OS Function Block Parameter List (table 4‐48)

 Read/Write Capability: RO - Read Only, RW - Read Write

 Mode: The block mode(s) required to write to the parameter

 Double indentation and shaded Index Number indicates sub‐parameter

Table 4‐48. Output Splitter Function Block Parameter Definitions

Label

Mode Range Initial

Value Description

Static Revision

ST_REV 1 RO N/A 0 to 65535 0

Data Type: Unsigned16

The revision level of the static data associated with the function block. The revision value will be incremented each time a static parameter value in the block is changed.

Tag Description

TAG_DESC 2 RW ALL 7 bit ASCII Spaces

Data Type: Octet String

The user description of the intended application of the block.

Strategy

STRATEGY 3 RW ALL 0 to 65535 0

Data Type: Unsigned 16:

The strategy field can be used to identify grouping of blocks. This data is not checked or processed by the block.

Alert Key

ALERT_KEY 4 RW ALL 1 to 255 0

Data Type: Unsigned8

The identification number of the plant unit. This information may be used in the host for sorting alarms, etc.

Block Mode

MODE_BLK 5

Data Type: DS‐69

The actual, target, permitted, and normal modes of the block.

Target: The requested block mode

Actual: The current mode of the block

Permitted: Allowed modes for Target

Normal: Most common mode for Target

TARGET 5.1 RW

PERMITTED 5.3 RW OOS+AUTO+CAS OOS AUTO

CAS

NORMAL 5.4 RW AUTO+CAS

Block Error

BLOCK_ERR 6 RO N/A

1: Block

Configuration Error 7: Input Failure/Bad PV Status 8: Output Failure 14: Power‐up 15: Out‐of‐Service

Dynamic

Data Type: Bit String 0=Inactive 1=Active

This parameter reflects the error status associated with the hardware or software components associated with a block.

It is a bit string, so that multiple errors may be shown.

Setpoint

SP 7 PV_SCALE +/- 10% Data Type: DS‐65

Analog setpoint of the block Output 1

OUT_1 8 MAN

OOS

OUT_SCALE +/- 10%

Data Type: DS‐65

The primary analog output value calculated as a result of executing the function (the first output value and status).

Output 2

OUT_2 9 MAN

OOS

OUT_SCALE +/- 10%

Data Type: DS‐65

The primary analog output value calculated as a result of executing the function (the second output value and status).

Output 1 Range

EU at 100% 100 Data Type: DS‐68

Table 4‐48. Output Splitter Function Block Parameter Definitions (Continued) Output 2 Range

OUT_2_RANGE 11 RO

EU at 100%

Data Type: DS‐68

The high and low scale values, engineering units code, and number of decimal places to be used in displaying the OUT value, this parameter has not effect on this block.

Grant Deny

GRANT_DENY 12 Data Type: DS‐70

Options for controlling access of host computers and local control panels to operating, tuning, and alarm parameters of the block. GRANT:0=N/A, 1=granted

DENY: 0=N/A, 1= denied

GRANT 12.1 N/A 0: Program

1: Tune

STATUS_OPTS 13 OOS 1: IFS if BAD CAS_IN All bits: 0

Data Type: Bit String 0=Disabled 1=Enabled User option for status

Cascade Input

CAS_IN 14 Status

BAD:

NC:

const Data Type: DS‐65

The remote setpoint from another block.

Value 0

Back Calculation Output

BKCAL_OUT 15 RO Status Limits

Data Type: DS‐65

Output value to another block for backwards output tracking.

Input Array

IN_ARRAY 16 All: 0

Data Type: Float

Used with OUT_ARRAY to map input to output. See Input to Output Mapping, page 163.

Output Array

OUT_ARRAY 17 All: 0

Data Type: Float

Used with IN_ARRAY to map input to output. See Input to Output Mapping, page 163.

Lockval

LOCKVAL 18

0=Undfined 1=no lock 2=lock

0=

Undefined

Data Type: Enum

Used with OUT_ARRAY to map input to output. See Input to Output Mapping, page 163.

Back Calculation Input 1

BKCAL_1_IN 19 Status

BAD:

NC:

const

Data Type: DS‐65

The value and status reflecting the BKCAL_OUT of the lower block associated with OUT_1. It is used for initialization and to prevent windup in upstream blocks.

Value 0

Back Calculation Input 2

BKCAL_2_IN 20 Status

BAD:

NC:

const

Data Type: DS‐65

The value and status reflecting the BKCAL_OUT of the lower block associated with OUT_2. It is used for initialization and to prevent windup in upstream blocks.

Value 0

Balance Time

BAL_TIME 21 Positive 0

Data Type: Float

Specifies the time for the internal working value of bias or ratio to return to the operator set bias or ratio, in seconds.

Hystval

HYSTVAL 22

Update Event

UPDATE_EVT 23 RO N/A

Data Type: DS‐73

This alert is generated by any change to the static data.

UNACKNOWLEDGED 23.1 RW N/A

0=Undefined 1=Acknowledged 2=Unacknowledged

0= Undefined

UPDATE STATE 23.2 RO N/A

0=Undefined 1=Update Reported 2=Updated not reported

0= Undefined

TIME_STAMP 23.3 RO N/A 0

STATIC_REVISION 23.4 RO N/A 0

RELATIVE_INDEX 23.5 RO N/A 0

-Continued-Table 4‐48. Output Splitter Function Block Parameter Definitions (Continued)

BLOCK_ALM 24

Data Type: DS‐72

The block alarm is used for all configuration, hardware, connection failure, or system problems in the block. The cause of the alert is entered in the subcode field.

UNACKNOWLEDGED 24.1 RW N/A

0: Undefined 1: Acknowledged 2: Unacknowledged

ALARM_STATE 24.2 RO N/A

0: Undefined 1: Clear reported 2: Clear not reported 3: Active reported 4: Active not reported

TIME_STAMP 24.3 RO N/A

SUBCODE 24.4 RO N/A

VALUE 24.5 RO N/A

View Lists

View lists allow the values of a set of parameters to be accessed at the same time. Views 1 and 2 contain operating parameters and are defined by the Fieldbus Foundation. View 3 contains dynamic parameters and View 4 contains static parameters with configuration and maintenance information. Views 3 and 4 are defined by the manufacturer.

Table 4‐49. OS Function Block, View 1

Index Number Parameter

1 ST_REV

Table 4‐50. OS Function Block, View 2

Index Number Parameter

1 ST_REV

10 OUT_1_RANGE

11 OUT_2_RANGE

12.1 GRANT_DENY.GRANT

12.2 GRANT_DENY.DENY

Table 4‐51. OS Function Block, View 3

Index Number Parameter

1 ST_REV

Table 4‐52. OS Function Block, View 4

Index Number Parameter

1 ST_REV

OUTPUT SPLITTER FUNCTION BLOCK

Field Communicator Menu Structure

All

Characteristics Static Revision Tag Description Strategy Alert Key Block Mode: Target Block Mode: Actual Block Mode: Permitted Block Mode: Normal Block Error Setpoint: Status Setpoint: Value Output 1: Status Output 1: Value Output 2: Status Output 2: Value

Output 1 Range: EU at 100%

Output 1 Range: EU at 0%

Output 1 Range: Units Index Output 1 Range: Decimal Output 2 Range: EU at 100%

Output 2 Range: EU at 0%

Output 2 Range: Units Index Output 2 Range: Decimal Grant Deny: Grant Grant Deny: Deny Status Options Cascade Input: Status Cascade Input: Value Back Calculation Output: Status Back Calculation Output: Value Input Array[1]

Input Array[2]

Input Array[3]

Input Array[4]

Output Array[1]

Output Array[2]

Output Array[3]

Output Array[4]

Lockval

Back Calculation Input 1: Status Back Calculation Input 1: Value Back Calculation Input 2: Status Back Calculation Input 2: Value Balance Time

Hystval

Update Event: Unacknowledged Update Event: Update State Update Event: Time Stamp Update Event: Static Rev Update Event: Relative Index Block Alarm: Unacknowledged Block Alarm: Alarm State Block Alarm: Time Stamp Block Alarm: Subcode Block Alarm: Value