Chapter 7 applies some suitable bulk pipeline performance indicators for assessing water losses on the pipes tested as described in Chapter 5 For each indicator the pipelines are ordered
4 Experimental Verification Tests 1 Introduction
4.4 Experimental procedure, data collection and analysis methodology
4.4.3 Data analysis procedure
The raw pressure and flow data were entered onto a spreadsheet in Microsoft Excel and the following steps were performed on the data:
4.4.3.1 Step 1: interpretation of the data
The raw flow and pressure data were plotted against time. Experimental data points were obtained by identifying stable sections of the flow and pressure graphs and then taking the average values over each of the ranges.
The flow and pressure data points were recorded in litres/min and bars, respectively. The units were then converted to SI units of π3/π and π for the flow rate and pressure, respectively. The following conversions were used:
πππππ π’πππ(π3β ) = ππ
ππππ π’πππ (π πππβ ) Γ 1 60000β .
Equation 4-1
βππππ π’πππ(π) = βππππ π’πππ (πππ) Γ 10.1997
Equation 4-2
4.4.3.2 Step 2: determining the actual pressure in the test pipe
Since the pressure sensor of the PCAE is not located at the leak, the measured pressure data point values had to be adjusted in order to estimate the true pressure at the leak. This adjustment was done by accounting for (a) the elevation difference between the pressure sensor and the leak, (b) head losses due to friction between the pressure sensor and the leak, and (c) minor losses due to the various hydraulic components between the pressure sensor and the leak. The elevation correction was determined by measuring the height between the deviceβs pressure sensor and the leak. Since the device was on the floor (see Figure 4-6), the height from the floor to the pressure sensor of the device was measured first; thereafter the height from the floor to the leak was measured. The difference between them was 0.05 meters.
4-123
The friction losses were calculated to account for friction loss between the PCAEβs pressure sensor and the entry point into the test rig. To do so, the first step was to calculate the Reynolds equation, given here,
π = 4π ππ·π
Equation 4-3
Where π is the flow rate, π· is the internal diameter, and π£ is the kinematic viscosity. All flow was observed to be turbulent. Using the parameters given in Table 4-1, the friction factor, f, was calculated for each data point using the Haaland equation for turbulent flow, given here as: 1 βπ = β1.8 log [( π π·β 3.7) 1.11 + 6.9 π ] Equation 4-4
Finally, to calculate the friction head loss, βπ, for each data point, the Darcy Weisbach equation was used: βπ = ππΏπ£2 2π·π = π πΏ π· (π ππ·2 4 β ) 2 2π Equation 4-5
Where βπ is the friction head loss (m), π is the measured flow rate (m3/s), π· is the internal diameter of the pipe (m), π is the friction coefficient, π is the acceleration due to gravity (m/s2) and πΏ is the length pipe (m). The parameters used to calculate the friction head loss are given in Table 4-1.
4-124
Table 4-1: Parameters used to calculate the friction head loss for each step
Parameter Value
Delivery line Internal diameter, π« (m) 0.0452
Length of delivery line, π³ (m) 10
Acceleration due to gravity, π (m/s2) 9.81
Rubber hose pipe Absolute roughness, π (mm) 0.05
Kinematic viscosity, π (m2/s) 11.39x10-7
The minor losses were calculated to take into account the effect of the various hydraulic components between the pressure sensor and the test rig. The hydraulic components are listed below in Table 4-2, with their respective minor loss coefficient obtained from Finnemore and Franzini (2009).
Table 4-2: Hydraulic components and their minor loss coefficients
Hydraulic components Minor loss coefficient, K
Ball valve 0.1
Adapter (Sudden Contraction) 0.3
Adapter (Sudden Expansion) 0.75
Rubber hose pipe bends 0.5
Straight connecters 0.2
The minor loss coefficients in Table 4-2 were added up and the minor loss for each data point was calculated, using the minor head loss equation given here:
βπ = β πΎ
(4π ππ·β 2)2 2π
Equation 4-6
Finally, once the measured pressure (h measured) from the pressure transmitter is obtained. The
adjusted pressure values were obtained by subtracting the elevation height, βz, friction head loss, hf, and the minor head loss, hm, from the measured average pressure, and the pressure at the leak could thus be established using the following equation:
βππππ’π π‘ππ = βππππ π’πππβ βπβ βπβ βπ§
4-125
4.4.3.3 Step 3: determining leakage parameters for the power equation
The leakage parameters for the power equation were determined empirically. The flow rate (π) and adjusted pressure (βππππ’π π‘ππ) values were plotted with a power equation fitted to the data. The power equation has a coefficient value, representing the leakage coefficient (πΆ) and an exponent value representing the leakage exponent (π1), respectively. The N1 equation is given here:
π = πΆ βπ1
Equation 4-8
In order to verify the power equation leakage parameters, Equation 4-8 is converted into an equivalent linear function by applying logs of base 10 on both sides of the equation. This results in the following linear expression:
πΏππ10π = πΏππ10πΆ + π1 πΏππ10βππππ’π π‘ππ
Equation 4-9
The slope and intercept of Equation 4-9 represents the π1 leakage exponent and the log of the leakage coefficient, respectively. Using the Microsoft Excel function of Slope and Intercept and the flow and adjusted pressure data, the slopes and intercept of the linear function in Equation 4-9 can be obtained. The π1 leakage exponent value is obtained directly from the slope of the linear equation; however, in order to obtain the leakage coefficient, the following formulation is required:
πΆ = 10πΏππ10πΆ
Equation 4-10
4.4.3.4 Step 4: calculating the effective leak area (πͺ
ππ¨)
The effective leak area, CdA, at each pressure step was calculated by re-arranging the orifice equation as follows:
πͺπ π¨ = πΈ
βπ π πππ ππππππ
4-126
Where πͺπ is the discharge coefficient, πΈ is the measured flow rate (m3/s), π
ππ ππππππ is the test pipe pressure (m), π is the acceleration due to gravity (m/s2) and π¨ is the equivalent leak area (m2).
If the total effective leak area of the system is estimated at different pressures, the effective leakage area can be plotted against pressure and a linear function fitted to the data points. The intercept of this line with the effective area axis gives the effective initial leak area (πΆππ΄0 ππ π΄β²), and the slope of this line gives the effective head-area slope (πΆππ ππ πβ²).
4.4.3.5 Step 5: determining the leakage parameters for the modified orifice
equation
Since the leak sources are drilled into the pipe, the actual initial leak area can be physically measured and thus is known (π΄0,ππππ€π). Consequently, the discharge coefficient (πΆπ) can be estimated by dividing the obtained initial effective leak area (πΆππ΄0), determined in step 4, by the known initial leak area (π΄0,ππππ€π) as follows:
πΆπ = πΆππ΄0 π΄0,ππππ€π
Equation 4-12
4.4.3.6 Step 6: estimating the leakage flow rate
The leakage flow rates were estimated using the power equation and the modified orifice equation models. The leakage parameters for the power equation (π1, πΆ) were substituted into the power equation, and the leakage parameters for the modified orifice equation (πΆππ΄0, πΆππ) were substituted in the modified orifice equation. The leakage equations models are given as follows:
Power Equation:
π = πΆ βπ1
Equation 4-13
Modified Orifice Equation:
π = β2π[(πΆππ΄0)β0.5+ (πΆππ)β1.5]
4-127
Once the leakage parameters are substituted into their respective leakage equation models, the flow rates, π, can be obtained and plotted for a range of pressure heads, i.e. β = 0, 15, 20, 25, 30, 35π. The leakage flow rates, π, obtained using the leakage equation models are plotted against pressure as continuous lines. The measured experimental flow rate data points are plotted against the measured pressure as discrete data points on the same flow vs pressure graphs. This is done to determine whether the measured flow and pressure data points correlate with the power equation and modified orifice equation flow rate models.
4.4.3.7 Step 7: determining the leakage number
Finally, a dimensionless leakage number (πΏπ) is calculated for the leak. The leakage number (πΏπ) represents the ratio between the expanding leakage area and the fixed leak area, and is expressed as follows:
πΏπ= πβ
π΄0
Equation 4-15
A simple equation was proposed by Cassa and van Zyl (2010) to convert between the leakage number (πΏπ) and the leakage exponent (π1):
πΏπ = π1 β 0.5 1.5 β π1 Equation 4-16 π1 = 1.5 πΏπβ 0.5 πΏπ+ 1 Equation 4-17