Overview• 4-channel loop control module for universal closed-loop control tasks
• Used for temperature, pressure, flowrate and fill-level control loops
• User-friendly online self-optim ization for temperature controls
• Preprogrammed controller structures
• 2 control algorithms
• 2 versions:
- FM 355 C as continuous-action controller;
- FM 355 S as step or pulse controller
• With 4 analog outputs (FM 355 C) or 8 digital outputs (FM 355 S) for direct control of the most common types of actuator
• Continued operation of the contro l loop is possible even after a CPU stop or failure
■
Technical specifications6ES7 355-0VH10-0AE0
6ES7 355-1VH10-0AE0 Voltages and currents
Load voltage L+
- Rated value (DC) 24 V 24 V
- permissible range, lower limit (DC)
20.4 V 20.4 V
- permissible range, upper limit (DC)
28.8 V 28.8 V
Current consumption
• from load voltage L+ (no load),
• Power dissipation, max. 7.8 W 6.9 W
• Power dissipation, typical 6.5 W 5.5 W Connection system
• Requisite front connector 2 x 20-pin 2 x 20-pin Digital inputs
• Number of digital inputs 8 8
Length of cable
- Length of cable shielded, max. 1,000 m 1,000 m - Length of cable unshielded,
max.
600 m 600 m
• Input characteristic to comply with IEC 1131, Type 2
Yes Yes Digital outputs
• Number of digital outputs 8
• Length of cable shielded, max. 1,000 m
• Length of cable unshielded, max. 600 m
• Short-circuit protection of the
output Yes;
electronic
• Limitation of voltage induced on circuit interruption to
L+ (-1.5 V)
• Lamp load, max. 5 W
• Driving a digital input Yes
Output voltage
- for 1 signal L+ (-2.5 V)
Output current
- for 1 signal rated value 100 mA
- for 1 signal permissible range
for 0 to 60 °C, min. 5 mA
- for 1 signal permissible range for 0 to 60 °C, max.
150 mA - for 0 signal residual current, max. 0.5 mA Parallel switching of 2 outputs
- for logical links Yes
Switching frequency
- at resistive load, max. 100 Hz
- at inductive load, max. 0.5 Hz
- at lamp load, max. 100 Hz
Summation current of the outputs (per group)
- up to 60 °C, max. 400 mA
Load impedance range
- lower limit 240 Ω
- upper limit 4 kΩ
Function modules
FM 355 closed-loop control modules
4
■
Technical specifications (continued) 6ES7 355-0VH10-0AE06ES7 355-1VH10-0AE0 Analog inputs
• Number of analog inputs 4 4
• Length of cable shielded, max 200 m; 50m at 80 mV and thermocouples
200 m; 50m at 80 mV and thermocouples
• Permissible input voltage for the voltage input (destruction limit), max.
30 V 30 V
• Permissible input voltage for the current input (destruction limit), max.
40 mA 40 mA
Input ranges (rated values), voltages
- 0 to +10 V Yes Yes
- -1.75 to +11.75 V Yes Yes
- -80 mV to +80 mV Yes Yes
Input ranges (rated values), currents
- 0 to 20 mA Yes Yes
- 0 to 23.5 mA Yes Yes
- -3.5 to +23.5 mA Yes Yes
- 4 to 20 mA Yes Yes
Input ranges (rated values), thermocouples
Input ranges (rated values), resistance thermometer
- Pt 100 Yes Yes
Characteristic curve linearization
- parameterizable Yes Yes
- for thermocouples Typ B, J, K, R, S Typ B, J, K, R, S - for resistance thermometer Pt 100
(Standard)
Pt 100 (Standard) Temperature compensation
- external temperature compensation with Pt100
Yes Yes
- internal temperature compensation possible
Yes Yes
Analog outputs
• Number of analog outputs 4
• Length of cable shielded, max 200 m;
50m at 80 mV and thermo-couples
• Voltage output, short-circuit protection
Yes
• Voltage output, short-circuit current, max
25 mA
• Current output, open-circuit voltage, max. Analog outputs (continued)
Output ranges, voltage
- 0 to 10 V Yes
- -10 to +10 V Yes
Output ranges, current
- 0 to 20 mA Yes
- 4 to 20 mA Yes
Actuator connection - for voltage output 2-wire
connection Yes
- for current output 2-wire connection
Yes Burden resistance
(in the nominal output range)
- at voltage outputs, min. 1 kΩ - at voltage outputs, capacitive
load, max.
1 µF - at current outputs, max. 500 Ω - at current outputs, inductive
load, max. 1 mH
Analog value formation
• Measuring principle integrating integrating Integration and conversion
time/triggering per channel - with over-range (bits incl. sign),
max. - Conversion time (per channel) 16.67 ms;
at 12 bits:
- for resistive load 0.1 ms 0.1 ms
- for capacitive load 3.3 ms 3.3 ms
- for inductive load 0.5 ms 0.5 ms
Sensor
Sensing element connection
- for voltage measurement Yes Yes
- for current measurement, as 4-wire measuring transducer
Yes Yes
Connectable encoders
- 2-wire BEROS Yes Yes
- permissible closed-circuit current (2-wire BEROS), max.
1.5 mA 1.5 mA
Function modules
FM 355 closed-loop control modules
4
■
Technical specifications (continued)■
Ordering data Order No. Order No.6ES7 355-0VH10-0AE0
6ES7 355-1VH10-0AE0 Error/accuracies
• Linearity error
(relative to the output range)
+/- 0.05 %
• Linearity error
(relative to the input range)
+/- 0.05 % +/- 0.05 %
• Temperature error
(relative to the output range)
+/- 0.02 %/K
• Temperature error (relative to the input range)
+/- 0.005 %/K +/- 0.005 %/K Operational limit in the entire
temperature range
- Relative to the output range, voltage
+/- 0.5 % - Relative to the output range,
current
+/- 0.6 % - relative to the input range,
voltage +/- 0.6 %;
+/-0.6 to +/-1%
+/- 0.6 %;
+/-0.6 to +/-1%
- relative to the input range,
current +/- 0.6 %;
+/-0.6 to +/-1%
+/- 0.6 %;
+/-0.6 to +/-1%
- relative to the input range,
resistance thermometer +/- 0.6 %;
+/-0.6 to +/-1%
+/- 0.6 %;
+/-0.6 to +/-1%
Basic error limit
(operational limit at 25 °C) - relative to the output range,
voltage +/- 0.2 %
- relative to the output range, current
+/- 0.3 % - relative to the input range,
voltage +/- 0.4 %;
- relative to the input range,
current +/- 0.4 %;
- relative to the input range,
resistance thermometer +/- 0.4 %;
+/-0.4 to
Interference voltage suppression for f = n x (fl +/- 1 %)
- Series-mode interference (peak value of interference <
rated value input range
40 dB 40 dB
- Common-mode interference
(USS < 2.5 V) , min. 70 dB 70 dB
Control engineering
• Number of controllers 4 4
Status information/
interrupts/ diagnostics
• Applying substitute values Yes;
• Insulation tested with 500 V DC 500 V DC Potentials/ electrical isolation
Electrical isolation, controller
- between the channels No No
- between the channels and the backplane bus
Yes; Optocou-pler
Yes; Optocou-pler
Permissible potential difference
• between the in puts and MANA (UCM)
2.5 V DC 2.5 V DC
• between Minternal and the inputs 75 V DC / 60 V AC
75 V DC / 60 V AC Dimensions and weight
• Weight, approx. 470 g 470 g
• Width 80 mm 80 mm
• Height 125 mm 125 mm
• Depth 120 mm 120 mm
FM 355 C controller module 6ES7 355-0VH10-0AE0 With 4 analog outputs for
4 continuous-action controllers
FM 355 S controller module 6ES7 355-1VH10-0AE0 With 8 digital outputs for
4 step or pulse controllers FM 355 manual
German 6ES7 355-0VH00-8AA0
English 6ES7 355-0VH00-8BA0
French 6ES7 355-0VH00-8CA0
Italian 6ES7 355-0VH00-8EA0
Front connector
20-pin, with screw-type terminals
• 1 item 6ES7 392-1AJ00-0AA0
Labeling strip 6ES7 392-2XX00-0AA0 10 units (spare part)
S7-SmartLabel 2XV9 450-1SL01-0YX0
Software for machine labeling of modules directly from the STEP 7 project
Labeling sheets for machine labeling
see "Accessories"
Slot number label 6ES7 912-0AA00-0AA0 Spare part
Shield connecting element 6ES7 390-5AA00-0AA0 80 mm wide, with 2 rows
or 4 terminal elements each Terminal elements 2 units