• No results found

Graphical techniques

In document High voltage engineering.pdf (Page 194-200)

Partial discharges and their measurement

4.3 Partial discharge measurement

4.3.4.3 Graphical techniques

As a consequence of IEC Code 599 being inconsistent in producing reliable diagnoses, additional schemes were introduced to complement the Code.

CH4/H2 C2H6/CH4 C2H4/C2H6 C2H2/C2H4

Range Code Range Code Range Code Range Code

≤0.1 5 <1 0 <1 0 <0.5 0

>0.1 < 1 0 ≥1 1 ≥ 1 < 3 1 ≥ 0.5 < 3 1

≥ 1 < 3 1 ≥3 2 ≥3 2

≥3 2

Code Diagnosis

CH4 H2

C2H6 CH4

C2H4 C2H6

C2H2 C2H4

0 0 0 0 normal

5 0 0 0 partial discharge

1, 2 0 0 0 slight overheating <150C 1, 2 1 0 0 slight overheating 150–200C

0 1 0 0 slight overheating 200–300C

0 0 1 0 general conductor overheating

1 0 1 0 winding circulating currents

1 0 2 0 core and tank circulating currents, overheated joints

0 0 0 1 flashover, no power follow through

0 0 1, 2 1, 2 arc, with power follow through

0 0 2 2 continuous sparking to floating potential 5 0 0 1, 2 partial discharge with tracking (note CO) CO2/CO > 11 higher than normal temperature in insulation

Figure 4.11 Rogers fault gas ratios (code based on Joseph B. DiGiorgio’s ‘Dissolved gas analysis of mineral oil insulating fluids’, published by NTT 1996–2002)

Duval [70] developed a triangle, Figure 4.15, based on the relative percentage of methane, ethylene and acetylene gas. The triangle is divided into six regions representing high energy arcing, low energy arcing, corona discharge and hot spots.

The triangle has the advantage that a diagnosis is always given – but, of course, this will always imply a fault! Hence it must only be used in conjunction with individual levels of gases which imply the possibility of a fault.

Other graphical techniques include the Church Nomograph Method, based on data published by Dornenburg and Strittmatter. The data are plotted on sliding loga-rithmic scales, with each scale representing a different gas. Data points are then joined together and the slope of the line between adjacent scales is indicative of the type of fault.

Code Diagnosis

<1.0 < 1.0 <1.0 <0.5 normal

≤0.1 <1.0 <1.0 <0.5 partial discharge – corona

≤0.1 <1.0 <1.0 ≥0.5

<3.0or >3.0 partial discharge – corona with tracking

>0.1

<0.1 <1.0 ≥3.0 ≥3.0 continuous discharge

>1.0

<0.1 <1.0 ≥1.0

<3.0or >3.0 ≥0.5

<3.0or >3.0 arc – with power follow through

>1.0

<0.1 <1.0 <1.0 ≥0.5

<3.0 arc – no power follow through

≥1.0

<3.0or >3.0 <1.0 <1.0 <0.5 slight overheating – to 150C

≥1.0

<3.0or >3.0 ≥1.0 <1.0 <0.5 overheating 150–200C

>0.1

<1.0 ≥1.0 <1.0 <0.5 overheating 200–300C

>0.1

<3.0 <0.5 circulating currents in windings

>1.0

<3.0 <1.0 ≥3.0 <0.5 circulating currents core and tank; overload joints

Note: several simultaneously occurring faults can cause ambiguity in analysis

Figure 4.12 Rogers fault gas ratios (ratio value based) (based on Joseph B.

DiGiorgio’s ‘Dissolved gas analysis of mineral oil insulating fluids’, published by NTT, 1996–2002)

As can be imagined, artificial intelligence in the form of expert systems, artificial neural networks and fuzzy-logic-based systems are finding increasing application in this area.

Before leaving chemical detection of partial discharges, it is appropriate to note that for oil/paper insulated plant, the detection of degradation byproducts of the paper

C2H2/C2H4 CH4/H2 C2H4/C2H6

0 0 0 no fault normal ageing

0 1 0 partial discharges of discharges in gas filled cavities low energy density resulting from incomplete

impregnation, or supersaturation or high humidity

1 1 0 partial discharges of as above, but leading to tracking high energy density or perforation of solid insulation 1→ 2 0 1→ 2 discharges of continuous sparking in oil

low energy between bad connections of different potential or to floating potential; breakdown of oil between solid materials

1 0 2 discharges of discharges with power follow

high energy through; arcing – breakdown of oil between windings or coils or between coils to earth;

selector breaking current

0 0 1 hot spots general insulated

T <150C conductor overheating

0 2 0 hot spots

150C < T < 300C

local overheating of the core due to concentrations of flux;

increasing hot spot temperatures;

varying from small hot spots in core, shorting links in core, overheating of copper due to eddy currents, bad contacts/joints (pyrolitic carbon formation) upto core and tank circulating currents

0 2 1 hot spots

300C < T < 700C

0 2 2 hot spots

T >700C

Figure 4.13 IEC 599 1978 fault gas ratios1

Case Characteristic fault C2H2 C2H4

CH4

H2

C2H4 C2H6 PD partial discharges NS1 <0.1 <0.2

(see notes 3 and 4)

D1 discharges of low energy >1 0.1–0.5 >1 D2 discharges of high energy 0.6–2.5 0.1–1 >2 T1 thermal fault T < 300C NS1 >1 but NS1 <1

T2 thermal fault <0.1 >1 1–4

300C < T < 700C

T3 thermal fault T > 700C <0.22 >1 >4

note 1 – in some countries, the ratio C2H2/C2H6is used, rather than the ratio CH4/ H2, also in some countries, slightly different ratio limits are used

note 2 – the above ratios are significant and should be calculated only if at least one of the gases is at a concentration and a rate of gas increase above typical values

note 3 – CH4/H2< 0.2 for partial discharges in instrument transformers; CH4/H2<0.07 for partial discharges in bushings

note 4 – gas decomposition patterns similar to partial discharges have been reported as a result of the decomposition of thin oil film between overheated core laminates at temperatures of 140C and above

1NS= non-significant whatever the value

2an increasing value of the amount of C2H2/C2H6may indicate that the hot spot temperature is higher than 1000C

Figure 4.14 IEC 60599 1999 edition fault gas ratios interpretation1

in the oil may also imply the presence of partial discharges. Paper degrades to form several furans and these can be detected using various techniques of oil analysis.

Although absolute levels of these byproducts are important, as with DGA, as the ratios of the different byproducts may prove more important in the longer term. It has been argued that, from these ratios, the temperature resulting in the paper degrading can be inferred and, in turn from this, the integrity of the paper [71–74]. Given that the temperature of the fault can be inferred, as with DGA, it should be possible to infer the presence (and, indeed, type) of partial discharges. However, this form of monitoring is not nearly so well established as DGA; the relationship to the detection of partial discharges has yet to be made. However, it is a potential technique for the future and most people would now analyse an oil sample for both gas and furan content.

4.3.5 Comparison among different PD measurement techniques relative to type of plant under investigation

From the foregoing it can be seen that, in general terms, most types of measurement of PD can be made on most types of plant – with some obvious exceptions as mentioned

T1

T2

D2

T3 D1

D + T

% CH4 % C2H4

% C2H2 80

80 60 40 20 60

40

20 80

60 40 PD

20

Key: partial discharges discharges of low energy discharges of high energy thermal fault, T < 300°C thermal fault, 300 °C < T < 700°C thermal fault, T > 700°C PD

D1 D2 T1 T2 T3

Limits of zones PD 98% CH4

D1 23% C2H4 13% C2H2

D2 23% C2H4 13% C2H2 38% C2H4 29% C2H2 T1 4% C2H2 10% C2H4

T2 4% C2H2 10% C2H4 50% C2H4 T3 15% C2H2 50% C2H4

triangle coordinates:

%C2H4= 100x

x+ y + z %C2H4= 100y

x+ y + z %CH4= 100z x+ y + z where x= C2H2 y= C2H4 z= CH4in p.p.m.

Figure 4.15 IEC 60599 1999 edition Duval’s triangle1

PD measurement technique

Type of IEPD tan δ C.T. capacitive antenna acoustic chemical thermography,

plant probes etc.

Generators    

Circuit   

breaker boxes

Transformers     ∗∗

Motors    

Cable end boxes  

Bushings   

Capacitors    ∗∗

CVTs     ∗∗

Overhead 

busbars, insulators, etc.

provided the plant item is air-cooled (i.e. has access vents)

∗∗provided the plant item is oil filled

Figure 4.16 A comparison of different PD measurement techniques in relation to various items of plant

in the text. The decision on which to choose in a given situation becomes a balanc-ing act among the costs of plant failure (includbalanc-ing health and safety considerations, replacement/repair costs and outage losses), the cost in making a given measurement (including the frequency of measurement dictated over given time periods and the cost of potential outages dictated by the need to make solid connections with some measurement systems) and the quality of information provided by the technique. This type of decision is unique in each situation. However, for those embarking on the measurement of PD for their plant, the table shown in Figure 4.16 may prove helpful.

4.3.6 Other items of plant

In addition to the various types of plant highlighted in the foregoing sections, there are two other plant systems which, because of their specialist nature, have had evolved for them special techniques to measure PD. This is not to say that they cannot utilise the techniques described earlier, merely that better techniques are available specifically related to them. The two items of plant are cables and gas-insulated substations (GIS).

4.3.6.1 Cables

Although other techniques can be applied to cables with limited success in PD mea-surements, the technique described as cable mapping [75] has evolved specifically for use with cables where not only is the magnitude and nature of PD required but also their location. Without location, refurbishment of a plant item hidden underground and extending potentially over many kilometres would be extremely daunting.

In document High voltage engineering.pdf (Page 194-200)