10 Diagnostics and servicing 10.1 Maintenance

If the device is used properly, no special maintenance is required in normal operation.

The cleaning helps that the type label and markings on the instrument are visible.

Take note of the following:

Use only cleaning agents which do not corrode the housings, type label and seals

Use only cleaning methods corresponding to the housing protec-tion rating

10.2 Rectify faults

The operator of the system is responsible for taking suitable meas-ures to rectify faults.

The device offers maximum reliability. Nevertheless, faults can occur during operation. These may be caused by the following, e.g.:

Sensor

Process

Voltage supply

Signal processing The first measures are:

Evaluation of fault messages

Checking the output signal

Treatment of measurement errors

A smartphone/tablet with the adjustment app or a PC/notebook with the software PACTware and the suitable DTM offer you further com-prehensive diagnostic possibilities. In many cases, the causes can be determined in this way and the faults eliminated.

Depending on the reason for the fault and the measures taken, the steps described in chapter " Setup" must be carried out again or must be checked for plausibility and completeness.

Should these measures not be successful, please call in urgent cases the VEGA service hotline under the phone no. +49 1805 858550.

The hotline is also available outside normal working hours, seven days a week around the clock.

Since we offer this service worldwide, the support is provided in English. The service itself is free of charge, the only costs involved are the normal call charges.

Maintenance Cleaning

Reaction when malfunc-tion occurs

Causes of malfunction

Fault rectification

Reaction after fault recti-fication

24 hour service hotline

10 Diagnostics and servicing

62097-EN-210701

10.3 Diagnosis, fault messages

The 360° status indication on the device indicates the operating status of the device (display according to NE 107). At the same time it indicates the switching state of the output. This enables simple on-site diagnosis without the need for tools.

Error Cause Rectification

Green signal lamp off Voltage supply interrupted. Check the voltage supply and the cable con-nection

Electronics defective Exchange the instrument or send it in for repair Green signal lamp flashes Maintenance required Carry out maintenance

Red signal lamp lights

(switch-ing output high-impedance) Error with the electrical

con-nection Connect the instrument according to the wir-ing plan

Shortcircuit or overload Check the electrical connection

Measuring tip damaged Check whether the measuring tip is damaged Red signal lamp flashes

(switching output high-imped-ance)

Sensor outside the specifi-cation Check the adjustment of the sensor Sensor is in simulation mode Terminate simulation mode Function test is carried out Complete function test

10.4 Status messages according to NE 107

The instrument features self-monitoring and diagnostics according to NE 107 and VDI/VDE 2650. In addition to the status messages in the following tables there are more detailed error messages available under the menu item " Diagnostics" via DTM or app.

The status messages are divided into the following categories:

Failure

Function check

Out of specification

Maintenance required and explained by pictographs:

4

1 2 3

Fig. 17: Pictographs of the status messages 1 Failure - red

2 Out of specification - yellow 3 Function check - orange 4 Maintenance required - blue

Failure: Due to a malfunction in the instrument, a fault message is output.

This status message is always active. It cannot be deactivated by the Checking the switching

signal

Status messages

10 Diagnostics and servicing Function check: The instrument is being worked on, the measured value is temporarily invalid (for example during simulation).

This status message is inactive by default.

Out of specification: The measured value is unreliable because an instrument specification was exceeded (e.g. electronics temperature).

This status message is inactive by default.

Maintenance required: Due to external influences, the instrument function is limited. The measurement is affected, but the measured value is still valid. Plan in maintenance for the instrument because a failure is expected in the near future (e.g. due to buildup).

This status message is inactive by default.

Code Text message

Cause Rectification

F013

no measured value available

Error in capacitive measurement Send instrument for repair

F036

No operable software

Wrong software type

Software update not successful or aborted

Repeat software update

F080

General software error

Software error Restart instrument

F105

Measured value is deter-mined

Device is still in the switch-on phase Wait for the end of the switch-on phase

F260

Error in the calibration

Error in the calibration carried out in the factory

Error in the EEPROM

Send instrument for repair

F261

Error in the instrument set-tings

Checksum error in the configuration

values Carry out a reset

Code Text message

Cause Rectification

C700

Simulation active

A simulation is active Finish simulation

Wait for the automatic end after 60 mins.

Code Text message

Cause Rectification

S600

Impermissible electronics temperature

Temperature of the electronics in the

non-specified range Check ambient temperature Insulate electronics Failure

Function check

Out of specification

10 Diagnostics and servicing

Switching output overloaded

Overload or short circuit on the

switch-ing output Check electrical connection

Code Text message

Cause Rectification

M511

Inconsistent software con-figuration

Software faulty or outdated Carry out software update

10.5 Software update

The device software is updated via Bluetooth.

The following components are required:

Instrument

Voltage supply

PC/notebook with PACTware/DTM and Bluetooth USB adapter

Current instrument software as file

You can find the current instrument software as well as detailed infor-mation on the procedure in the download area of our homepage.

Caution:

Instruments with approvals can be bound to certain software versions.

Therefore make sure that the approval is still effective after a software update is carried out.

You can find detailed information in the download area on our home-page.

10.6 How to proceed if a repair is necessary

You can find an instrument return form as well as detailed information about the procedure in the download area of our homepage. By doing this you help us carry out the repair quickly and without having to call back for needed information.

In case of repair, proceed as follows:

Print and fill out one form per instrument

Clean the instrument and pack it damage-proof

Attach the completed form and, if need be, also a safety data sheet outside on the packaging

Ask the agency serving you to get the address for the return ship-ment. You can find the agency on our homepage.

Maintenance

11 Dismount

11 Dismount

11.1 Dismounting steps

Warning:

Before dismounting, be aware of dangerous process conditions such as e.g. pressure in the vessel or pipeline, high temperatures, cor-rosive or toxic media etc.

Take note of chapters " Mounting" and " Connecting to voltage sup-ply" and carry out the listed steps in reverse order.

11.2 Disposal

The device is made of recyclable materials. For this reason, it should be disposed of by a specialist recycling company. Observe the ap-plicable national regulations.