• No results found

described Table 9.

Note: The GSC+P diagnoses a fault in the output

circuit of the programmable spare relay. For more information, refer to Testing And Adjusting, “Diagnostic Fault Codes”.

Procedure For Spare Input/Output

Programming

Note: Service Mode cannot be entered when the

ECS is in the AUTO position.

Note: Any active shutdown fault must be made

inactive in order to access service mode. A shutdown fault is active when any shutdown indicator is FLASHING. To temporarily change a shutdown fault from an active shutdown fault to an inactive shutdown fault, turn the ECS to the OFF/RESET position. To permanently change a shutdown fault from an active shutdown fault to an inactive shutdown fault, the shutdown fault must no longer be occurring. The fault must be corrected and the ECS must be turned to the OFF/RESET position. If the jumper from terminal 6 to terminal 9 is not installed on the ECS, the GSC+P does not power up in OFF/RESET and any active shutdown fault must be corrected before entering Service Mode.

1. Shut down the engine by turning the ECS to the

STOP position. Enter Service Mode and enter the password. “OP 4” is showing on lower display. For more information, refer to Systems Operation, “Procedure To Enter The Password”.

2. Press the “SCROLL UP” key three times. “OP 6”

is showing on the lower display.

3. Press the “SELECT” key. SP01 is showing. SP01

is followed by the value of the setpoint.

4. Press the “SCROLL UP” or the “SCROLL DOWN”

key. The next setpoint and the value for the setpoint is showing. Repeat this step until the desired value is showing.

5. Press the “SELECT” key. The value of the setpoint

is flashing.

6. Press the “SCROLL UP” key or the “SCROLL

DOWN” key in order to adjust the value of the setpoint.

7. Press the “ENTER” key. The value of the setpoint

stops flashing. Repeat steps 4, 5, 6, and 7 until all the desired setpoints are adjusted.

8. Press the “EXIT” key. “OP 1” is showing on the

lower display.

9. Press the “EXIT” key. The display returns to

Normal Mode.

Table 9

OP6-0 Setpoints(1)- Spare Input/Output Programming

Setpoint Name Description Range Of Value Factory Default

SP01 Spare Input 1 Active State

Input state used by the GSC+P to declare that a SP01 fault exists.

0 - active low

1 - active high 0 SP02 Spare input 1

Response GSC+P response to aSP01 fault. 0 - shutdown1 - alarm 0 SP03 Spare Input 1 Time

Delay Amount of time theGSC+P waits before responding to a SP1 fault.

0 to 250 seconds in

increments of 1 0 seconds

SP04 Spare Input 2 Active

State Input state used by theGSC+P to declare that a SP02 fault exists.

0 - active low

1 - active high 0 SP05 Spare Input 2

Response GSC+P response to aSP02 fault

0 - shutdown

1 - alarm 0 SP06 Spare Input 2 Time

Delay Amount of time theGSC+P waits before responding to a SP02 fault.

0 to 250 seconds in

increments of 1 0

SP07 Spare Input 3 Active

State Input state used by theGSC+P to declare that a SP03 fault exists.

0 - active low

1 - active high 0 SP08 Spare Input 3

Response GSC+P response to aSP03 fault. 0 - shutdown1 - alarm 0 SP09 Spare Input 3 Time

Delay Amount of time theGSC+P waits before responding to a SP03 fault.

0 to 250 seconds in

increments of 1 0 seconds

SP10 Spare Input 4 Active

State Input state used by theGSC+P to declare that a SP04 fault exist.

0 - active low

1 - active high 0 SP11 Spare Input 4

Response GSC+P response to aSP04 fault.

0 - shutdown

1 - alarm 0 SP12 Spare Input 4 Time

Delay Amount of time theGSC+P waits before responding to a SP04 fault.

0 to 250 seconds in

increments of 1 0 seconds

(Table 9, contd)

OP6-0 Setpoints(1)- Spare Input/Output Programming

Setpoint Name Description Range Of Value Factory Default

SP13 Spare Output Response

GSC+P response to the spare output trigger condition.

0 - active low

1 - active high 0 SP15 Spare Relay Output

Response GSC+P response tothe spare relay trigger condition.

0 - relay inactive when triggered

1 - relay active when triggered

1

SP14 Spare Output Trigger

Condition The condition used bythe GSC+P to trigger the spare output trigger response. SP16 Spare Relay Output

Trigger Condition The condition used bythe GSC+P to trigger the spare relay.

0 - unused 1 - active SP01 fault(2) 2 - active SP02 fault(2) 3 - active SP03 fault(2) 4 - active SP04 fault(2) 5 - any combination of active SP01, SP02, SP03 or SP4 faults(2) 6 - any active shutdown fault (AL1 - AL14, SP01 - SP04, or CID FMI)

7 - any active alarm or shutdown fault (AL1 - AL15, SP01 - SP04, or CID FMI)

8 - cooldown mode 9 - coolant loss fault(2)

10 - high oil temperature fault(2)

11 - CCM control(3)

8

SP17 Spare Indicator 1

Trigger Condition The condition used bythe GSC+P to trigger spare indicator 1. SP18 Spare Indicator 2

Trigger Condition

The condition used by the GSC+P to trigger Spare Indicator 2. SP19 Spare Indicator 3

Trigger Indicator The condition used bythe GSC+P to trigger spare indicator 3. 0 - unused 1 - active SP01 fault(2) 2 - active SP02 fault(2) 3 - active SP03 fault(2) 4 - active SP04 fault(2) 5 - any combination of active SP01, SP02, SP03 or SP04 faults(2)

6 - coolant loss fault(2)

7 - high oil temperature fault(2)

8 - kW level relay active

0

(1) The setpoints are programmed at the factory to the default value. The setpoints may be changed to satisfy customer requirements

or application requirements.

(2) Either alarm or shutdown faults are valid trigger conditions.

(3) When SP14 is programmed to 11 (CCM control), the spare output is always active low. When SP16 is programmed to 11 (CCM control),

the spare relay is always active when triggered.

i02898711