FM 355 closed-loop control modules

In document 6ES BE01-0AB0 6ES BE01-0AB0 (Page 107-110)

4

Overview

• 4-channel loop control module for universal closed-loop control tasks

• Used for temperature, pressure, flowrate and fill-level control loops

• User-friendly online self-optim ization for temperature controls

• Preprogrammed controller structures

• 2 control algorithms

• 2 versions:

- FM 355 C as continuous-action controller;

- FM 355 S as step or pulse controller

• With 4 analog outputs (FM 355 C) or 8 digital outputs (FM 355 S) for direct control of the most common types of actuator

• Continued operation of the contro l loop is possible even after a CPU stop or failure

Technical specifications

6ES7 355-0VH10-0AE0

6ES7 355-1VH10-0AE0 Voltages and currents

Load voltage L+

- Rated value (DC) 24 V 24 V

- permissible range, lower limit (DC)

20.4 V 20.4 V

- permissible range, upper limit (DC)

28.8 V 28.8 V

Current consumption

• from load voltage L+ (no load),

• Power dissipation, max. 7.8 W 6.9 W

• Power dissipation, typical 6.5 W 5.5 W Connection system

• Requisite front connector 2 x 20-pin 2 x 20-pin Digital inputs

• Number of digital inputs 8 8

Length of cable

- Length of cable shielded, max. 1,000 m 1,000 m - Length of cable unshielded,

max.

600 m 600 m

• Input characteristic to comply with IEC 1131, Type 2

Yes Yes Digital outputs

• Number of digital outputs 8

• Length of cable shielded, max. 1,000 m

• Length of cable unshielded, max. 600 m

• Short-circuit protection of the

output Yes;

electronic

• Limitation of voltage induced on circuit interruption to

L+ (-1.5 V)

• Lamp load, max. 5 W

• Driving a digital input Yes

Output voltage

- for 1 signal L+ (-2.5 V)

Output current

- for 1 signal rated value 100 mA

- for 1 signal permissible range

for 0 to 60 °C, min. 5 mA

- for 1 signal permissible range for 0 to 60 °C, max.

150 mA - for 0 signal residual current, max. 0.5 mA Parallel switching of 2 outputs

- for logical links Yes

Switching frequency

- at resistive load, max. 100 Hz

- at inductive load, max. 0.5 Hz

- at lamp load, max. 100 Hz

Summation current of the outputs (per group)

- up to 60 °C, max. 400 mA

Load impedance range

- lower limit 240 Ω

- upper limit 4 kΩ

Function modules

FM 355 closed-loop control modules

4

Technical specifications (continued) 6ES7 355-0VH10-0AE0

6ES7 355-1VH10-0AE0 Analog inputs

• Number of analog inputs 4 4

• Length of cable shielded, max 200 m; 50m at 80 mV and thermocouples

200 m; 50m at 80 mV and thermocouples

• Permissible input voltage for the voltage input (destruction limit), max.

30 V 30 V

• Permissible input voltage for the current input (destruction limit), max.

40 mA 40 mA

Input ranges (rated values), voltages

- 0 to +10 V Yes Yes

- -1.75 to +11.75 V Yes Yes

- -80 mV to +80 mV Yes Yes

Input ranges (rated values), currents

- 0 to 20 mA Yes Yes

- 0 to 23.5 mA Yes Yes

- -3.5 to +23.5 mA Yes Yes

- 4 to 20 mA Yes Yes

Input ranges (rated values), thermocouples

Input ranges (rated values), resistance thermometer

- Pt 100 Yes Yes

Characteristic curve linearization

- parameterizable Yes Yes

- for thermocouples Typ B, J, K, R, S Typ B, J, K, R, S - for resistance thermometer Pt 100

(Standard)

Pt 100 (Standard) Temperature compensation

- external temperature compensation with Pt100

Yes Yes

- internal temperature compensation possible

Yes Yes

Analog outputs

• Number of analog outputs 4

• Length of cable shielded, max 200 m;

50m at 80 mV and thermo-couples

• Voltage output, short-circuit protection

Yes

• Voltage output, short-circuit current, max

25 mA

• Current output, open-circuit voltage, max. Analog outputs (continued)

Output ranges, voltage

- 0 to 10 V Yes

- -10 to +10 V Yes

Output ranges, current

- 0 to 20 mA Yes

- 4 to 20 mA Yes

Actuator connection - for voltage output 2-wire

connection Yes

- for current output 2-wire connection

Yes Burden resistance

(in the nominal output range)

- at voltage outputs, min. 1 kΩ - at voltage outputs, capacitive

load, max.

1 µF - at current outputs, max. 500 Ω - at current outputs, inductive

load, max. 1 mH

Analog value formation

• Measuring principle integrating integrating Integration and conversion

time/triggering per channel - with over-range (bits incl. sign),

max. - Conversion time (per channel) 16.67 ms;

at 12 bits:

- for resistive load 0.1 ms 0.1 ms

- for capacitive load 3.3 ms 3.3 ms

- for inductive load 0.5 ms 0.5 ms

Sensor

Sensing element connection

- for voltage measurement Yes Yes

- for current measurement, as 4-wire measuring transducer

Yes Yes

Connectable encoders

- 2-wire BEROS Yes Yes

- permissible closed-circuit current (2-wire BEROS), max.

1.5 mA 1.5 mA

Function modules

FM 355 closed-loop control modules

4

Technical specifications (continued)

Ordering data Order No. Order No.

6ES7 355-0VH10-0AE0

6ES7 355-1VH10-0AE0 Error/accuracies

• Linearity error

(relative to the output range)

+/- 0.05 %

• Linearity error

(relative to the input range)

+/- 0.05 % +/- 0.05 %

• Temperature error

(relative to the output range)

+/- 0.02 %/K

• Temperature error (relative to the input range)

+/- 0.005 %/K +/- 0.005 %/K Operational limit in the entire

temperature range

- Relative to the output range, voltage

+/- 0.5 % - Relative to the output range,

current

+/- 0.6 % - relative to the input range,

voltage +/- 0.6 %;

+/-0.6 to +/-1%

+/- 0.6 %;

+/-0.6 to +/-1%

- relative to the input range,

current +/- 0.6 %;

+/-0.6 to +/-1%

+/- 0.6 %;

+/-0.6 to +/-1%

- relative to the input range,

resistance thermometer +/- 0.6 %;

+/-0.6 to +/-1%

+/- 0.6 %;

+/-0.6 to +/-1%

Basic error limit

(operational limit at 25 °C) - relative to the output range,

voltage +/- 0.2 %

- relative to the output range, current

+/- 0.3 % - relative to the input range,

voltage +/- 0.4 %;

- relative to the input range,

current +/- 0.4 %;

- relative to the input range,

resistance thermometer +/- 0.4 %;

+/-0.4 to

Interference voltage suppression for f = n x (fl +/- 1 %)

- Series-mode interference (peak value of interference <

rated value input range

40 dB 40 dB

- Common-mode interference

(USS < 2.5 V) , min. 70 dB 70 dB

Control engineering

• Number of controllers 4 4

Status information/

interrupts/ diagnostics

• Applying substitute values Yes;

• Insulation tested with 500 V DC 500 V DC Potentials/ electrical isolation

Electrical isolation, controller

- between the channels No No

- between the channels and the backplane bus

Yes; Optocou-pler

Yes; Optocou-pler

Permissible potential difference

• between the in puts and MANA (UCM)

2.5 V DC 2.5 V DC

• between Minternal and the inputs 75 V DC / 60 V AC

75 V DC / 60 V AC Dimensions and weight

• Weight, approx. 470 g 470 g

• Width 80 mm 80 mm

• Height 125 mm 125 mm

• Depth 120 mm 120 mm

FM 355 C controller module 6ES7 355-0VH10-0AE0 With 4 analog outputs for

4 continuous-action controllers

FM 355 S controller module 6ES7 355-1VH10-0AE0 With 8 digital outputs for

4 step or pulse controllers FM 355 manual

German 6ES7 355-0VH00-8AA0

English 6ES7 355-0VH00-8BA0

French 6ES7 355-0VH00-8CA0

Italian 6ES7 355-0VH00-8EA0

Front connector

20-pin, with screw-type terminals

• 1 item 6ES7 392-1AJ00-0AA0

Labeling strip 6ES7 392-2XX00-0AA0 10 units (spare part)

S7-SmartLabel 2XV9 450-1SL01-0YX0

Software for machine labeling of modules directly from the STEP 7 project

Labeling sheets for machine labeling

see "Accessories"

Slot number label 6ES7 912-0AA00-0AA0 Spare part

Shield connecting element 6ES7 390-5AA00-0AA0 80 mm wide, with 2 rows

or 4 terminal elements each Terminal elements 2 units

Function modules

FM 355-2