• No results found

PERFORMANCE TESTING

In document ASHRAE 2010 - Refrigeration (SI).pdf (Page 131-135)

EQUIPMENT AND SYSTEM DEHYDRATING, CHARGING, AND TESTING

PERFORMANCE TESTING

Because there are many types and designs of refrigeration sys-tems, this section only presents some specific information on com-pressor testing and covers some important aspects of performance testing of other components and complete systems.

Compressor Testing

The two prime considerations in compressor testing are power and capacity. Secondary considerations are leakback rate, low-voltage starting, noise, and vibration.

Testing Without Refrigerant.A number of tests measure com-pressor power and capacity before the unit is exposed to refrigerant.

In cases where excessive power is caused by friction of running gear, low-voltage tests spot defective units early in assembly. In these tests, voltage is increased from a low or zero value to the value that causes the compressor to break away, and this value is com-pared with an established standard. When valves or valve plates are accessible, the compressor can be tested by using an air pump for a leakback. Air at fixed pressure is put through the unit to determine the flow rate at which valves open. This flow rate is then compared to an established standard. This method is effective only when the valves are reasonably tight, and is difficult to use on valves that must be run in before seating properly.

Extreme care should be taken when a compressor is used to pump air because the combination of oil, air, and high temperatures caused by compression can result in a fire or explosion.

In a common test using the compressor as an air pump, the dis-charge airflow is measured through a flowmeter, orifice, or other flow-measuring device. Because this test adiabatically compresses the air, the discharge pressure must be low to prevent overheating of discharge lines and oil oxidation if the test lasts longer than a few minutes. The discharge temperature of isentropic compression from ambient condition is 140°C at 240 kPa (gage), but 280°C at 860 kPa (gage). When the compressor is run long enough to stabilize tem-peratures, both power and flow can be compared with established limits. Discharge temperature readings and speed measurements aid in analyzing defective units. If a considerable amount of air is dis-charged or trapped, the air used in the test must be dry enough to prevent condensation from causing rust or corrosion on the dis-charge side.

Another method of determining compressor performance re-quires the compressor to pump from a free air inlet into a fixed vol-ume. The time required to reach a given pressure is compared against a maximum standard acceptable value. The pressure used in this test is approximately 860 kPa (gage), so that a reasonable time spread can be obtained. The time needed for measuring the capacity of the compressor must be sufficient for accurate readings but short enough to prevent overheating. Power readings can be recorded at any time in the cycle. By shutting off the compressor, the leakback rate can be measured as an additional check. In addition to the pump-up and leakback tests noted above, a vacuum test should also be performed.

The vacuum test should be performed by closing off the suction side with the discharge open to the atmosphere. This test is typically performed on reciprocating compressors. The normal vacuum obtained under these conditions is 6.5 to 10 kPa (absolute). Abrupt closing of the suction side also allows the oil to serve as a check on the priming capabilities of the pump because of the suppression of the oil and attempt to deaerate. This test also checks for porosity and leaking gaskets. To establish reasonable pump-up times, leakback

rates, and suctions, a large number of production units must be tested to determine the range of production variation.

In any capacity test using air, only clean, dry air should be used, to prevent compressor contamination.

Observing performance while testing compressors of known capacity and power best establishes the acceptance test limits described. Take precautions to prevent oil in the compressors from becoming acidic or contaminated.

Testing with Refrigerant.Calorimeter and flow meter testing methods for rating positive-displacement compressors are described in ASHRAE Standard 23. This type of testing is typically conducted on an audit basis. If the purpose of the testing is not an accurate deter-mination of the unit’s capacity and efficiency, alternative methods can be used, such as testing on vapor or desuperheating stands. The vapor stand requires an expansion device (TXV) and a heat exchanger (or condenser) large enough to handle the heat equivalent to the motor power. The gas compressed by the compressor is cooled until its enthalpy is the same as that at suction conditions. It is then adiabatically expanded back to the suction state. This method elim-inates the need for an evaporator and uses a smaller heat exchanger (condenser). On small-capacity compressors, a piece of tubing that connects discharge to suction and has a hand expansion valve can be used effectively. The measure of performance is usually the relation-ship of suction and discharge pressures to power. When a water-cooled heat exchanger (condenser) is used, the discharge pressure is usually known, and the water temperature rise and flow are used as capacity indicators. Operation of the desuperheating stand is similar, but in addition to a condenser and TXV, it also requires a hot-gas bypass valve (HGBV). Liquid refrigerant from a condenser and hot discharge gas are mixed by the HGBV to provide adequate suction pressure and temperature to the compressor: the HGBV controls suc-tion pressure and the TXV, acting as a quench valve, controls super-heating. Note that higher range and stability during operation are achieved by using a desuperheating stand instead of a vapor stand.

As a further refinement, flow-measuring devices can be installed in the refrigerant lines. This system is charge-sensitive if predeter-mined discharge and suction pressures and temperatures are to be obtained. This is satisfactory when all units have the same capacity and one test point is acceptable, because the charge desired can be determined with little experimentation. When various sizes are to be tested, however, or more than one test point is desired, a liquid receiver after the condenser can be used for full-liquid expansion.

The refrigerant must be free of contamination, inert gases, and moisture; the tubing and all other components should be clean and sealed when they are not in use. In the case of hermetic and semi-hermetic systems, a motor burnout on the test stand makes it imper-ative not to use the stand until it has been thoroughly flushed and is absolutely acid-free. In all tests, oil migration must be observed carefully, and the oil must be returned to the crankcase.

The length of a compressor performance test depends on various factors. Stable conditions are required for accuracy. If oil pump or oil charging problems are inherent, the compressor should be run long enough to ensure that all defects are detected.

Testing Complete Systems

In a factory, any system may be tested at a controlled ambient temperature or at an existing shop ambient temperature. In both cases, tests must be run carefully, and any necessary corrections must be made. Because measuring air temperature and flow is dif-ficult, production-line tests are usually more reliable when second-ary conditions are used as capacity indicators. When testing self-contained air conditioners, for example, a fixed load may be applied to the evaporator using any air source and either a controlled ambi-ent or shop ambiambi-ent temperature. As long as the load is relatively constant, its absolute value is not important. Suction and discharge pressures and temperatures can be used as an indirect measure of capacity in units with air-cooled condensers. Air distribution,

velocity, or temperature over the test unit’s coil must be kept con-stant during the test, and the test unit’s performance must then be correlated with the performance of a standard unit. Power measure-ments supplement the suction and discharge parameter readings.

For water-cooled units, in which water flow can be absolutely controlled, capacity is best measured by the heat rejected from the condenser. Suction and discharge pressures can be measured for the analysis. Measurements of water temperature and flow, power, cycle time, refrigerant pressures, and refrigerant temperatures are reliable capacity indicators.

The primary function of the factory performance test is to ensure that a unit is constructed and assembled properly. Therefore, all equipment must be compared to a standard unit, which should be typical of the unit used to pass the Air-Conditioning, Heating, and Refrigeration Institute (AHRI) and Association of Home Appliance Manufacturers (AHAM) certification programs for compressors and other units. AHRI and AHAM provide rating standards with applicable maximum and minimum tolerances. Several ASHRAE and International Organization for Standardization (ISO) standards specify applicable rating tests.

Normal causes of malfunction in a complete refrigeration system are overcharging, undercharging, presence of noncondensable gases in the system, blocked capillaries or tubes, and low compressor effi-ciency. To determine the validity and sensitivity of any test proce-dure, it is best to use a unit with known characteristics and then establish limits for deviations from the test standard. If the estab-lished limits for charging are ±30 g of refrigerant, for example, the test unit is charged first with the correct amount of refrigerant and then with 30 g more and 30 g less. If unit performance is not satis-factory during testing, the established charge limits should be rede-fined. This same procedure should be followed for all variables that influence performance and cause deviations from established limits.

All equipment must be maintained carefully and calibrated if tests are to have any significance. Gages must be checked at regular inter-vals and protected from vibration. Capillary test lines must be kept clean and free of contamination. Power leads must be kept in good repair to eliminate high-resistance connection, and electrical meters must be calibrated and protected to yield consistent data.

In plants where component testing and manufacturing control have been so well managed that the average unit performs satisfac-torily, units are tested only long enough to find major flaws. Sample lot testing is sufficient to ensure product reliability. This approach is sound and economical because complete testing taxes power and plant capacity and is not necessary.

For refrigerators or freezers, the time, temperature, and power measurements are used to evaluate performance. Performance is evaluated by the time elapsed between start and first compressor shutoff or by the average on-and-off period during a predetermined number of cycles in a controlled or known ambient temperature.

Also, concurrent suction and discharge temperatures in connection with power readings are used to establish conformity to standards.

On units where the necessary connections are available, pressure readings may be taken. Such readings are usually possible only on units where refrigerant loss is not critical because some loss is caused by gages.

Units with complicated control circuits usually undergo an oper-ational test to ensure that controls function within design specifica-tions and operate in the proper sequence.

Testing of Components

Component testing must be based on a thorough understanding of the use and purpose of the component. Pressure switches may be calibrated and adjusted with air in a bench test and need not be checked again if there is no danger of blocked passages or pulldown tripout during the operation of the switch. However, if the switch is brazed into the final assembly, precautions are needed to prevent blocking the switch capillary.

--``,`,,``,,,`,,,````,``````,,``-`-`,,`,,`,`,,`---Capillaries for refrigeration systems are checked by air testing.

When the capillary limits are known, it is relatively easy to establish a flow rate and pressure drop test for eliminating crimped or improperly sized tubing. When several capillaries are used in a dis-tributor, a series of water manometers check for unbalanced flow and can find damaged or incorrectly sized tubes.

In plants with good manufacturing control, only sample testing of evaporators and condensers is necessary. Close control of coils during manufacture leads to the detection of improper expansion, poor bonding, split fins, or uneven spacing. Proper inspection elim-inates the need for costly test equipment. In testing the sample, either a complete evaporator or condenser or a section of the heat transfer surface is tested. Because liquid-to-liquid is the most easily and accurately measurable method of heat transfer, a tube or coil can be tested by flowing water through it while it is immersed in a bath of water. The temperature of the bath is kept constant, and the capac-ity is calculated by measuring the coil flow rate and the temperature differential between water entering and leaving the coil.

REFERENCES

ASHRAE. 2005. Methods of testing for rating positive displacement refrig-erant compressors and condensing units. ANSI/ASHRAE Standard 23-2005.

ASHRAE. 1992. Method of testing desiccants for refrigerant drying. ANSI/

ASHRAE Standard 35-1992.

ASHRAE. 2002. Reducing the release of halogenated refrigerants from refrigerating and air-conditioning equipment and systems. ANSI/

ASHRAE Standard 147-2002.

ASTM. 2002. Standard guide for sampling, test methods, and specifications for electrical insulating oils of petroleum origin. Standard D117-02.

American Society for Testing and Materials, West Conshohocken, PA.

Blair, H.A. and J. Calhoun. 1946. Evacuation and dehydration of field instal-lations. Refrigerating Engineering (August):125.

Goddard, M.B. 1945. Moisture in Freon refrigerating systems. Refrigerating Engineering(September):215.

Larsen, L.W. and J. Elliot. 1953. Factory methods for dehydrating refriger-ation compressors. Refrigerating Engineering (December):1325.

Morton, J.D. and L.K. Fuchs. 1960. Determination of moisture in fluorocar-bons. ASHRAE Transactions 66:434.

Reed, F.T. 1954. Moisture determination in refrigerant oil solutions by the Karl Fischer method. Refrigerating Engineering (July):65.

Taylor, E.S. 1956. New instrument for moisture analysis of “Freon” fluori-nated hydrocarbons. Refrigerating Engineering (July):41.

BIBLIOGRAPHY

ASHRAE. 2007. Designation and safety classification of refrigerants. ANSI/

ASHRAE Standard 34-2004.

REFRIGERANT CONTAINMENT, RECOVERY,

In document ASHRAE 2010 - Refrigeration (SI).pdf (Page 131-135)

Outline

Related documents