• No results found

Description and operation of the system

1 DESCRIPTION AND OPERATION OF THE SYSTEM

1.3 Description and operation of the system

The System is a hardware and software system that includes SC described in section 1.4.

Depending on RCD type, the System operates in one of the following modes:

а) in call mode when RCD and remote calling stations are connected by RS-485 network or four-wire communication line;

b) in call bell mode when a push-button sends signals to signaling unit.

During operation, remote stations call to central or additional RCD, initiating sound and light alarm signaling and displaying the address of the calling station.

In call bell mode, call button sends a call and supplies power to a signaling unit, and by that, switching it on.

RCDs of all types (except SCS-WP) and remote calling stations SCS-CH and

SCS-REF connected via RS-485 set up local data exchange network.

RCDs SCS-SPS-5, SCS-SPS-10 may operate with 5 and/or 10 remote stations in common network, and SCS-CU and SCS-CU-REP – with 32 remote stations.

RCDs SCS-SPS-5, SCS-SPS-10 may also operate via four-wire communication line.

RCD SCS-WP type allows for direct button connection via four-wire communication line.

Once remote station sends a call, the System operates in the following order:

а) if remote stations are connected via RS-485, a remote station controller registers a signal, then actuates local signaling units and sends a call signal to RCDs SCS-SPS-5, SCS-SPS-10, SCS-CU, SCS-CU-REP types that display network address of the calling station.

The call actuates local alarm on the RCD and repeater SCS-CU-REP and switches light indication of the calling station number (name);

b) if call buttons are connected via four-wire line – firstly, local signaling units actuate; RCDs SCS-SPS-5, SCS-SPS-10 and SCS-WP register signal on the corresponding port, and then actuate local and external call alarms;

c) in call bell system a signaling unit is switched on by push-button.

Once the call is received, an operator may use Mute function (call bell system does not provide this function) and temporarily mute sound signaling by corresponding button on RCD.

Sound signaling will be switched off both on RCD and repeater SCS-CU-REP;

light indication on both units will change from flashing to constant lighting.

An operator may also mute sound signaling on the repeater, but RCD signaling will be still working.

Sound signaling muted by RCD or repeater will resume after time interval (timer), if during this time the call has not been reset at the calling station. Set time interval in the settings.

Only when the call is reset (by Reset/Mute button) on the calling station, alarm signaling will be switched off on RCD, repeater and remote calling station.

Button «Mute/Reset» on SCS-WP switches off sound alarm and resets call signaling.

To reset a call in call bell System, return button to the initial position.

Therefore, the System operates in the following order:

а) remote calling station initiates a call to watch officer station and backup station where local signaling actuates;

b) an operator mutes sound signaling on RCD and heads to the calling station;

c) at the calling station the officer resets the call and investigates the reason of the call.

Depending on System application, we recommend the following System configurations, see Table 2:

а) for a ship’s hospital, according to Figure 1;

b) for refrigerated holds and refrigerator units, according to Figure 1;

c) to call a watch officer according to Figure 2;

d) as a call bell system according to Figure 3.

Table 2 – Optional System configurations

Code

Figure 1 – Configuration for ship’s hospital and refrigerated holds

Figure 2 – System configuration to call a watch officer

Figure 3 – System components of call bell system 1.4 SYSTEM COMPONENTS

For the SC, which might be included in a scope of delivery, see Table 3. For more information on specifications and types of SC, see Description.

Table 3 – The System components

Name/Code Description

Central units

Reception and control device SCS-SPS-5-P Ensures light and sound call signaling;

indicates the number of calling station with corresponding LEDs. Depending on the type, controls 5 or 10 remote stations.

Remote stations are connected via RS-485 or four-wire communication line

Reception and control device SCS-SPS-5-W Reception and control device SCS-SPS-10-P Reception and control device SCS-SPS-10-W

Reception and control device SCS-CU-P Ensures light and sound call signaling, displays the number of calling station on the LCD. Controls 32 stations. Remote button stations are connected via RS-485

Reception and control device SCS-CU-W

Reception and control device SCS-WP Ensures light and sound call signaling (watch officer station). Controls one line (station).

Remote button station is connected via four-wire communication line

Repeater SCS-CU-REP-P Repeats call signaling at the backup station;

displays the number of calling station on the LCD. Controls 32 stations. Remote button stations are connected via RS-485

Repeater SCS-CU-REP-W

Remote calling station (controller) SCS-CH Sends Reset and Call signals to RS-485 network

Remote calling station (controller) SCS-REF

Call button SCS-CH-PB Initiates a call; equipped with a connector for hand-held push button SCS-CH-EPB

Call button SCS-CH-EPB Initiates a call; equipped with a connector for call button SCS-CH-PB

Name/Code Description

Call button SCS-BPT Initiates a call from the spaces with special temperature

Call button SCS-PBP Push-button to provide power supply for a signaling unit. Power supply 24 V DC or 220 V AC, frequency 50 Hz

Call button SCS-WP-PU Initiates or resets a call

Call button SCS-CH-LB Repeats call signal from SCS-CH-PB until reset at local station; sends control signal to signaling units

Junction box SCS-JB-2 Distributes RS-485 network and power line to 2 outputs

Junction box SCS-JB-6 Distributes RS-485 network and power line to 6 outputs

Relay unit RB-139G-24 Supplies power to signaling units by control signal. Power supply 24 V DC or 220 V AC, frequency 50 Hz

Relay unit RB-139G-220

Flashing lamp FL-24 Provides light signaling, pulse. Power

supply 24 V DC

Rotating lamp RL-24 Provides light signaling, flashing. Power supply 24 V DC or 220 V AC, frequency 50 Hz

Rotating lamp RL-220

Sound signaling unit A-24 Provides sound signaling. Power supply 24 V DC or 220 V AC, frequency 50 Hz Sound signaling unit A-220

Sound and light signaling unit AL-24 Provides sound and light signaling. Power supply 24 V DC or 220 V AC, frequency 50 Hz

Sound and light signaling unit AL-220

1.5 MEASUREMENT TOOLS, INSTRUMENTS AND APPLIANCES

Control operation of the System units by their controls and LED indicator lights.

Technical service of the System is carried out using tools and consumables represented in Table 4 and Table 5.

Table 4 – Instruments and appliances

Name Place of storage

Strengthened screwdriver (cross) PH-2, 100 mm

Station of person in charge for the System Screwdriver (cross) РH-1, 80 mm

Table 5 – Consumables required for TS

Name and identifier of consumables

Amount of

consumables Note

Cleaning cloth 0.10 kg 1) to clean surfaces and parts of the system – use clean cloth;

2) to clean severe contamination – use alcohol-soaked cloth Rectified hydrolytic

technical ethyl alcohol

0.05 l To soak cloth while removing contamination

Varnish 0.005 kg To cover surfaces of the unit in case of paint coating damage Abrasive cloth 0.06 х 0.06 m To polish surfaces of the unit in case of paint coating damage

1.6 MARKING AND SEALING

The System has a nameplate displaying information on the System’s name, serial number, Manufacturer’s details. The nameplate is located on RCD casing.

The SC also have nameplates displaying serial number, weight, IP rating, input voltage and power consumption. The nameplate is located on the SC casings.

Sealing of SC and packaging is not provided.

1.7 PACKAGING

The System is delivered, transported and stored in corrugated board boxes; each SC is packed in air bubble film.

Transport packaging is also used as a returnable packaging for transportation of the System to the place of repair and back.

2 DESCRIPTION AND OPERATION OF THE SC 2.1 RECEPTION AND CONTROL DEVICES

The System includes two types of RCDs:

a) one line RCD (controls one remote station) – SCS-WP (a watch officer station);

b) several lines RCD (controls several stations) – SCS-SPS-5, SCS-SPS-10, SCS CU, SCS-CU-REP.

Call button may be connected directly to one line RCD.

Several lines RCDs are network devices; they operate in RS-485 network and allow for connection of remote calling stations: controllers SCS-CH and SCS-REF.

RCDs SCS-SPS-5 and SCS-SPS-10 types may also operate with call buttons by four-wire line.

2.1.1 Reception and control devices SCS-SPS-5 and SCS-SPS-10 The functions of SCS-SPS-5 and SCS-SPS-10:

a) to control signals received from controllers in RS-485 network;

b) to control remote stations connected via four-wire communication line;

c) to actuate alarm immediately (acoustic, light, address) once call signal is supplied to data exchange network;

d) to indicate status of 5 or 10 remote stations on LED display at the same time;

e) to mute alarm sound signaling (initiated by current call and connection failure with remote stations);

f) to reset current call signaling, or reset a call from remote station connected via four-wire line;

g) to actuate alarm when connection with remote calling station is lost and display the corresponding address;

h) external alarm may be connected;

i) to provide backlight of controls and LEDs with stations numbers; backlight dimming;

j) test function checks operation of sound and light signaling units;

k) to control power supply to stations and repeater, depending on the power supply diagram.

Figure 4 describes appearance of RCD SCS-SPS-5. Table 6 describes controls and LEDs of RCD SCS-SPS-5.

Figure 4 – Appearance and description of controls and LEDs of SCS-SPS-5

Table 6 – Controls and LEDs of SCS-SPS-5

Name Description

1 Remote stations status LEDs To display status of remote stations (operation status, fault, communication line failure)

2 Plastic pockets Transparent pockets for replaceable inserts 3 «Reset/Mute» button To reset (mute) sound signaling

4 «Call» LED To indicate incoming call

5 Backlight dimmer To adjust backlight brightness of LEDs and buttons 6 «Power» LED To display power availability (status)

7 Power on (off) button To switch on (off) power supply to the unit and connected external units

8 Speaker To provide for sound signaling of incoming call 9 «Test» button To initiate operation test of light indicators

Two or more RCDs may be included in the System with network connection of buttons (does not apply to SCS-CU). One device always operates as master device (ensuring full control of the System), and others – as slave devices (functioning as data repeating devices with reset (mute) mode).

SCS-SPS-5 and SCS-SPS-10 are equipped with a delay timer of sound signaling.

When a remote station calls, different RCDs may actuate sound signaling with delay from 0 to 180 sec (depending on settings), according to Table 7.

Table 7 – Settings of the delay timer

DIP position Delay, sec DIP position Delay, sec

0 120

30 150

60 180

90

2.1.2 Reception and control device SCS-CU The functions of SCS-CU:

a) to control signals received from controllers in RS-485 network;

b) to actuate alarm immediately (acoustic, light, address) once call signal is supplied to the network;

c) to control 32 remote stations at the same time;

d) to display status of 32 remote stations on LCD at the same time;

e) to mute temporarily call sound alarm and alarm of connection failure;

f) to switch off call signaling once Call reset signal is supplied to data exchange network;

g) to display connection status of controllers on LCD;

h) to actuate alarm when connection with remote calling station is lost and display the corresponding address;

i) external alarm may be connected;

j) to provide backlight of controls and LCD; backlight dimming;

k) to control power supply to all connected devices.

The device is equipped with an integrated touch screen LCD using which an operator can see and control displayed names of the stations, and carry out settings. Figure 5 describes appearance of SCS-CU. Description and correct use of controls is described in Table 8.

Figure 5 – Appearance of SCS-CU Table 8 – Controls and LEDs of SCS-CU

Name Description

1 LCD To display names of stations, control RCD and provide settings

2 Navigation buttons To move throughout a menu

3 Power on (off) button To switch on (off) power to external devices 4 «Mute» button To mute sound signaling (temporarily)

5 Speaker To provide call signaling

6 «Exit» button To return to previous menu level, until the main (working) screen

7 «Brightness dimming» button To adjust backlight brightness of buttons and LCD

8 «Menu» button To access the menu

Operation of SCS-CU and SCS-CU-REP LCDs: after turning on and in wait mode LCDs of SCS-CU and SCS-CU-REP display status of controlled remote stations. The stations are shown as screen areas with numbers and text information, see Figure 6.

Figure 6 – Working mode of SCS-CU and SCS-CU-REP

Each screen area (indicator) may operate in the following modes or their combination:

– no call (normal);

– call (call detected);

– no station connection;

– buttons failure (error) or communication line failure.

Each mode (except normal) may have active (when call received) or reset status (once an operator resets/mutes the call):

– active status is supported with flashing light and intermittent sound signaling;

when connection with station or call button is lost, а corresponding screen area is crossed with flashing red cross and displays «No connection» or «Button failure». In the first case a red frame with a cross appears on the indicator’s area; in the second case – only red frame;

– reset status is supported with bright glowing of indicator; if connection is lost, indicator’s frame (perimeter) remains red.

An indicator’s area returns to an initial view once the call is reset or connection recovered.

2.1.3 Reception and control device SCS-WP

Any call button connected to the device may send a call.

The functions of the SCS-WP:

а) to control signals from call buttons connected directly to SCS-WP;

b) to actuate alarm immediately if call button sends a call;

c) to control one connected line (station). Several call buttons may be connected in parallel;

d) to reset call by «Reset/Mute» button on the device, or temporarily mute sound signaling (depending on selected operation mode);

e) external alarm may be connected;

f) to initiate alarm in case of connection failure with call button;

g) to provide controls backlight;

h) to adjust brightness of controls and LEDs.

Figure 7 describes appearance of SCS-WP. Description and correct use of the device are represented in Table 9.

Figure 7 – Appearance of SCS-WP Table 9 – Controls and LEDs of SCS-WP

Name Description

1 «Brightness» knob To adjust controls backlight

2 «Reset/Mute» button To mute temporarily sound signaling

3 Speaker To ensure sound signaling

4 «Power» LED To indicate power supply to the device

5 «Fault» LED To indicate faults

6 «Call» LED To indicate call

2.1.4 Repeater SCS-CU-REP

Repeater SCS-CU-REP receives a call signal from remote stations in data exchange network.

Use the repeater if you need additional control over calls from remote calling stations (along with the main station) and (or) RCD operation.

As a System component, the unit repeats RCD; it may also mute local sound signaling.

Note – RCD may be used as a repeater (in repeater mode).

The unit has the same functions and controls as SCS-CU, except a button to supply power to the connected devices.

Mute mode of the repeater is independent, and does not influence sound signaling of the main RCD.

Figure 8 describes appearance of SCS-CU-REP. Description and correct use of controls are shown in Table 10.

Figure 8 – Description of controls and LEDs of SCS-CU-REP Table 10 – Controls and LEDs of SCS-CU-REP

Name Description

1 LCD To display names of stations, control RCD and provide settings

2 Navigation buttons To move throughout a menu

3 «Mute» button To mute sound signaling (temporarily)

4 Speaker To provide call signaling

5 «Exit» button To return to previous menu level until the main (working) screen

6 «Brightness dimming» button To adjust backlight brightness of buttons and LCD

7 «Menu» button To access the menu

2.2 REMOTE STATIONS (CONTROLLERS)SCS-CH,SCS-REF

Controllers are designed to register call from remote stations and transmit it to RCD through data exchange network RS-485.

Controllers have two types:

а) for ship’s internal spaces – SCS CH;

b) for refrigerated holds – SCS REF.

The functions of controllers:

а) to send a call from local button (for REF) or button connected to SCS-CH;

b) to actuate local alarm: call button LED – for controller SCS-REF, and external signaling unit (if available) – for all controllers;

c) to reset current call by «Reset» button;

d) to display power availability and connection with RCD.

2.2.1 Controller SCS-CH

Controller SCS-CH is not equipped with a call button. One or two external call

buttons may be connected in the close vicinity of user. Figure 9 describes appearance of the device. Description and correct use of controls and LEDs are shown in Table 11.

Figure 9 – Layout of SCS-CH controls and LEDs Table 11 – SCS-CH controls and LEDs

Name Description

1 Plastic pocket To put a replaceable insert with a station name on it 2 Button «Reset» with LED To reset and display a call

3 «Power» LED To display power availability

4 «Status» LED To display controller status (operation, fault, communication line failure)

2.2.2 Controller SCS-REF

Controller SCS-REF is used in refrigerated holds and refrigeration units. To call press «Call» button on the controller.

External call buttons cannot be connected to SCS-REF. Figure 10 describes appearance of the device. Description of controls and LEDs is shown in Table 12.

Figure 10 – Layout of SCS-REF controls and LEDs

Table 12 – SCS-REF controls and LEDs

Name Description

1 «Status» LED To display controller status (operation, fault, communication line failure)

2 Plastic pocket To put a replaceable insert with a station name on it

3 «Power» LED To display power availability

4 Button «Reset» To reset a call

5 Button «Call» with LED To initiate and display a call

2.3 CALL BUTTONS

Different types of call buttons ensure calling within the System, see Table 13.

Table 13 – Brief specifications of call buttons

Button code Buttons Control of external signaling unit

IP

code Notes

«Call» «Reset»

SCS-CH-PB + IP22

SCS-BPT + IP56 Heatproof

SCS-PBP + + IP56 Push-button

SCS-WP-PU + + + IP56

SCS-CH-EPB + IP56

SCS-CH-LB + + IP22 Latching button

Note – SCS-CH-LB button repeats call from external call button until reset by the local button.

Notes

«+» – functional element is present.

«–» – functional element is not present.

3 INTENDED USE

3.1 OPERATION LIMITATIONS

Connect the System units according to connection diagram and tables issued for the order. All units shall be grounded; cables shall be isolated; all non-isolated cable ends shall be isolated.

3.2 USAGE PREPARATIONS

3.2.1 Safety features

After transportation in winter, leave unpacked Product for 12 hours at the facilities where it will be used.

Before using the System, the installer shall:

– train the personnel to operate the Product; familiarize the personnel with test and control equipment and applicable occupation safety requirements;

– familiarize personnel with all grounding points; check grounding;

– use only standard fuses;

– de-energize all devices before disconnecting cables, replacing fuses, units and modules;

– the installer shall follow «The technical rules for operation of electric installation» and «Safety rules for operation of electric installation» while testing electrical circuits and insulation resistance.

After unpacking the device, check that there is no mechanical damage.

3.2.2 Visual check procedure

Before switching the SC on,the installer shall:

– observe visually the cable integrity and initial position of the controls on the SC front panels;

– clean the SC from dust and dirt by clean soft cloth, if necessary;

– check fail-safe cable connections to the SC and their proper grounding.

3.2.3 How to switch the System on

3.2.3 How to switch the System on

Related documents