10.1. How to enter programming mode

You can gain access to the programming mode from any dialog box through “Programming” of the main menu. After that enter the engineer password (engineer factory default - [1][2][3][4][4][3][2][1]). The programming menu items become available upon entering the correct password.

10.1. How to program the panel

You can change object parameters by programming the panel. As a rule, programming menu items correspond to object types (e.g., “Zone”, “Outputs”, “Users”).

The marker «» is located in the object parameter setting window, pointing to the current field or parameter. Use [↑], [↓] buttons to move between fields (parameters). To activate the current field (parameter) change option press [Enter] or functional button «Edit». The field (parameter) change process can be 2 types:

- choice from the list of available values (use [↑], [↓]), with a field that includes the parameter value flashing.

- entry of character number from the keypad, with the vertical bar (cursor) in enter position on the screen flashing.

To confirm changes press [Enter] or the functional key «ОК». To cancel changes press [Esc], or the functional key «Cancel». The confirmed changes are saved to panel’s non-volatile memory the when you activate «Save» in the context menu for the current object.

10.2. How to program “ZONE”

To activate the zone programming window use “AL” item of the programming menu. The display will look like the below:

You can change the following parameters in the window:

Name of zone (Name). Defines the character name of the zone, which will be displayed in status windows “AL status” and “AL list”. The name may contain capital and small Latin or Cyrillic letters, numbers, space, brackets etc. Maximum number is 14 characters.

AL type. Defines the way of zone current change processing. The following values of the parameter are available:

– Combined;

– Active;

– Passive.

AL operation algorithm. Sets the way of the FIRE condition detecting in a zone. The following values of the parameter are available:

– With verification;

– Without verification;

– Two detectors activation (2 det. activation).

Standby current. Sets the primary zone current through which zone current change is calculated. When the parameter is activated by pressing [Enter], the context menu item

“Store in memory” becomes available through which the actual current in zone is stored in memory.

Threshold activation current of the first active detector (Curr Thres. Up1). Sets the value of threshold (current raise) of first active detector relative to the primary standby current of a zone (standby zone current). The value can be set from 0,5 до 8,0 mА in increments of

Threshold activation current of the first passive detector (Curr Thres. Dn1). Sets the value of threshold (current drop) of first passive detector relative to the primary standby current of a zone (standby zone current). The value can be set from 0,5 до 8,0 mА in increments of 0,5mА.

Threshold activation current of the second active detector (Curr Thres. Up2). Sets the value of threshold (current raise) of second active detector relative to the first activated detector.

The value can be set from 0,5 до 8,0 mА in increments of 0,5mА.

Threshold activation current of the second passive detector (Curr Thres. Dn2). Sets the value of threshold (current drop) of the second passive detector relative to the first activated detector. The value can be set from 0,5 до 8,0 mА in increments of 0,5mА.

AL reset time. Sets the reset period for a zone. The value can be set within 0 and 99 seconds.

Waiting-to-ready time (Wait time). Sets the time of zone waiting-to-ready after applying power supply or AL reset. The value can be set within 0 and 99 seconds.

Verification time (Verif time). Sets the time of reactivation or activation of second detector in the zone depending on the effective zone operation algorithm. The value can be set within 1 and 255 seconds. ( Value 0 – waiting till deenergizing).

10.3. How to program “OUTPUT”

To activate the output programming window use the “Outputs” item of the programming menu.

The display will look like the below:

You can change the following parameters of outputs in the window:

Output name (Name). Defines the character output name which will be displayed in status windows “Output list”. The name may contain capital and small Latin or Cyrillic letters, numbers, space, brackets etc. Maximum number is 14 characters.

Output type. The following values of the parameter are available:

- standard;

Operation algorithm. Designates direct or inverse mode for an output. The following options of the parameter are available:

- With inversion;

– Without inversion.

Active period. Sets the time of output active status. The value can be set within 1 and 65000 seconds (0 – non limited active time).

Delay period. Sets the delay time for output active period. The value can be set within 0 to 255 seconds.

Automatic restore time (Disabl time). Sets the time in that the output goes from disabled to actual state. The value can be set within 1 to 255 seconds (0 – switch off the auto restore mode).

Allow to enable at SC (Allow ON at SC). Sets the permission to activate output at SC in its load. The following options of the parameter are available:

– Yes;

– Active period in active state (Та1 act/act). Sets the time of output’s active period in active state. The value can be set within 0,1 to 25,5 seconds (0 – switch off the dynamic mode).

Passive period in active state (Та2 pas/act). Sets the time of output’s passive period in active state. The value can be set within 0,1 to 25,5 seconds (0 – switch off the dynamic mode).

Active period in passive state (Тp1 act/pas). Sets the time of output’s active period in passive state. The value can be set within 0,1 to 25,5 seconds (0 – switch off the dynamic mode).

Passive period in passive state (Та2 pas/pas). Sets the time of output’s passive period in passive state. The value can be set within 0,1 to 25,5 seconds (0 – switch off the dynamic mode).

10.4. How to program “USER”

To activate the user programming window use the “User” item of the programming menu. The display will look like the below:

You can change the following parameters of users in the window:

Allow to control AL (AL). Sets the list of AL available to control for the user. Available ALs are marked with «+», non available - with «-». On activation of the parameter with [Enter], the choice of the relevant AL is made with the keys [←] [→] , and setting of permissions with [↑], [↓].

User access code (Access code). The password is a line from 0 to 15 characters for users 2…9 and from 8 to 15 characters for user 1 (engineer).

10.5. How to set system date and time

To activate the system date and time programming window use “Set date” and “Set time” in the

“Additional” submenu of the programming menu. The display will look like the below:

You can move between parameters using the keys [←] [→] , and setting of values is made with [↑], [↓]. Activation of new system date and time is done with the help of the “Set” item of the window menu.

10.6. How to reset engineer password to factory defaults

When necessary you can reset the engineer password to factory default following the below steps:

- deenergize the panel (both mains and battery);

- open the lid and fit the jumper Р7 of MCU;

- apply power and in not less than 5 sec. remove the jumper. When the procedure is complete the engineer password will be reset to factory default.

10.7. How to reset values of ZONE and OUTPUT to factory defaults

To reset all parameters of “AL” and “Output” to factory defaults use “Reset FACP” in the

“Additional” submenu of the programming menu.

10.8. How to autoconfigure the panel

After you have added a new board or replaced a failed one perform the Autoconfiguring function using the item “AutConf” from the programming menu.

<Config> Set date and time

10.9. How to exit programming mode

To exit the programming mode press [Esc] a few times.

10.10. Factory defaults

Users

Password Rights to zones Rights to outputs

1

(engineer) 12344321 All zones All outputs

2…9 2…9 All zones All outputs