• No results found

EXAMPLES IN IDENTIFICATION OF COMMUNICATIONS SYSTEMS The Identification will be according to task process-related identification

In document KKS Guideline for Equipments-rev1 (Page 51-74)

Variant 4 : each structure is considered global and the correlation between floor numbers and ranges of elevations are agree before start the identification.

9 EXAMPLES IN IDENTIFICATION OF COMMUNICATIONS SYSTEMS The Identification will be according to task process-related identification

The identification uses the KKS normal principles. We use AY for Grid and Distribution Systems and CY for Power Plants into Level 1 (attached 1).

Example 1 – Fire Alarm System

10CYE41CP320-B15 means:

Level 0: 10 = power plant unit 1

Level 1: CYE41 = Fire alarm system, cabinet 1 of control centre 4

Level 2: CP320 = Measuring circuit type (pressure), instrument loop nº 320 Level 3: B15 = Fire alarm nº 15 in the loop no 320

Example 2 – Alarm System

10CYN12315-H12 means

Level 0: 10 = power plant unit 1

Level 1: CYN12 = Alarm system, cabinet 2 of control centre 1 Level 2: 315 = serial number of alarm 15 of Alarm group no 3

Level 3: H12 = Acoustic signalling equipment (loudspeaker) no 12 in loop 15 The Level 2 can also be written as:

10CYN12EK315-H12.

Example 3 – Control console telephone system (two way intercom system) A0CYB13204 means

Level 0: A0 = power plant unit 1+2

Level 1: CYN13 = Control console telephone system, cabinet 3 of the control centre 1

Level 2: 204 = serial number of alarm 15 of Control centre no 2

Level 3: H12 = Acoustic signalling equipment (loudspeaker) no 12 in loop 15 The Level 2 can also be written as:

A0CYB13GK204 Example 4 – Telephone system (PABX) A0CYA01259

Level 0: A0 = power plant unit 1+2

Level 1: CYA01 = Telephone system, control centre 1

Level 2: 204 = serial number of alarm 15 of Control centre no 2 Level 3: H12 = telephone no 259

The Level 2 can also be written as: A0CYA01GK259

N.º 1.2.060-PG-005-RL-2010 REV.: 1 FL.: 50 / 74 Example 5 – Clock system

A0CYF13-P71

Level 0: A0 = power plant unit 1+2

Level 1: CYF13 = Clock system, output no 3 of master clock no 1 Level 3: P71 = Clock no 71 of output 3

We can introduce the Level 2 and it can also be written as: A0CYF13GK001-P71

Example 6 – Optical monitoring (plant CCTV system only) A0CYP14GK002-H12

Level 0: A0 = power plant unit 1+2

Level 1: CYP14 = Optical monitoring system, CCTV system (1), system 4 Level 2: GK002 = Television facility (GK), crossbar distribution no 2 Level 3: H12 = monitor, serial no 12

Example 7 – Radio System (radiotelephone system) A0CYS01-W02

Level 0: A0 = power plant unit 1+2

Level 1: CYS01 = radio system, system 1 Level 3: W02 = Antenna (W), antenna no 2 We can introduce the Level 2 and it can also be written as: A0CYS01GK001W02

Example 8 – Junction boxes for communications systems

The rules are the same as used on junction boxes of C&I (3.3). The Level 1 assume the place where is installed. The letters for Level 2 are GM for junction boxes for national telecommunications service and GY for the others.

A0UMA03GY001 means: A0 = power plant unit 1+2

UMA03 = 3rd floor of turbine housing GY001 =Junction box no 1 of 3 rd floor

N.º 1.2.060-PG-005-RL-2010 REV.: 1 FL.: 51 / 74

N.º 1.2.060-PG-005-RL-2010 REV.: 1 FL.: 52 / 74

10.1 APPENDIX I – Process Identification

10.1.1

Level 1 – System Code

This level 1 have 3 identification letters that are defined on the KKS code. Examples:

A = Grid and distribution systems AD = > 220 (245) kV systems

ADA = Voltage transformers ACB = line traps

ACC = Coupling capacitors ACE = Disconnectors ACF = Circuit breakers ACG = Current Transformers ACH = Lightning arresters AF = 60 kV switchgear

AR = Equipment for protection

ARA = Line protection cubicles ARA01=Disturbance recorder ARA02=Main line protection cubicle ARA03=Reserve line protection cubicle AS = Decentralized panels and cabinets

ASJ = Automated controls, closed loop control ASM= Measuring equipment

ASP = Recording ASQ = Metering ASR = Protection ASS = Synchronization AST = Transformation

ASV = Group, intermediate and general terminal blocks ASW = Indication, manual operation, monitoring ASX = Alarm annunciation

B = Power transmission and auxiliary power supply BA = Power transmission

N.º 1.2.060-PG-005-RL-2010 REV.: 1 FL.: 53 / 74 BAB = Generator neutral cubicle

BAC = Generator load breaker BAT = Main Transformer

BAW = Earthing and lightning protection BAY = control and protection equipment BB = 6 kV unit switchgear and unit transformer

BBA = 6kV unit switchgear 1 BBB = 6kV unit switchgear 2 BBT = Unit auxiliary transformer BC = 6 kV general services switchgear

BCD = 6 kV Overland conveyor switchgear BCF = 6 kV Coal yard switchgear

BF = Unit System, 660 V Load centers and load center transformers BFA = 660 V Turbine Load Center 1

BFC =660 V Boiler Load Center 1 BFG =660 V Pulverizer Load Center 1 BFT = Load center transformers 6/0.6 kV BM = Emergency power system

BR = Uninterruptible power supply BT = DC generation

BU = DC distribution

C = Instrumentation and control equipment

CB = Functional group control, partial control (Drive and Group Control) CBA = MCC for Sootblower

CBB = Control cubicles for hoppers of boiler CBC = Cubicles for Turbine/Generator CC = Binary system conditioning

CCA = Cubicles for Boiler

CCB = Cubicles for Turbine/Generator CE = Annunciation

CEA = Cubicles for fault annunciation systems

CEJ =Cubicle for disturbance signal recording for Boiler

CEK =Cubicle for disturbance signal recording for Turbine/Generator CF = Analog signal conditioning (and Binary if both in the same cubicle)

CFA = Cubicles for Boiler

CFB = Cubicles for Turbine/Generator CFD = Metering cubicles

N.º 1.2.060-PG-005-RL-2010 REV.: 1 FL.: 54 / 74 CGA = Cubicles for Boiler

CGB = Cubicles for Turbine/Generator CH = Protection (not drive level)

CHA = Cubicles for unit protection

CHB = Cubicles for protection of Station Auxiliary Power, Diesel plant, etc (Generator, transformers, motors)

CHC = Cubicles for Generator Protection and Transformer Protection CHE = Cubicle for Boiler protection

CHF = Cubicle for Turbine protection

CJ = Unit Control level (not drive and group control cubicles and analog control cubicles) CJA = Unit control system (mimic and panels control room)

CJD = Start-up control, unit reference value control CJF = Boiler control system

CJJ = Plant Start-up program CJK = Turbine Control System CJL = Binary and analog control CJM = Reclosing device

CJU = Instrumentation and control for other main machine sets CJW = Binary control cubicles for electrical systems

CK = Process computer system CKA = Computer panels CKB = Computer Printers

CKV = computer interface cubicles for boiler

CKW = computer interface cubicles for Turbine/Generator CT = Auxiliary cubicles

CTA = Auxiliary cubicles for Generator and Transformer Protection (intermediate current and voltage transformers, etc)

CTB = Interposing cubicles for Turbine/Generator CTE = Local cubicles for Boiler auxiliary equipment CTF = Local cubicles for Turbine auxiliary equipment CU = Analog Control (actuators, if not included in the switchgear)

CUA = Cubicles for excitation

CV = Marshalling racks (signal distribution cubicles) CVA = signal distribution cubicles general CVC = Marshalling cubicles

CVP = Measurements distribution CVR = Marshalling cubicles for Boiler

N.º 1.2.060-PG-005-RL-2010 REV.: 1 FL.: 55 / 74 CVT = Marshalling cubicles for Control Room

CVW = Marshalling cubicles for Process computer CW = Control Room

CWA = Primary Desk control of the Main Control Room CWB = Secondary Desk control of the Main Control Room CWF = Vertical panels of the Main Control Room

CWG = Voltage Signal distribution cubicles CX = Local control panels or consoles

CXB = Local panels for minimum flow of the feedwater pumps CXC = Main Condenser cleaning system

CXD = Water cooling system for air compressors

CXE = Air ventilation system and air conditioning system CXK = Chemical injection cubicles

CXL = Sampling and chemical continuous monitoring system CXM = Auxiliary steam cubicles

CXN = Lube oil Purification system CXP = Diesel generator control cubicles CXR = Coal handling system cubicles CXS = Effluent treatment control panels

CXT = Generator breaker control cubicle and earthing system CXW = H2/CO2 local signalling box

CY = Communication equipment

CYA = Telephone installation (PABX) CYB = Intercom system

CYC = Staff alarm and location system CYE = Fire alarm system

CYF = Master clock system CYG = Telecontrol system CYJ = Telecounter system CYK = High frequency system CYP = optical supervision system CYN = Alarm System

CYS = Radiotelephone system

D= Instrumentation and control equipment (for use only when the function keys CM to CT are insufficient for the identification)

E = Conventional fuel supply and residues disposal EA = Coal transport and storage system

N.º 1.2.060-PG-005-RL-2010 REV.: 1 FL.: 56 / 74 EAC = Transport system

EAD = Coal stacking equipment EAE = Coal site storage

EAG = Coal reclaiming equipment EAT = coal weighing equipment EAU = Coal sampling equipment EC = Coal distribution system

ECA = Conveyors from site storage to bunkers ECB = Shuttle conveyors

ECD = Coal mobile equipment

ECT = Coal weighing equipment before bunkers input ECU = Coal sampling equipment before bunkers input EG = Fuel oil supply

EGA = fuel oil reception EGB = Fuel oil and slop tanks EGC = fuel pumps

EGD = fuel oil piping system EGT = fuel oil heating system

ER = Lightning fuel supply (Propane gas supply unit) ET = Ash removal, storage and disposal plant

ETC = Bottom ash hopper and drag link ETE = Bottom ash silo

ETG = Conveyor plant for fly ash ETH = Fly ash silo

ETJ = Conveyor plant for fly ash ETK = ash disposal plant ETL = ash disposal area

ETN = bottom ash water recover system F = Handling of nuclear equipment

G = Water supply and disposal GA = Raw water supply

GAA = Raw water intake and filtration GAC = raw water piping

GAE = Raw water chemical treatment system GAF = Pumping system

GB = Raw water Treatment plant GBB = Sand filtration system GBK = piping

N.º 1.2.060-PG-005-RL-2010 REV.: 1 FL.: 57 / 74 GBN = Equipments for chemical injection

GBP = Equipment for regeneration and sand filter cleaning GBS = Decanter

GBY = Equipment for control

GC = Treatment system (demineralization plant) GCF = Ion change, reverse osmosis system GCH = Degasifier

GCK = piping

GCL = Water Demineralization tank GCN = Chemical storage tank

GH = Raw and demineralised water distribution GHA = Raw water distribution

GHC = Demineralised water distribution GHH = Service water distribution 1 GHK = Service water distribution 2 GK = Drinking water production and distribution

GKA = Production GKB = Storage GKC = Distribution

GN = Industrial waste water Treatment Plant GNA = waste water tanks equipments GNB = oil separation equipments GNK = Piping

GNM = clarifier/decanter equipments

GNN = storage and chemical dosing equipments GNS = sludge thickening equipments

GNY = plant control equipments GR = Domestic waste water treatment plant

GRC = Mechanical purification equipment GRK = internal piping

GRY = plant control equipments GU = Rain water collecting and drain system GV = Rain Water treatment

GVB = Mechanical purification system GVK = internal piping

GVY = plant control equipments H = Conventional heat generation

N.º 1.2.060-PG-005-RL-2010 REV.: 1 FL.: 58 / 74 HAC = Economizer system

HAD = Evaporator system HAH = HP superheater system HAJ = Reheater system

HAN = Drains and vents of pressure system HB = Support structure, sheathing

HBA = framework including foundations HBB = enclosures, insulations

HBC = brick linings including insulating brickwork HBD = platforms, stairways

HC = Flue gas side heating surface cleaning equipment HCB = Steam blowing system

HCC = Water blowing system

HF = Bunker, feeder and pulverizing equipment HFA = Coal bunkers

HFB = Pulveriser feeding system HFC = Pulveriser

HFE = Pulveriser primary air HFH = pyrite mill reject system

HFV = Pulveriser lubricating lube oil system HFW = Pulveriser sealing air system HH = Main Firing

HHA = Main Coal burner equipment

HHE = Pulverised coal, conveyance and distribution from pulveriser outlet to burner. HHL = Combustion air supply (secondary air)

HJ = Ignition firing

HJA = Ignition burner (fuel oil) equipment

HJF = Heated fuel oil conveyance and distribution HJG = Atomizing medium supply (steam)

HJQ = Cooling medium supply (air) HJT = Heating medium supply (steam) HL = Combustion Air System

HLA = Ducting system

HLB = Forced Draught fan, sealing air and penthouse pressurization fans HLC = Steam air heater

HLD = Regenerative air heater

HLV = Lubrication oil system for F.D. fan, P.A. fan and I.D.F. fan HN = Flue gas exhaust (without flue gas treatment)

N.º 1.2.060-PG-005-RL-2010 REV.: 1 FL.: 59 / 74 HNA = Ducting system

HNC = Induced Draught Fan system HNE = Chimney

HQ = Electrostatic precipitator

HY = Instrumentation and control equipment for boiler J = Nuclear heat generation

K = Reactor auxiliary systems

L = Steam, feedwater and condensate circuits (water-steam cycle) LA = Feedwater system

LAA = Feedwater tank and dearator

LAB = feed water piping (from feedwater tank outlet to to boiler inlet) LAC = Feedwater pump system

LAD = Feedwater preheating LAE = HP water injection system LAF = IP injection water system LB = Steam System

LBA = Live Steam piping system LBB = Hot Reheat Steam piping system LBC = Cold Reheat Steam piping system LBF = HP bypass

LBG = Auxiliary steam piping system

LBQ = Extraction steam piping system for feedwater preheating LBR = Auxiliary turbine piping system

LBS = Extraction steam piping system for main condensate heating and heat exchangers. LC = Condensate System

LCA = Main condensate piping system LCB = Main condensate pumping station LCC = Main condensate preheating LCE = Condensate injection water system

LCF = Auxiliary turbine condensate piping system LCG = Auxiliary turbine condensate pumping system LCH = feedwater heating condensate system

LCJ = Main condensate feedheating and heat exchanger condensate system LCM= Drains and vents of condensate system

LCN = Auxiliary steam condensate system

LCP = Stand-by condensate system including storage and conveyance LCQ = Steam generator blowdown

N.º 1.2.060-PG-005-RL-2010 REV.: 1 FL.: 60 / 74 LCN = Condensate seal water system

M= Main machine sets

MA = Steam turbine plant MAA = HP Turbine MAB = IP turbine MAC = LP turbine MAD = Bearings MAG = Condenser MAJ = Evacuation

MAK = Couplings between driving and driven machines (turbine-generator, shaft barring gear,..)

MAL = Draining and venting systems MAM= Steam extraction system (flanges) MAN = LP Bypass including injection MAP = Turbine start-up system MAV = Lubrication oil system

MAW = Sealing, exhaust, heating and cooling steam system

MAX = Non-electric control, regulation and protection equipment including medium supply MAY = Electric control, regulation and protection equipment

MK = Generator plant

MKA = Generator Stator and rotor

MKB = Exciter set including diodes or brush assembly MKC = Generator exciter set

MKD = Bearings

MKF = Water cooling system

MKG = Hydrogen cooling system and air cooler MKK = Power transmission coupling

MKW = Sealing oil system

MP = Common equipment for Turbine Generator Plant MPA = Foundation

MPB = Sheating

MPG = Frame, supports MPR = Forced Cooling System

MPS = Heating and Conservation equipment for maintenance purposes MV = Lubricating oil supply and storage

MVA = Oil storage and reticulation system

MVX = Non electric control, regulation and protection equipment including medium supply N = Process energy/fluid supply for external users

N.º 1.2.060-PG-005-RL-2010 REV.: 1 FL.: 61 / 74 P = Cooling water systems

PA = Circulating water system

PAA = Mechanical cleaning system (racks and screens) PAB = Piping

PAC = Circulating water pumping system PAD = Mechanical equipment of Cooling Tower PAH = Condenser cleaning system

PAV = Circulating Water pump Lube oil system PAY = Instrumentation and control

PB = Chemical conditioning of Circulating water system PBX = Piping

PBY = Control Equipment for conditioning system PC = Secondary Cooling Water System

PCB = Piping

PG = Closed Cooling water system PGA = Inlet Piping PGB = Return piping PGC = Pumping station PGD = Intermediate cooler PGK = Pressurizing system Q = Auxiliary systems

QC = Central Chemical Supply including storage QCA = Hydrazine supply and distribution QCC = Phosphate supply and distribution

QCD = Ammonia – hydrazine supply and distribution QCH = Chlorine supply and distribution

QCK = Piping and accessories~

QE = General compressed air and conveying air supply QEA = Service air generation

QEB = Service air distribution (not for boiler, not for turbine house) QEH = Service air distribution for boiler house

QEM = Service air distribution for turbine house QF = General Control Air

QFA = Central control air generation QFB = Central control air distribution

QFH = Control air distribution for boiler house QFM = Control air distribution for turbine house QG = Central gas supply for closed gas circuits

N.º 1.2.060-PG-005-RL-2010 REV.: 1 FL.: 62 / 74 QGA = Nitrogen supply and distribution

QGB = Hydrogen supply and distribution QGC = Carbon dioxide Supply and distribution QH = Auxiliary steam generation

QL = Feedwater, steam and condensate circuits for auxiliary steam generation QU = Sampling systems and chemical continuous monitoring of the unit

QUA = sampling points of feedwater system QUB = sampling points of steam system QUC = sampling points of condensate system QUE = sampling points of auxiliary steam system QUG = sampling points of water supply system QUH = sampling points of main boiler drum system QUK = sampling interconnection piping

QUQ = sampling points of auxiliary systems excluding QUE

QUY = Equipment for control and regulation of the sampling systems and chemical continuous monitoring.

S = Common systems SA = HVAC system

SAA = HVAC for main buildings

SAB = HVAC for Secondary buildings (fuel oil, compressed air, diesel, …)

SAC = HVAC for Auxiliary buildings (Administrative, Labs, Workshop, social, gate) SAD = HVAC for coal and ash plant

SAE = HVAC for Cooling water systems and chlorination plant SG = Stationary fire fighting system

SGA = Stationary fire fighting water storage, pumping and distribution system SGK = Fire fighting halon system

SM = Cranes, lifting gears and handling equipment

SMG = Lifting gear for secondary buildings (Demineralization) SMM = Crane for Turbine Building

SMQ = Crane for Circulating water pumping house SMS = Crane for workshop and stores

SN = Elevators

SNB = Elevator for electrical building SNH = Elevator for boiler house SNM = Elevator for Turbine building SNY = Elevator for Administrative building U = Structures

N.º 1.2.060-PG-005-RL-2010 REV.: 1 FL.: 63 / 74 UAA = Structure of Outdoor switchgear (220 kV)

UAB = Structure of Outdoor switchgear (60 kV) UAE = Ambient Monitoring building

UAG = Oil retention pits for unit transformers

UAY = Electrical Tower Foundations of high voltage lines UAZ = Cables galleries

UB = Structures for power distribution and auxiliary power supply UBA = Electrical Building

UBB = Building for general electrical services UBE = Auxiliary transformers 20/6,6 kV UBF = Main Transformer 20/220 kV UBH = oil retention pits for transformers UBJ = Structures for main transformer tracks UBN = diesel building

UBQ = structure for diesel fuel supply UBZ = structures for cable and channel UE = Structures for fuel oil, coal and ash handling

UEA = Emergency storage (harbour) UEB = Coal site storage

UEF = Coal transfer tower UEH = Fuel-oil installation

UEJ = Fuel-oil tanks and retention basin UG = Structures for water supply and disposal

UGA = Raw Water tank

UGD = Water treatment plant incl. Demineralization plant UGE = Neutralization basin

UGF = Fire fighting system UGG = Potable water UGK = Pre-treatment plant UGN = Demineralization tanks

UGP = Basins for Domestic wastes treatment UGR = Waste water tanks

UGU = Networks collecting for waste water UGV = Supports for air conduits

UGZ = Galleries and channels

UH = Structures for Boiler, intermediate building, precipitators and FGD UHA = Boiler house

N.º 1.2.060-PG-005-RL-2010 REV.: 1 FL.: 64 / 74 UHL = Fans and air/flue gas heaters

UHN = Chimney UHQ = Precipitators UHT = FGD

UHY = Conduits supports UHZ = Galleries and channels UM = Structures of Turbine generator plant

UMA = Turbine building UMZ = Galleries and channels UP = Structures for cooling water system

UPA = Marine intake structures

UPC = Water intake and pumping station UPD = Structures for main inlet piping UPN = Structures for piping distribution UPZ = Galleries and channels

UQ = Structures for cooling water system UQA = Circulating water pumps house UQB = intake pressure conduits

UQY = structures for cooling water conduits UQZ = Galleries and channel

UR = Cooling Towers system URA = Cooling tower

URG = Water compensation conduits URH = Main inlet piping

URK = Main outlet piping

URM = Cooling tower equipment supports URN = Cooling tower by-pass

URP = Cooling tower overflow and drainage US = Auxiliary buildings

USG = waste Pumping station UST = Workshop

USU = storage USV = Laboratory

UT = Structures for auxiliary plants UTF = Air compressor building UTG = Gases (CO2, H2, ..) UTH = Auxiliary boiler

N.º 1.2.060-PG-005-RL-2010 REV.: 1 FL.: 65 / 74 UTS = Chemical products storage

UX = General Structures (Power plant Outside) UXX = Train and road connection UXY = Bridges

UY = General Service Structures UYB = Social building

UYC = Administrative building, laboratories UYD = Canteen

UYE = Gate house

UYG = Public relations Point

UYJ = First aid and medical services UYP = Fire fighting station

UYQ = Garage

UZ = Structures for transport, traffic, fencing, garden, other purposes UZA = Site roads

UZC = Yards UZD = parking lots UZE = Railways

UZJ = Fencing and eventual inlets UZK = Environmental layout incl. trees UZY = bridges

UZZ = underground and channel conduits X = Heavy machinery (not main machine sets)

XJ = Diesel engine plant

XJG = Cooling water system XJN = Fuel oil system

XJP = compressed air starting system XJV = Lubricating oil system

XK = Generator plant for emergency diesel

XKA = Diesel Generator set (incl. stator, rotor and all integral cooling equipment) XLA = Electrical feed pump

N.º 1.2.060-PG-005-RL-2010 REV.: 1 FL.: 66 / 74

10.1.2

Level 2 – Equipment Unit Code

Examples A Mechanical equipment

AA = Valves, dampers, etc., incl. Actuators, also manual AC = Heat exchangers

AN = Compressor, fan units AP = Pump units

AU = Braking, gearbox, coupling equipment, non-electrical converters AS = Adjusting and tensioning equipment for non-electrical variables AT = Cleaning, drying, filtering, separation equipment

B Mechanical equipment BB = Vessels

BF = Foundations BR = Piping

BN = Jet pumps, injectors BQ = Supports

C Direct measuring circuits (following DIN 19227 part 1, 1973 edition) CD = Density

CF = Flow rate CP = Pressure CR = radiation

D Closed loop control circuits (following DIN 19227 part 1, 1973 edition) DD = Density

DF = Flow, rate DP = Pressure

E Analogue and binary signal conditioning

EA = open loop control – control of the functional group EE = open loop control – software of the functional group EG = Alarm, annunciation – priority alarms

G Electrical, instrumentation and control equipment

GA = Junction boxes and cable/bus bar penetrations - binary signals of the marshling cubicle