3) CONDENSATE FROM STEAM LINE
11.3 Instrumentation Numbering 1 Loop numbering
Refer to DOC. No. 3034-00-ED-IN-JSP-70087 “Job Specification for Smartplant Instrumentation”. 11.3.2 Instrument numbering
Refer to DOC. No. 3034-00-ED-IN-JSP-70087 “Job Specification for Smartplant Instrumentation”. 11.3.3 ESD, DCS and PLC Logic and Sequence numbering
ESD
Each Emergency Shutdown System Logic and Sequence shall be represented and shall be allocated a unique reference number:
where:
• IZ -ESD logic (Z stands for ESD)
• xxx -Serial number, ranging from 001 to 999
The full name of ESD logics to be shown in the ESD logic diagrams shall have the following format:
IZ-hh-xxx
where:
• IZ -ESD logic (Z stands for ESD) • nn -Unit number
• xxx -Serial number, ranging from 001 to 999 DCS
Each Distributed Control System Logic and Sequence shall be represented and shall be allocated a unique reference number:
where:
• I -DCS logic
• xxx -Serial number, ranging from 001 to 999
The full name of DCS logics to be shown in the DCS logic diagrams shall have the following format:
I-hh-xxx
where:
• I -DCS logic • nn -Unit number
• xxx -Serial number, ranging from 001 to 999 xxx
IZ
xxx I
PLC
Each PLC System Logic and Sequence shall be represented and shall be allocated a unique reference number:
where:
• PLC -name of PLC system (could be FGS, TGS or PLC) • I -PLC logic
• xxx -Serial number, ranging from 001 to 999
The full name of PLC logics to be shown in the PLC logics shall have the following format:
I-hh-xxx
where:
• I -PLC logic • nn -Unit number
• xxx -Serial number, ranging from 001 to 999 11.3.1 Numbering Procedure
Due to the implementation of the numbering code in SPI Tools, the prescriptions of the present specification are mandatory and deviations are not allowed. The use of the letters and digit codes is strictly restricted to the ones clearly listed in ATTACHMENT 3, tables IV, V, VI and VII. Codes not listed in the mentioned tables cannot be used unless previously agreed with EMPLOYER/CONTRACTOR.
Measured or initiating variable letter code and function letter code
For measured or initiating variable letter a single capital letter only shall be used. For function letter code a maximum of five (5) letters shall be used.
For function letter code capital letter only shall be used.
The measured or initiating variable letter shall identify the process condition/property measured or initiating variable, as per column 2 of the Table I in ATTACHMENT 3. The measured or initiating variable letter shall be followed by the function letter code without hyphens (refer to ATTACHMENT 3 - Table I, columns 3, 4 and 5).
Where there are two or more succeeding letters, the priority of lettering shall be in the sequence TQIBRCSZAV e.g. PICA not PIAC, FQI not FIQ etc
For computing functions the succeeding letter Y shall be used (HY where operator access is required) with qualifiers shown outside the balloon (refer to ATTACHMENT 3 - Table II).
The relevant primary function letter shall be added to the Y, e.g. FY.
Loop where initiating variable is not a process variable may use a letter code of more than one character (e.g. UV, XV, MOV , PSV, etc.).
Refer to DOC. No. 3034-00-ED-IN-JSP-70087 “Job Specification for Smartplant Instrumentation”.
Measured or initiating variable letter available codes and function letter available codes are summarized in the ATTACHMENT 3 - Table IV.
xxx I PLC
Unit identification
Two (2) digits code only shall be used.
Process units, auxiliary units and offsite units identification numbers are summarized in the ATTACHMENT 3 - Table VII.
Serial number
For numbers three (3) digits shall be used (001 up to 999), with the possible addition of one letter to identify specific functions of components which otherwise would have the same tag, e.g.:
YHS-xx-001M and YHS-xx-001P respectively for Maintenance and Process Override Switches of the transmitter YZT-xx-001 connected to ESD.
For the not-licensed units, numbering shall be parallel, i.e. a numerical sequence will start for each instrument function code first letter 'Y' and for each process unit designation 'xx'.
All instruments part of the same loop shall have the same serial number 'zzz'. For numbering ranges reference is made to the ATTACHMENT 3 - Table VI.
The process instruments and process loops serial number relevant to the Licensed Units shall follow the numbering philosophy specified in this procedure and not the Licensor philosophy (refer to ATTACHMENT 3 - table VII for the Licensed Unit list).
Suffix
In general. for suffix letter a single capital letter and digits shall be used. The suffix must not exceed three (3) letters/digits length.
Suffix letter shall be used only for in case two or more instruments are required to satisfy the same process requirement.
Such instruments shall be suffixed as follows:
• Level Gauges: A = Top, B/C = Lower
• Transmitters (general): A = High Range, B = Low Range • Transmitters (2ooN): A, B, . . , N
• Indicators on transmitter output: NO SUFFIX= Control Room, A=Local • Valves: A = Positive (Pressure/Heat),
B = Negative (Vent/Cool)
• Chromatographs: A1÷An = First Stream Components (components from 01 to 99)
B1÷Bn = Second Stream Components
(components from 01 to 99)
Z1÷Zn = Last Stream Components (components from 01 to 99)
In general no suffix letter shall be used in the Loop numbering tag numbers. 11.3.2 Instruments in Packaged Units
Instruments supplied in packaged units shall be tagged according to the above mentioned criteria and within the serial number range shown in ATTACHMENT 3 - Table VI.
However, due to presence of more packaged supplies in the same unit, it is necessary to assign restricted number ranges for each package supply. This range assignment will be defined at a later stage by Contractor.
11.4 Symbols
It is not scope of this specification to list all symbols or combinations of them.
When required, these shall be developed using this specification as a basis, and referring to ISA standard. To clarify functionality, the information flow direction may be shown by arrows on signal line symbols; the qualification of the function (for example to indicate process condition or computation) shall be located next to the balloon (right hand side).
Where control signals split across P&ID sheets, the signal lines shall route to a flag located at the left or right margin of the drawing; the flag shall identify the continuation P&ID sheet with the tag number/service description detailed local to the flag.
11.4.1 Typical of instrument representation
Unit identification may be omitted on P&IDs related to the same unit; in such case a note on P&ID shall clearly specify that: “All instruments shown on this P&ID are part of the unit ‘xx’ ”.
11.4.2 Instrument symbols
For available instrument symbols refer to the following Tables in ATTACHMENT 3: TABLE VIII Instrument symbols - Instrument Lines
TABLE IX Instrument symbols - Primary Elements TABLE X Instrument symbols - Instrument Valves
TABLE XI Instrument symbols - Instrument Safety Devices TABLE XII Instrument symbols - General
TABLE XIII Instrument symbols - Discrete instrumentation TABLE XIV Instrument symbols - Computer Based Functions 11.4.3 Instrument typical loops
For available instrument symbols refer to the following Tables in ATTACHMENT 3: TABLE XV Typical Instrument Loops - Examples - Valves Accessories
TABLE XVI Typical Instrument Loops - Examples - Electric Motor Operated Valves TABLE XVII Typical Instrument Loops - Examples - LV/MV Motors
TABLE XVIII Typical Instrument Loops - Examples - Transmitter to ESD
TABLE XIX Typical Instrument Loops - Examples - Temperature Measurement TABLE XX Typical Instrument Loops - Examples - Flow Measurement
TABLE XXI Typical Instrument Loops - Examples - Level Instruments (Direct or Stand-pipe mounting) TABLE XXII Typical Instrument Loops - Examples - Pressure Measurement
TABLE XXIII Typical Instrument Loops - Examples - DCS function - On-off valve with single solenoid TABLE XXIV DELETED
TABLE XXV Typical Instrument Loops - Examples - ESD function - On-off valve with single solenoid TABLE XXVI Typical Instrument Loops - Examples - ESD function - On-off valve with double solenoid
YFF.. zzz xx
Function letters
Qualifier (analysis, computation or condition)
Serial number Unit
identification
HH
11.4.1 Vibrations & Temperatures Monitoring of Machinery
For vibration and temperatures monitoring of machinery refer to the following Tables in ATTACHMENT 3: TABLE XXVII Typical for Vibr. & Temp. Monitoring of Machinery - Examples - Axial Displacement TABLE XXVIII Typical for Vibr. & Temp. Monitoring of Machinery - Examples - Radial Vibration TABLE XXIX Typical for Vibr. & Temp. Monitoring of Machinery - Examples - Piston Rod Drop
TABLE XXX Typical for Vibr. & Temp. Monitoring of Machinery - Examples - Velometer/Accelerometer for casing vibration monitoring
TABLE XXXI Typical for Vibr. & Temp. Monitoring of Machinery - Examples - Key Phasor
TABLE XXXII Typical for Vibr. & Temp. Monitoring of Machinery - Examples -Vibraton Monitoring for Coolers
TABLE XXXIII Typical for Vibr. & Temp. Monitoring of Machinery - Examples - Bearings Temperature TABLE XXXIV Typical for Vibr. & Temp. Monitoring of Machinery - Examples - Motor Winding Temperature