To analyze the membrane separation process and system performance, a mathematical model was developed in Engineering Equation Solver based on the available experimental data. The main criteria for the energy efficiency analysis were: effective system COP, the membrane separation factor, and effective air and water permeances through the membrane surface and the airflow.
The key measured parameters for the analysis were:
Temperature and relative humidity of feed airstream: at the system inlet at Point 01, before the membrane module inlet at Point 1, after the
membrane module at Point 2, and after the sensible cooling system (system outlet) at Point 2A.
Permeate vacuum flow temperatures and pressure: on the permeate side of the membrane module at Point 3, after the intermediate compressor at Point 4, and after the vacuum condenser at Point 5.
Pressure drop across the membrane module to estimate the power required to move the air.
The small scale of the system and the corresponding manufacturing limitations of several system components required development of assumptions about the potential energy efficiency of commercial system components:
Supply air fan and electrical motor energy efficiency – 60%.
Water pump and electrical motor – 80%.
Vacuum pump and electrical motor – 60%.
Intermediate compressor and electrical motor – 60%.
Another assumption made is saturation with water of the permeate airflow after it is cooled in Condenser 4. This assumption is valid for membranes with a relatively large selectivity coefficient.
System effective coefficient of performance (effective COP) was calculated
based on the equation:
𝐶𝑂𝑃 =(ℎ𝑆𝑦𝑠 𝐼𝑛− ℎ𝑆𝑦𝑠 𝑜𝑢𝑡) ∙ 𝑉̇ ∙ 𝜌1
𝑊𝑇𝑜𝑡𝑎𝑙 (64)
where: hx – feed airflow enthalpy at point x, [kJ/kmol]; 𝑉̇ – feed airflow volumetric flow rate, [m³/s]; ρ1 – density of feed airflow, [kmol/m³];
WTotal – system operation effective power consumption, [kW]. System operation effective power consumption can be found:
𝑊𝑇𝑜𝑡𝑎𝑙 = 1.1 ∙ ( 1 0.6∙ 𝑊𝑠𝑓𝑎𝑛+ 1 0.8∙ 𝑊𝑤𝑝+ 1 0.6∙ 𝑊𝑣𝑝+ 1 0.6∙ 𝑊𝑖𝑐) , [kW] (65) where: Wsfan – power delivered by supply air fan to move feed airflow, [kW];
Wwp – power delivered by water pump between Point 5 and Point 7, [kW]; 𝑊𝑣𝑝 – power delivered by vacuum pump for gas compression between Point 5 and Point 6, [kW];
𝑊𝑖𝑐 – power delivered by intermediate compressor for gas compression between Point 3 and Point 4, [kW].
In Equation (65), 10% of energy is reserved for operation of the control system and other supplemental system components.
Power delivered by the supply air fan to move feed airflow can be estimated based on the actual measured data:
𝑊𝑠𝑓𝑎𝑛 = ∆𝑃𝑚𝑚∙ 𝑉,
̇
[𝑘𝑊] (66)
where: ∆Pmm – static pressure drop of feed airflow across the membrane module, [kPa].
Power delivered by the water pump between Point 5 and Point 7 can be estimated with assumption of liquid water incompressibility:
𝑊𝑤𝑝 = 𝑁 ̇ 𝐿𝑖𝑞𝑢𝑖𝑑𝑊𝑎𝑡𝑒𝑟 𝜌𝐿𝑖𝑞𝑢𝑖𝑑𝑊𝑎𝑡𝑒𝑟7 ∙ (𝑃𝑎𝑡𝑚 − 𝑃5), [kW] (67) where: 𝑁 ̇
𝐿𝑖𝑞𝑢𝑖𝑑𝑊𝑎𝑡𝑒𝑟 – molar flow rate of water condensed in the vacuum condenser, [kmol/s].
Power delivered by the vacuum pump between Point 5 and Point 6 was estimated for the isothermal process with the equation:
𝑊𝑣𝑝 = 𝑁 ̇ 𝐴𝑖𝑟6∙ 𝑅 ∙ 𝑇5∙ 𝑙𝑛 ( 𝑃6 𝑃𝑎5) + 𝑁 ̇ 𝐺𝑎𝑠 𝑊𝑎𝑡𝑒𝑟5∙ 𝑅 ∙ 𝑇5∙ 𝑙𝑛 ( 𝑃6 𝑃𝑤5) , [kW] (68) where: N ̇
Air6 – molar flow rate of air permeated through the membrane surface,[kmol/s];
𝑅 – universal gas constant, [kJ/(kmol ∙ K)]; 𝑇5 – gas mixture temperature at Point 5,[K]; 𝑃𝑎5 – partial pressure of air at Point 5, [kPa]; 𝑁
̇
𝐺𝑎𝑠 𝑊𝑎𝑡𝑒𝑟5 – molar flow rate of water leaving condenser as a vapor, [kmol/s];
𝑃𝑤5 – partial pressure of water vapor at Point 5, [kPa]; 𝑃6 – total pressure of gas at Point 6, [kPa].
The power input required by the intermediate compressor in an ideal isothermal process between Point 5 and Point 6 is:
𝑊𝑖𝑐 = 𝑁̇𝑤3∙ 𝑅 ∙ 𝑇4∙ 𝑙𝑛 (𝑃𝑤4
𝑃𝑤3) + 𝑁̇𝑎3∙ 𝑅 ∙ 𝑇4∙ 𝑙𝑛 ( 𝑃𝑎4
𝑃𝑎3) , [kW] (69)
The effective water permeance includes mass transfer conductivity for water
vapor permeation through the bulk airflow, membrane surface and the permeate flow, and can be found as:
𝑃𝐴𝐵𝑊𝑎𝑡𝑒𝑟 =
𝑁̇𝑊𝑎𝑡𝑒𝑟3
𝐴𝑚𝑒𝑚𝑏𝑟∙ ∆𝑃𝑤𝑎𝑡𝑒𝑟, [
kmol
kPa ∙ m2∙ s] (70)
where: ṄWater3 – molar flow rate of water permeated through the membrane surface, [kmol/s];
𝐴𝑚𝑒𝑚𝑏𝑟 – membrane surface area, [m²];
∆𝑃𝑤𝑎𝑡𝑒𝑟 – Log-mean water vapor partial pressure difference through the membrane, [kPa].
The molar flow rate of water permeating through the membrane surface can be measured based on the humidity ratio change in the feed airstream through the membrane module:
𝑁̇𝑊𝑎𝑡𝑒𝑟3= max(0, 𝑉̇ ∙ 𝜌1 ∙ 𝑋𝑤1− 𝑁̇𝑎2∙ 𝑋𝑟𝑒𝑙𝑊2), [kmol/s] (71) where: Xw1 – water molar concentration at Point 1, [ kmolw
kmoltotal];
Ṅa2 – molar flow rate of air on the retentate side at Point 2, [kmols a]; 𝑋𝑟𝑒𝑙𝑊2 – relative water molar fraction at Point 2, [kmolkmolw
a].
The log-mean water vapor partial pressure difference through the membrane accounts for the change of partial pressure of the water profile along the membrane surface as: ∆𝑃𝑤𝑎𝑡𝑒𝑟= 𝑃𝑤1− 𝑃𝑤2 ln (𝑃𝑤1− 𝑃𝑤3 𝑃𝑤2− 𝑃𝑤3) , [kPa] (72) where: Pw1 - Partial pressure of water vapor in the feed air stream at the membrane
module inlet, [kPa];
Pw2 - Partial pressure of water vapor in the retentate air stream at the membrane module outlet, [kPa];
Pw3 - Partial pressure of water vapor in permeate gas flow, [kPa].
Effective air permeance can be found with the equation:
𝑃𝐴𝐵𝐴𝑖𝑟 =
𝑁̇𝐴𝑖𝑟3
𝐴𝑚𝑒𝑚𝑏𝑟∙ ∆𝑃𝐴𝑖𝑟, [
kmol
kPa ∙ m2∙ s] (73)
where: 𝑁̇𝐴𝑖𝑟3 – molar flow rate of air permeated through the membrane surface, [kmol/s];
∆𝑃𝑎𝑖𝑟 – Log-mean air partial pressure difference through the membrane, [kPa].
The log-mean air partial pressure difference through the membrane can be found as: ∆𝑃𝐴𝑖𝑟 = 𝑃𝑎1− 𝑃𝑎2 ln (𝑃𝑎1− 𝑃𝑎3 𝑃𝑎2− 𝑃𝑎3) , [kPa] (74) where: Pa1 - Partial pressure of air in the feed air stream at the membrane module
inlet (Point 1), [kPa];
Pa2 - Partial pressure of air in the retentate air stream at the membrane module outlet (Point 2), [kPa];
Pa3 - Partial pressure of air in permeate gas flow (Point 3), [kPa];
The Separation Factor of the membrane module can be found with [6]:
𝛼𝑤/𝑎 = (𝑋𝑤3 𝑋𝑎3) (𝑋𝑤1 𝑋𝑎1) (75)
where: Xw3 – Water molar concentration in permeate stream, [ kmolw kmoltotal]; Xa3 – Air molar concentration in permeate stream, [kmolkmolAir
total];
Xw1 – Water molar concentration in feed air stream at the membrane module inlet, [ kmolw
kmoltotal];
Xa1 – Air molar concentration in feed air stream at the membrane module inlet, [kmolAir
kmoltotal].
Based on the previous calculations, the Selectivity Coefficient of water to air for the membrane module can be found from the membrane effective water and air permeances as:
𝐬𝐰/𝐚 =𝑃𝐴𝐵𝑊𝑎𝑡𝑒𝑟