415 55 2.2 9.8

RD200VQXGA 50 380~415 380 415 60 2.2 9.8

RD220VQXGA 50 380~415 380 415 70 2.2 9.8

RD240VQXGA 50 380~415 380 415 80 2.2 9.8

RD260VQXGA 50 380~415 380 415 80 3.3 14.7

RD280VQXGA 50 380~415 380 415 85 3.3 14.7

RD300VQXGA 50 380~415 380 415 90 3.3 14.7

RD320VQXGA 50 380~415 380 415 100 3.3 14.7

RD340VQXGA 50 380~415 380 415 110 3.3 14.7

RD360VQXGA 50 380~415 380 415 120 3.3 14.7

 The relationship between the starting time and the starting current (Digital Scroll Comp. + Fixed Scroll Comp)

 RLA is based on the following conditions.

- Indoor temp. : 27˚C DB/ 19˚C WB - Outdoor temp. : 35˚C DB

 Voltage range

Units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits.

 Maximum allowable voltage variation between phases is 2%.

 Select wire size based on the larger value of MCA.

 MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker).

 Abbreviations

- MCA: Min. Circuit Amps. (A) MCA = 1.25 X LOAD1 + LOAD2

(LOAD1: RLA of Digital Comp. / LOAD2: RLA of Fixed Comp. + FLA of Fan Motor) - MFA: Max. Fuse Amps. (A)

Classification Capacity(Ton) Capacity(HP) MCCB(A) ELB

RVXVHT075FE RVXVHT100FE RVXVHT125FE

Module unit

5 Wiring works

5-1. External connection diagram of DVM PLUS III

1) 3 phase 4 wires

R S T N

R S T N

OF1 OF2 OF1 OF2

3 phase 4 wires

(380~415V) 3 phase 4 wires

(380~415V)

Communication cable among outdoor units

220~230V 220~230V

Indoor Outdoor Outdoor

Communication cable between indoor and

Main unit Sub unit

Indoor

Installation

1. Be sure to connect the suitable length of power wiring to the power wiring terminal block using ring terminal above the figures.

2. Make sure to fix wiring using cable tie like above the figures.

3. After wiring, reinstall the housing cover which has an isolator into the middle frame.

Connecting the ring terminal of 3 phase cable (CV) Connecting the ring terminal of 3 phase cable (FCV)

A

 Make sure that all wiring should not contact with piping line during the field wiring work. If not, the vibration of compressor can make a damage to wiring and piping. It may result in fire.

 Make sure to pass electrical wiring of the power cable (3 phase 4 wires) through a conduit hole of the front side.

CAUTION

Base line Middle frame Base line

Housing cover

A B C

30mm 60mm 90mm

A B C

30mm 60mm 90mm

6 Refrigerant piping works

6-1. Notice & Cautions

Cautions Correct piping work Wrong piping work

The refrigerant piping should be the same level or lower than connecting position of piping to outdoor units.

Piping work should be run with side direction for better uniform distribution of refrigerant and oil like next diagram.

Outdoor joint kits should be installed in a horizontal direction, even it is a low pressure pipe.

When the piping length between outdoor and branch joints is 2m or more, a vertical trap has to be installed like right diagram.

Less than 1m 2m or more

2m or more 200~300mm

Horizontal length = over 100mm Minimum 100mm

Installation

Example of piping layouts for DVM PLUS III

Using Y-joint

Using Header

joint

6 Refrigerant piping works

6-3. Piping examples

Classification Branch with Y-joint Branch with Y and Header joint Branch with Header joint

One outdoor unit installed

Multiple outdoor units installed

Items Examples Remarks

Max. (220m below)

Branch with Y-joint a+b+c+d+e+f+g+p ≤ 200m (220m)

Equivalent pipe length Y-joint:0.5m, Header:1m Branch with Y-joint

and Header joint a+i+k ≤ 200m (220m) a+b+h ≤ 200m (220m) Branch with

header joint a+i ≤ 200m (220m)

Total

piping 1000m below

Branch with Y-joint a+b+c+d+e+f+g+p+h+i+j+k+l+m+n≤ 1000 Branch with Y-joint

and Header joint a+b+c+d+e+f+g+p+h+i+j+k

≤ 1000m Branch with

Header joint a+b+c+d+e+f+g+p+h+i ≤ 1000m Outdoor

Indoor unit Piping 15m below H2 ≤ 15m

Outdoor ~

Outdoor unit Piping 5m below H3 ≤ 5m

Allowable

Piping 90m below*1) It needs to satisfy required conditions Only apply DVM PLUS III

Distribution kit Model Remarks

Allowable

From distribution kit to

indoor unit 3m MEV-A13SA / MEV-A16SA (For 1 indoor unit)

For wall-mounted indoor unit From distribution kit to

indoor unit 20m

MXD-A13K116A / MXD-A13K200A / MXD-A16K200A / MXD-A22K200A (For 2 indoor units)

MXD-A13K216A / MXD-A13K300A / MXD-A16K213A / MXD-A16K300A (For 3 indoor units)

Required condition Example

The first branch joint ~ the farthest indoor unit

If the sum of pipe length (b+c+d+e+f+g+p) is over 45m, (but not exceed : 90m) increase pipe size of b,c,d,e,f,g (b,c,d,e,f,g : pipe 1 size up)

Total pipe length

If main pipe size is not increased,

a+bx2+cx2+dx2+ex2+fx2+gx2+h+i+j+k+l+m+n+p≤1000m If main pipe size is not increased,

ax2+bx2+cx2+dx2+ex2+fx2+gx2+h+i+j+k+l+m+n+p≤1000m

*1) Required condition

Installation

Outdoor unit connection pipe size : (A1), (A2), (A3) Branch joint : (D), (E), (F)

Indoor unit’s capacity Pipe size (O.D. mm) Liquid pipe Gas pipe

2.2~5.6 kW ø6.35 ø12.70

Model Capacity of outdoor MXJ-T3819K Below 36 HP A1 : Select the pipes according to the outdoor unit

capacity with following table.

A2 : Select the pipes according to sum of outdoor unit capacities behind the outdoor joint with following table.

A3 : Select the main pipe of outdoor units with the following table.

Pipe size between branch joints : (B)

Pipe size between branch joints and indoor unit (C)

Outdoor multi connection branch joint (D)

Select the pipe size according to the indoor's capacity.

Branch joint of outdoor unit’s multi connection (D)

Model Total indoor unit’ capacity MXJ-YA1509K 15.0 kW and below MXJ-YA2512K Over 15.0~40.6 kW and below MXJ-YA2812K Over 40.6~46.4 kW and below MXJ-YA2815K Over 46.4~69.6 kW and below MXJ-YA3119K Over 69.6~98.6 kW and below MXJ-YA3819K Over 98.6~100.5 kW and below Y-joint

(F)

First branch joint (E)

Select branch joint according to the outdoor unit's capacity

Branch joint (F)

Select the pipe size according to the capacity sum of indoor units which are connected below this pipe.

1) Y-joint

Select the pipe size according to the capacity sum of indoor units which are connected below this pipe.

*A1 : Pipes to the outdoor unit (Liquid, Gas)

*A2 : Pipes between outdoor joint kits (Liquid, Gas)

*A3 : Main pipes (Liquid, Gas) (B) HP Mark Pipe size(O. D. mm)

Liquid Gas 12 HP (A1)

16 HP (A1) 26 HP (A2)

Total Indoor unit’s capacity Pipe size (O. D. mm) Liquid pipe Gas pipe

15.0 kW and below ø15.88 Over 98.6~100.5 kW and below ø38.10

Model Total Indoor The connectable unit’s quantity of capacity indoor units MXJ-HA2512K 46.4 kW

and below 4

2) Header joint Y-joint

(E)

Outdoor unit Model 8, 10, 12HP MXJ-YA2512K

16 HP MXJ-YA2812K

18, 20, 22, 24HP MXJ-YA2815K 26, 28, 30, 32, 34HP MXJ-YA3119K

36HP MXJ-YA3819K

Outdoor unit Pipe size (O.D. mm) Oil balancing pipe size

Liquid Gas

8HP ø9.52 ø19.05

ø6.35

10HP ø22.23

12HP ø12.70 ø25.40

16HP

6 Refrigerant piping works

6-4. Pipe selection

Main pipe 1 size increment

Main pipe

Main pipe : from outdoor unit to the first branch joint

Equivalent pipe length between outdoor unit and the farthest indoor unit

When the equivalent pipe length from outdoor unit to the farthest indoor unit is over than 90m, the main pipe (both liquid and gas pipe) has to be increased with 1 size like below table.

Equivalent length calculation method

Equivalent length = actual pipe length(m) + number of ‘Y-joint' X 0.5(m) + number of 'Header joint' X 1.0(m) + number of elbows X equivalent length of each elbow

Outdoor unit Thickness(mm)

(O. D. mm) Material

ø6.35 0.7

The pipe length between outdoor and the farthest indoor unit

below 90 m 90m and over

Pipe size (O. D. mm) Equivalent length (m)

ø 9.52 0.18

Type Equivalent length (m)

Y joint 0.5

Header joint 1.0

Installation

Total refrigerant amount of the system must be less then 100kg. If total refrigerant amount of system is over 100kg more, the system has to be divided into smaller system, each containing less than 100kg.

Caution

Additional refrigerant charging of

distribution kit (kg/m) Remarks

Regardless of the liquid pipe size, additional refrigerant charging is 0.01kg

per meter after distribution kit. 0.01 For wall-mounted Indoor unit

Liquid pipe size

(O.D.) Additional

refrigerant charging

Basic model Factory charging(kg)

RD080VQXGA 8.5

RD100VQXGA 8.5

RD120VQXGA 8.5

Liquid pipe size (O.D. mm) Ø6.35 Ø9.52 Ø12.70 Ø15.88 Ø19.05

Length (m) 15 25 21 25 5

over than 90m, the main pipe (both liquid and gas pipe) has to be increased with 1 size like below table.

 Example of additional refrigerant charging Pipe length is as below without distribution kit

 Additional refrigerant = 15 x 0.02 + 25 x 0.06 + 21 x 0.125 + 25 x 0.18 + 5 x 0.27 = 10.275 kg

Option switches & function keys 7

7-1. Option switches

0123456789 A BC DEF

Switch Setting Function Remarks

SW01/SW02 Setting total quantity of Installed indoor units Main unit required only

SW01 : The tens digit, SW02 : The units digit

Main unit required only

Ex) As 12 indoor units were installed, SW01:1, SW02: 2

SW03 K5 On Manual address setting

Off Auto address setting

SW04

K9 K10 Target evaporating temperature (°C)

Cooling capacity compensation

On On 7~9

On Off 5~7

Off On 9~11

Off Off 10~12

SW04

K11 K12 Target high pressure (kgf/cm2, psig, kPa)

On On 30.0, 426, 2941

Heating capacity compensation

On Off 31.5, 448, 3089

Off On 33.0, 469, 3236

Off Off 27.0, 384, 2647

SW05

K13 K14 Outdoor unit’s address

On On Outdoor unit’s address : No 1 Main unit

On Off Outdoor unit’s address : No 2 Sub I unit

Off On Outdoor unit’s address : No 3 Sub 2 unit

Off Off Outdoor unit’s address : No 4 Sub 3 unit

K15 K16 Maximum current control

On On Standard Factory default

On Off 90% of standard peak current value Off On 80% of standard peak current value

Off Off Not use

SW06

K17 On Since supplying power, first oil return operation happens after 5hrs and then 7 hrs.

Off Since supplying power, first oil return operation happens after 2hrs and then 2 hrs.

K18 On Standard Defrost period setting

Off Shorten defrost period by 20% approximately

K19 On Standard fan step

Off Fan step compensation (Maximum step) 8/10 HP : 19 Steps, 12HP : 23 Steps

On Normal

Installation

0123678945 A BC

K1 Key function Display LED

Push 1st time Refrigerant charging in heating operation “K” “1” “BLANK” “BLANK”

Push 2nd time Test run in heating mode “K” “2” “BLANK” “BLANK”

Push 3rd time Pump out operation in heating mode (Outdoor unit’s address : NO 1) “K” “3” “BLANK” “1”

Push 4th time Pump out operation in heating mode (Outdoor unit’s address : NO 2) “K” “3” “BLANK” “2”

Push 5th time Pump out operation in heating mode (Outdoor unit’s address : NO 3) “K” “3” “BLANK” “3”

Push 6th time Pump out operation in heating mode (Outdoor unit’s address : NO 4) “K” “3” “BLANK” “4”

Push 7th time Open all valve of outdoor unit for vacuum preparation (Outdoor unit’s address : NO 1) “K” “4” “BLANK” “1”

Push 8th time Open all valve of outdoor unit for vacuum preparation (Outdoor unit’s address : NO 2) “K” “4” “BLANK” “2”

Push 9th time Open all valve of outdoor unit for vacuum preparation (Outdoor unit’s address : NO 3) “K” “4” “BLANK” “3”

Push 10th time Open all valve of outdoor unit for vacuum preparation (Outdoor unit’s address : NO 4) “K” “4” “BLANK” “4”

Push 11th time Open all valve for vacuum preparation (Total outdoor units, indoor unit and MCU units) “K” “4” “BLANK” “4”

Push 12th time Return to normal view mode

-K2 Key function Display LED

Push 1st time Refrigerant charging in cooling operation “K” “5” “BLANK” “BLANK”

Push 2nd time Test run in cooling mode “K” “6” “BLANK” “BLANK”

Push 3rd time Pump down operation in cooling mode (All outdoor units) “K” “7” “BLANK” “BLANK”

Push 4th time Pipe checking (Check whether the pipe connection of MCU correspond with indoor unit’s address in HR system.) “K” “8” “BLANK” “BLANK”

Push 5th time Judgment system of refrigerant amount “K” “9” “BLANK” “BLANK”

Push 6th time Return to normal view mode

-K3 Key function Display LED

Push 1st time Reset

-K4 Key function Display LED

SEG 1 SEG 2, 3, 4

Push 1st time Outdoor capacity 1 Ex) 16 HP  Off, 1, 6

Push 2nd time Digital comp loading time 2 Ex) Loading 13 sec  Off, 1, 3 Push 3rd time High pressure (kg/cm2) 3 Ex) High pressure 15.2 (kg/cm2)  1, 5, 2 Push 4th time Low pressure (kg/cm2) 4 Ex) Low pressure 4.3 (kg/cm2)  0, 4, 3 Push 5th time Discharge temperature of compressor 1 5 Ex) 87°C  0, 8, 7

Push 6th time Discharge temperature of compressor 2 6 Ex) 87°C  0, 8, 7 Push 7th time Discharge temperature of compressor 3 7 Ex) 87°C  0, 8, 7

Push 8th time CT sensor value of compressor 1 8 Ex) 2A  0, 0, 2

8 Error codes

Display alphabet at  Description

E It displays from error 101 to error 700.

P It displays from error 701 to error 800.

U It displays the address of outdoor unit.

Ex) U200 : Outdoor unit 1, U201: Outdoor unit 2, U202: Outdoor unit 3, U203 : Outdoor unit 4 A It displays the address of indoor unit.

Ex) A000 : Indoor address 1, A001: Indoor address 1, A002 : Indoor address 2

No. Error code Description

1 E-101 Communication error in indoor unit. It displays when the indoor unit receives no data from the outdoor unit.

2 E-102 Communication error between indoor and outdoor unit. It displays in indoor unit.

3 E-121 Room temperature sensor of indoor unit. (Open or Short) 4 E-122 Eva_in temperature sensor of indoor unit. (Open or Short) 5 E-123 Eva_out temperature sensor of indoor unit. (Open or Short)

6 E-124 Communication error between indoor and outdoor unit. It displays in outdoor unit.

7 E-125 Mid 2 temperature sensor of indoor unit. (Open or Short)

8 E-128 Eva_in temperature sensor is detached from eva_in pipe of indoor unit.

9 E-129 Eva_out temperature sensor is detached from eva_out pipe of indoor unit.

10 E-130 Eva_in and Eva_out temperature sensors are detached from eva_in and out pipes of indoor unit at the same time.

11 E-137 VOC sensor of ERV product. (Open or Short) 12 E-138 Gas sensor of ERV product. (Open or Short) 13 E-139 CO2 sensor of ERV product. (Open or Short ) 14 E-151 EEV opening error of indoor unit (2nd detection) 15 E-152 EEV closing error of indoor unit (2nd detection) 16 E-153 Floating switch error of indoor unit (2nd detection) 17 E-154 RPM feed back error of indoor unit.

18 E-155 RPM feed back error of indoor unit. (The second motor of indoor unit)

19 E-161 Mixed operation mode of indoor units. It occurs when outdoor unit is operating or going to operate in cooling mode(or heating mode) and then other indoor unit is going to operate in heating mode (or cooling mode).

20 E-162 EEPROM error of MICOM. (Physical damage) 21 E-163 Option code error of indoor unit’s EEPROM.

22 E-167 Option setting error of indoor unit’s dip switch.

Installation 28 E-191 No matching between indoor unit’s address and eva_out sensor in pipe checking operation.

29 E-199 It displays when pipe checking operation is not operated.

30 E-201 Communication error between indoor and outdoor unit (Tracking failure or the setting quantity of indoor unit on outdoor unit’s PCB differs from the quantity of installed indoor unit.)

31 E-202 Communication error between indoor and outdoor unit.

(After tracking is completed, and then no response from indoor unit) 32 E-203 Communication error between main and sub outdoor unit

33 E-204 The setting quantity of MCU on outdoor unit’s PCB differs from the quantity of installed MCU.

34 E-210 Communication error between MCU and outdoor unit.

35 E-211 Indoor unit’s address overlapped on the MCU.

35 E-213 No matching between installed indoor unit’s address and indoor unit’s address on the MCU.

35 E-214 Setting error of MCU’s quantity in outdoor unit’s PCB

36 E-215 Indoor unit’s address setting error on the MCU. (There is same address among the MCUs)

36 E-215 Indoor unit’s address setting error on the MCU. (There is same address among the MCUs)

In document DVM PLUS3 1 Outdoor Units (Page 36-64)

Related documents