• No results found

P ROGRAMMING O UTPUTS U SING THE D ISPLAY

In document Emcp 4.1,4.2 (Page 123-129)

EMCP 4 Remote Start

10 OUTPUTS

10.1 P ROGRAMMING O UTPUTS U SING THE D ISPLAY

For some of the setpoints, LEVEL 2 OR LEVEL 3 ACCESS is required. For information on obtaining Level 2 Access refer to Chapter 6 Security.

This section will assume that Level 2 or Level 3 Access has already been obtained.

VIEWING THE CURRENT OUTPUT STATUS

To view the current status of an Output, go through the following menu options:

AT THE MAIN MENU,scroll DOWN TO VIEW The status of all Relay or Digital Outputs is shown.

A dash under an output number indicates an output that is programmed, but inactive. A large “X” under an output number indicates an output that is disabled. A number under an output number indicates an output that is programmed and active.

With the LEFT ARROW or RIGHT ARROW , select the RELAY OR DIGITAL OUTPUT that you want to view, then press the OKKEY .

The programmed Usage Type of the selected relay or Digital Output is shown.

Scroll DOWN to view the remaining parameters for this output (including physical and logical state).

CONFIGURING OUTPUTS FOR STATUS PARAMETERS

Command or Status parameters are used to control specific functions within the control

Note: The Fuel Control Relay does not pickup when the Engine Operating State is set to CAN. Engine Start Initiated can be used in Lieu of the Fuel Control Relay for most purposes.

To configure a Digital Output or Relay Output as a Status Parameter, go through the following menu options (substitute Digital Output for Relay Output in the following steps, as needed):

AT THE MAIN MENU,scroll down TO CONFIGURE

Press the OKKEY .

SCROLL DOWN to INPUTS & OUTPUTS

Press the OKKEY . Alternately, access to THE INPUTS & OUTPUTS

submenu is accessible from ALL SETPOINTS.

SCROLL DOWN to RELAY OUTPUTS

Press the OKKEY . Select the RELAY OUTPUT that you want to program

Press the OKKEY .

Press the OKKEY to highlight the current configuration (DISABLED,STATUS,SYSTEM EVENT,

OR SCADADATA LINK).

Scroll DOWN to STATUS

Press the OKKEY .

Scroll DOWN to STATUS PARAMETER

Press the OKKEY to highlight the current STATUS PARAMETER. Select the STATUS PARAMETER that you want to

Any Output can be configured for any one of the Status parameters in Table 10:

Run Mode Common Warning

Auto Mode Common S/D

Stop Mode ECU Fault Reset

Pckg Not in Auto Air Shutoff

Fuel Ctrl Relay* Prog Cycl Time #2 (EMCP 4.2 only) Start Mtr Relay kW Relay Trip #1 (EMCP 4.2 only) Start Aid kW Relay Trip #2 (EMCP 4.2 only)

Disable Aux AC Common Alarm

Crank Alert Breaker #1 Trip

Engine Start Initiated Breaker #2 Trip Engine Started Reduced Power Off Rated Speed Transfer Fuel In V/Hz Within Limits Volt Raise Cmnd Eng in Cooldown Volt Lower Cmnd Wait Delay Stop Speed Raise Cmnd

Horn Control Speed Lower Cmnd

Table 10: Output Status List

*The Fuel Control Relay does not pickup when the Engine Operating State is set to CAN.

Engine Start Initiated can be used in Lieu of the Fuel Control Relay for most purposes.

Note: If the Engine State Configuration is configured for Hard Wired, then Relay Output

#1 must be programmed for the Status Parameter of Starter Motor Relay and Relay Output #2 must be programmed for Fuel Control Relay

CONFIGURING OUTPUTS FOR SYSTEM EVENTS

System Events are used to know when specific conditions are reached and to alert the control system of warning or shutdown conditions. To configure a Relay or Digital Output as a System Event, go through the following menu options (substitute Digital Output for Relay Output in the following steps, as needed):

AT THE MAIN MENU,scroll down TO CONFIGURE

Press the OKKEY .

SCROLL DOWN to INPUTS & OUTPUTS

Press the OKKEY . Alternately, access to THE INPUTS & OUTPUTS

submenu is accessible from ALL SETPOINTS.

SCROLL DOWN to RELAY OUTPUTS

Press the OKKEY . Select the RELAY OUTPUT that you want to program

Press the OKKEY .

Press the OKKEY to highlight the current configuration (DISABLED,STATUS,SYSTEM EVENT,

OR SCADADATA LINK).

Scroll DOWN to SYSTEM EVENT

Press the OKKEY .

Scroll DOWN to EVENT PARAMETER

Press the OKKEY to edit the current STATUS

PARAMETER. Select the type of EVENT PARAMETER that you want to program (Pressures, Temperatures, Levels, or Others)

Press the OKKEY .

Select the EVENT PARAMETER that you want to

Any Output can be configured for any one of the System Events in Table 11:

Pressures Others Custom Events

Engine Oil Pres Any SPN Dig In #1 Cstm Service Interval Expired

Levels Unexpected Eng S/D

Care must be taken in configuring the correct triggers. Only some of these can be configured for a specific System Event and even if it can be configured, it may not be representative of the system requirements.

CONFIGURING OUTPUTS FOR SCADA DATA LINK

When an Output is configured for SCADA Data Link, an active state will be sent over MODBUS. No alarms or warnings will be generated by the EMCP. To configure a Relay Digital Output for SCADA Data Link, go through the following menu options (substitute Digital Output for Relay Output in the following steps, as needed):

AT THE MAIN MENU,scroll down TO CONFIGURE

Press the OKKEY .

SCROLL DOWN to INPUTS & OUTPUTS

Press the OKKEY . Alternately, access to THE INPUTS & OUTPUTS

submenu is accessible from ALL SETPOINTS.

SCROLL DOWN to RELAY OUTPUTS

Press the OKKEY . Select the RELAY OUTPUT that you want to program

Press the OKKEY .

Press the OKKEY to highlight the current configuration (DISABLED,STATUS,SYSTEM EVENT,

OR SCADADATA LINK).

Scroll DOWN to SCADADATA LINK

Press the OKKEY .

DISABLING OUTPUTS

To disable an Output, go through the following menu options (substitute Digital Output for Relay Output in the following steps, as needed):

AT THE MAIN MENU,scroll down TO CONFIGURE

Press the OKKEY .

SCROLL DOWN to INPUTS & OUTPUTS

Press the OKKEY . Alternately, access to THE INPUTS & OUTPUTS

submenu is accessible from ALL SETPOINTS.

SCROLL DOWN to RELAY OUTPUTS

Press the OKKEY . Select the RELAY OUTPUT that you want to program

Press the OKKEY .

Press the OKKEY to highlight the current configuration (DISABLED,STATUS,SYSTEM EVENT,

OR SCADADATA LINK).

Scroll DOWN to DISABLED

Press the OKKEY .

10.2 PROGRAMMING OUTPUTS USING THE CAT SERVICE TOOL

In document Emcp 4.1,4.2 (Page 123-129)

Related documents