• No results found

Image ‐ Maximum vertical viewing angle

Image ‐ Maximum vertical viewing angle 

15.2. Projection Surfaces 

Projection should ideally be directly onto a flat wall. All new buildings should be constructed with a  flat display wall suitable for projection. The wall should be clean and painted flat (matt) white and be  uniformly flat and perpendicular to the projector and the audience. 

For existing installation refurbishments where there is not a suitable wall for projection in the room,  a motorised drop‐down projection screen is permitted.  

Whiteboards  are  generally  not  suitable  to  use  as  a  projection  screen  as  the  shiny  surface  causes  unacceptable  glare  and  hot‐spotting.  Where  whiteboard  surfaces  are  used  for  projection  (for  example  in  an  interactive  whiteboard  installation  with  an  ultra‐short  throw  projector),  the  whiteboard needs to be non‐gloss type suitable for projection. 

15.3. Lectern and Presenter Desks 

The University has developed standard lectern designs, intended for use in all lecture theatres and  classrooms.  The  lectern  design  is  standardised  in  a  spatial  sense,  however  the  outer  skin  can  be  modified to match the architectural design and aesthetic of individual spaces. 

Liaise directly with LTU ICT/AV for the current standard lectern designs. 

15.4. Room Acoustics 

Room acoustics that support intelligible communication with all participants is of critical importance  in  all  teaching  spaces.  Special  consideration  must  be  given  to  the  design  of  teaching  spaces  with  regards to acoustic performance. The choice of room size, shape, layout, construction, materials and  finishes should be chosen carefully to provide spaces with the required acoustic performance for the  intended use. 

Ambient Sound Levels and Reverberation Times 

The design sound levels and reverberation times for all rooms and spaces should be in accordance  with the Noise Rating & RT60 defined in Australian Standard AS 2107. 

Speech Intelligibility 

Speech  intelligibility  as  quantified  by  the  Speech  Intelligibility  Index  (STI)  that  measures  in  the 

“excellent”  range  0.75‐1.0  should  be  achieved  at  the  listening  position  for  all  teaching  spaces.  In  large lecture theatres or open teaching spaces an STI that measures in the “good” range 0.60‐0.75 is  acceptable. 

Mechanical Services and Air Conditioning 

The level of ambient noise from air‐conditioning, ventilation and other  mechanical equipment can  pose  significant  challenges  to  acoustic  performance.  High  capacity  air  handling  systems  should  typically operate at low velocity to minimise noise. Air handling systems with Fan Coil Units (FCUs) 

15.5. Room Lighting 

Careful lighting design (selection, arrangement and control of light fittings) is critical for a successful  presentation and teaching venue so that presentation materials can be easily read and the presenter  clearly seen by the audience and the camera.  

It is important that the lighting design addresses the following objectives: 

Control of ambient light so that the image is not washed out 

Provide task lighting for students 

Illuminate the presenter and presentation area 

Lighting fittings should be selected that provide a high degree of direction control and avoid glare. 

Lighting  should  be  divided  into  zones  so  that  front  lights  that  spill  directly  onto  the  screen  can  be  dimmed (or separately switched) to prevent the image from becoming washed out and difficult to  read.  Task  lighting  and  spot  lights  should  be  used  to  properly  illuminate  the  presenter  and  presentation area. 

Generally  a  lighting  control  system  should  be  provided  for  flexible  and  easy‐to‐use  control  of  the  room lighting from the presenter position. This often involves integration of the lighting control with  the AV control system. 

Actual lighting levels must meet the requirements of Australian Standards AS 1680 and the Building  Code of Australia. 

15.6. Motorised Blinds 

For teaching spaces with projection systems, special consideration should be given to the control of  natural  ambient  light  by  limiting  the  use  of  windows  and  glazing.  Where  windows  and  glazing  is  present, the use of curtains and blinds will be required for control of ambient and spilled light falling  on  the  projection  screen  is  essential  in  all  spaces  with  projection  so  that  the  image  will  not  be  washed out or difficult to read.  

For spaces with video conference systems complete control of ambient light is needed and black out  blinds are recommended. 

Control of the motorised blinds or curtains from the presenter position often involves integration of  the blinds control with the AV control system. 

15.7. Emergency Evacuation 

Emergency evacuation systems may require the room sound system to be muted in the event of a  building  fire  alarm.  Advice  should  be  sought  from  the  Fire  Engineer  as  to  what  is  required  of  the  sound system in relation to evacuation alarms/announcements. 

 

16. EQUIPMENT RACKS  16.1. Equipment Racks 

All audio visual equipment should be installed into purpose built, lockable and ventilated equipment  racks. 

16.2. Joinery 

All  audio  visual  equipment  needs  to  be  accessible  for  routine  maintenance  as  well  as  repairs  for  equipment failure.  

Where equipment racks are installed inside joinery, front and rear access doors should be provided  to allow removal of the rack without disassembly. Where rear access cannot be provided, the rack  should be installed with castor wheels to allow removal for service.  

Adequate clearance must be provided inside joinery for equipment racks, access, audio visual cable  looms,  power  and  data  distribution  and  ventilation.  Provide  minimum  150mm  clear  space  behind  the equipment racks inside joinery. 

16.3. Ventilation 

Where  equipment  racks  are  installed  inside  joinery,  adequate  cooling  and  ventilation  must  be  provided  to  ensure  that  all  equipment  operates  within  the  recommended  operating  temperature  band. 

For  small  equipment  racks  with  minimum  equipment  natural  convection  is  often  adequate.  To  facilitate  natural  convection  must  be  ventilated  with  provision  to  draw  air  in  at  the  bottom  and  release air at the top. 

For large equipment racks with critical equipment installed, a cooling system should be considered. 

 

17. CABLING STANDARDS  17.1. Cabling and Connections 

All  cabling  materials  and  workmanship  shall  comply  with  the  relevant  Australian  Standards,  the  Building Code of Australia and any other governing authority forming part of the installation. 

All  audio  visual  cabling  shall  be  segregated  from  all  other  cables  by  minimum  300mm  to  ensure  there is no induced current flow on the audio visual cable. 

All cabling should be installed in accordance with the manufacturers guidelines for segregation and  minimum bend radius. 

All cables should be cut to length. 

Where cables cross they shall do so at an angle of 90 degrees. 

All  connections  and  cable  terminations  shall  be  covered  by  a  connector  hood  or  shall  have  crimp  ferrules  which  securely  grasp  the  cable  outer  jacket  to  provide  protection  to  the  connector  and  provide strain relief for the cable. All connectors shall have mechanical attaching connectors so that  connections cannot fall off. 

Cable runs should be continuous, and without joins, unless approved by LTU ICT/AV. 

All use of twisted pair data cabling for network data or AV signal transmission must comply with the  La  Trobe  University  Cabling  Standards.  Provide  test  results  and  manufacturers  certification  and  warranty for the installation. 

All  cabling  shall  be  neatly  laced,  dressed  and  adequately  supported.  All  exposed  cabling  shall  be  neatly bundled and dressed within black nylon woven mesh fabric. 

17.2. Labelling 

All connectors, patch leads, cabling, equipment and equipment racks shall be permanently typed  labels (handwritten labels are not acceptable). 

Related documents