Input programming

detectors

Molex 3.5 to connect the web-server to J3 (24 V DC) in the EBL512 G3 c.i.e.

11 Input programming

Input programming is done in WinG3. For more information see WinG3 help. Each input has to have an individual Trigger condition ("Triggered by") and Logic. It is not recommended to let two or more inputs have the same trigger condition.

11.1

Trigger conditions

The following trigger conditions are available (numbering only for the comments below):

0. Activate output

1. Activated fault routing equipment (one input per C.U.) 2. Activated key cabinet

3. Activated Routing Equipment (one input per C.U.) 4. Alarm Key Cabinet (one input per control unit) 5. Alert Annunciation Acknowledge

6. Alert Annunciation Reset 7. Door Closing Test Input 8. Evacuate (one input per C.U.) 9. External Fault (50 inputs per system)

10. External Time Channel (one input per time channel 15-63 per system)

11. Extinguishing alarm 12. Extinguishing system fault

13. Extinguishing system released (one input per C.U.) 14. Fault Signal External Fuses (one input per control unit)

15. Fault Signal External Power Supply (one input per control unit) 16. Fault warning routing equipment fault

17. General Fire (max. 127 per C.U.)

18. Interlocking (200 inputs per C.U. / 1000 per system)

19. Loss of battery charger to external power supply (one input per C.U.)

20. Loss of main power source to external power supply (one input per C.U.)

21. Not used

22. Pre-warning (input and corresponding fire alarm input have to be "connected" to the same C.U.)

23. Silence alarms49 (one input per system) 24. Zone Line Input50

49

Only valid for the New Zealand convention.

50 Only valid for the Addressable multipurpose I/O unit 3361 input "In0",

65

Comments to the trigger conditions (above):

0. Activates any output as long as the input is active. This is valid even if the output is disabled.

1. "Activated Fault routing equipment" signal (feed-back) to EBL512 G3 will light up the LED "Fault tx activated" on the front. Output with trigger condition "Indication Fault tx Activated" will be activated.51

2. Output with trigger condition "Activated Key cabinet" will be activated.

3. Activated Fire brigade tx feedback to the EBL512 G3 control unit to light up the LED "Fire brigade tx".52

4. Key cabinet, where the fire brigade store there key to the building. Will activate a Key cabinet alarm. See EBL512 G3 Operating Instructions for more information.

5. Alert annunciation, see chapter "Alert Annunciation", page 102 and EBL512 G3 Operating Instructions for more information. 6. Like 2.

7. When one or more "Fire door closing" outputs are used, these outputs will be activated for 20 seconds by this trigger condition. NOTE! Only valid for inputs and outputs connected to the same c.i.e.

8. Normally used for the New Zealand key switch "Evacuation". The function is like the soft key "Evacuate" (P7) on the c.i.e. front.53 The input has to be activated as long as the Evacuate function shall be on.

9. Ext. fault will activate a fault in EBL512 G3. A user definable fault message ("Error text") up to 40 characters will be shown. 10. External clock, timer, key switch, etc. can disable / re-enable

alarm points. The function Alert Annunciation, etc. can be turned on / off by a time channel. Control outputs can be turned on / off by a time channel.

11. Input activated when the specified zone has activated fire alarm. The specified zone is an "extinguishing zone", e.g. a sprinkler zone. This trigger condition is normally used only for the "New Zealand indicating panel" in order to control the function of the key switch "Silence alarms".

51 One input activated in any control unit, will light up the LED respectively

in all control units.

52

One input activated in any control unit, will light up the LED respectively in all control units.

12. Activated input will generate a fault in EBL512 G3. Output with trigger condition "Extinguishing system fault" will be activated. The following fault message will be shown:

FAULT: Extinguishing system, control unit xx

13. Activated Extinguishing equipment feedback to the EBL512 G3 control unit to light up the LED "Extinguishing".52

14. Ext. fuses (for ext. power supply equipment) fault output will activate a fault in the EBL512 G3 system. The following fault message will be shown:

FAULT: External fuses, control unit xx 15. Ext. power supply equipment fault output will activate a fault in

the EBL512 G3 system. The following fault message will be shown:

FAULT: External power supply, control unit xx

16. Activated input (i.e. fault on the fault routing equipment) will generate a fault in EBL512 G3:

FAULT: Fault warning routing equipment, control unit xx

17. A special detector, push button, etc. can activate a fire alarm in EBL512 G3. Zone no. and Address (+ user definable alarm text). 18. A feed-back from the equipment activated by the corresponding

interlocking output. Activated input is shown in menu H9/C1. See also chapter "Interlocking function", page 84.

19. "Loss of the battery charger to external power supply equipment" fault output will activate a fault in the EBL512 G3 system. It will have the same time delay, as set for the Loss of main power source fault for the c.i.e. The following fault message will be shown:

FAULT: Charging external power supply, control unit xx

20. "Loss of main power source to external power supply equipment" fault output will activate a fault in the EBL512 G3 system. It will have the same time delay, as set for the Loss of main power source fault for the c.i.e. The following fault message will be shown:

FAULT: Mains, external power supply, control unit xx

21. Default. Indicating that an input trigger condition is not selected, i.e. the input will not "activate" anything.

22. Pre-warning, e.g. from a High Sensitive Smoke Detector's pre- warning output. Zone no. and Address have to be set to the same as the corresponding fire alarm (from the same detector).

67

23. Used for the "outside switch" (i.e. the New Zealand FB silence switch).

24. The Addressable multipurpose I/O unit 3361 monitored Input 0 used as zone line input (Z).

11.2

Logic

The logic has to be set. 54

(•) Normally open / normally low Normally open contact or normally low optocoupler input.

( ) Normally closed / normally high Normally closed contact or normally high optocoupler input.

11.2.1

Supervised

Valid for the Inputs and Outputs expansion board (4583) program- mable inputs (Input 0-4) only.

(•) Normally open (high resistance) ( ) Normally closed (low resistance)

Depending on the selected logic, Normally open (high resistance, 3K3) or Normally closed (low resistance, 680R), the function will be according to the table on page 63.

54 In the WinG3 dialog box "Input".