IRIG BNC connector
(LED1 LED4) Step 1 Press the RESET
4.2.6 Changing the Settings
4.2.6.5 Setting the Recording
To set the recording function as described in Section 4.2.3, do the following:
• Press 4 (= Setting (change)) on the main "MENU" screen to display the "Setting (change)" screen.
• Press 4 (= Record) to display the "Record" screen.
R e c o 1 = r e c o r d 3 = D i s t u r b a n c e / 2 r a u t F l 2 = E v e n t r e c o r d r e c o r d 4 = A u t o m a t i c t e s t i n t e r v a l d
Setting the fault recording
• Press 1 (= Fault record) to display the "Fault record" screen.
r e c o r d r 1 _ 1 1 / / 3 0 = O f f a u t F l 1 = O n l o c a t o a u t F l
• Enter 1 (= On) to record the fault location. Enter 0 (= Off) not to record the fault location.
• Press the ENTER key.
Setting the event recording
/3 Event record 1/129 BITRN( 0- 128): 128 _ EV1 ( 0- 3071): 0 EV2 ( 0- 3071): 1 EV3 ( 0- 3071): 1 EV4 ( 0- 3071): 1 EV5 ( 0- 3071): 3071 EV6 ( 0- 3071): 3071 EV7 ( 0- 3071): 3071 EV8 ( 0- 3071): 3071 EV9 ( 0- 3071): 3071 EV10 ( 0- 3071): 3071 : : : EV128( 0- 3071): 3071 <BITRN>
• Enter the number of event to record the status change both to "On" and "Off". If enter 20, both status change is recorded for EV1 to EV20 events and only the status change to "On" is recorded for EV21 to EV128 events.
<EV∗>
• Enter the signal number to record as the event in Appendix B. It is recommended that this setting can be performed by RSM100 because the signal name cannot be entered by LCD screen. (Refer to Section 3.4.2.)
Setting the disturbance recording
• Press 3 (= Disturbance record) to display the "Disturbance record" screen.
e 2 = S c h e m s w i t c h / 3 D i s t u r b a n c e r e co rd g i s n a y 3 = B i n r a l 1 = R e c o r d t ime & s t a rte r
• Press 1 (= Record time & starter) to display the "Record time & starter" screen.
U V P - G ( 0 - 7 6 ) : 5 7 V U V P - S ( 0 - 1 3 2 ) : 1 0 0 V O C P - G ( 0 . 5 - 2 5 0 . 0 ) : 1 0 . 0 A O C P - S ( 0 . 5 - 2 5 0 . 0 ) : 1 0 . 0 A / 4 R e c o r d t i m e & s t a r t e r 1 / 5 T i m e ( 0 . 1 - 3 . 0 ) : 2 . 0 _ A
• Enter the recording time and starter element settings. To set each starter to use or not to use, do the following:
• Press 2 (= Scheme switch) on the "Disturbance record" screen to display the "Scheme switch" screen.
1 T R I P 0 = fO f 1 = O n 1 O C P - S 0 = O f f 1 = O n 1 / 5 / 4 S c h e m e s w i t c h 1 O C P - G 0 = O f f 1 = O n 1 U V P - S 0 = O f f 1 = O n 1 U V P - G 0 = O f f 1 = O n
• Enter 1 to use as a starter.
• Press 3 (= Binary signal) on the "Disturbance record" screen to display the "Binary signal" screen. S I G 4 ( 0 - 3 0 7 1 ) : 4 S I G 3 ( 0 - 3 0 7 1 ) : 3 S I G 2 ( 0 - 3 0 7 1 ) : 2 / 4 B i n a r y s i g n a l 1 / 3 2 S I G 1 ( 0 - 3 0 7 1 ) : 1 _ S I G 3 2 ( 0 - 3 0 7 1 ) : 0
• Enter the signal number to record binary signals in Appendix B. It is recommended that this setting can be performed by RSM100 because the signal name cannot be entered by LCD screen. (Refer to Section 3.4.3.)
Setting the automatic testing
• Press 4 (= Automatic test interval) to display the "Automatic test interval" screen.
/ 3 A u t o m a t i c t e s t i n t e r v a l 1 / 1 C h a n n ( 1 - 2 4 ) : 1 2 _ h r s
• Enter the test intervals of the signal channel. 4.2.6.6 Status
To set the status display described in Section 4.2.4, do the following.
• Press 5 (= Status) on the "Setting (change)" sub-menu to display the "Status" screen.
3 = T i m e z o n e
2 = T i m e s y n c h r o n i z a t i o n / 2 S t a t u s
1 = M e t e r i n g
Setting the metering
• Press 1 (= Metering) to display the "Metering" screen.
/ 3 M e t e r i n g 1 / 3
P o w e r ( P / Q ) 1 = S e n d 2 = R e c e i v e 1
C u r r e n t 1 = L a g 2 = L e a d 1
D i s p l a y v a l u e 1 = P r i m a r y 2 = S e c o nd a r y 1
Note: Power and Current setting
Active Power Display
Power setting=1(Send) Power setting=2(Receive)
+ + - - V I V I + + - -
Reactive Power Display
Current setting=1(Lag) Current setting=2(Lead)
+ - + - V I V I + - - +
Setting the time synchronization
The calendar clock can run locally or be synchronized with external IRIG-B time standard signal, RSM clock or IEC60870-5-103. This is selected by setting as follows:
• Press 2 (= Time synchronization) to display the "Time synchronization" screen.
/3 Time synchronization 0=Off 1=IRIG 2=RSM 3=IEC
Current No.=0 Select No.=_
• Enter the selected number and press the ENTER key.
Note: When to select IRIG-B, RSM, or IEC, check that they are active on the "Time synchronization source" screen in "Status" sub-menu. If it is set to an inactive IRIG-B, RSM, or IEC, the calendar clock runs locally. IEC is available only for relay model with IEC60870-5-103 communication.
Setting the time zone
When the calendar clock is synchronized with the IRIG-B time standard, it is possible to transform GMT to the local time.
• Press 3 (= Time zone) to display the "Time zone" screen.
/ 3 T i m e z o n e 1 / 1 G M T ( - 1 2 - + 1 2 ) : + 9 _ h r s
• Enter the difference between GMT and local time and press the ENTER key. 4.2.6.7 Protection
The GRZ100 can have 8 setting groups for protection in order to accommodate changes in the operation of the power system. One setting group is assigned active. To set the protection, proceed as follows:
/ 2 P r o t e c t i o n
1 = C h a n g e a c t i v e g r o u p 2 = C h a n g e s e t t i n g
3 = C o p y g r o u p
Changing the active group
• Press 1 (= Change active group) to display the "Change active group" screen.
/ 3 C h a n g e a c t i v e g r o u p ( A c t i v e g r o u p = * ) 1 = G r o u p 1 2 = G r o u p 2 3 = G r o u p 3 4 = G r o u p 4 5 = G r o u p 5 6 = G r o u p 6 7 = G r o u p 7 8 = G r o u p 8 C u r r e n t N o . = * S e l e c t N o . =
• Enter the selected number and press the ENTER key. Changing the settings
Almost all the setting items have default values that are set when the product was shipped. For the default values, see Appendix D and H.
To change the settings, do the following:
• Press 2 (= Change setting) to display the "Change setting" screen.
/ 3 C h a n g e s e t t i n g ( A c t i v e g r o u p = * ) 1 = G r o u p 1 2 = G r o u p 2 3 = G r o u p 3 4 = G r o u p 4 5 = G r o u p 5 6 = G r o u p 6 7 = G r o u p 7 8 = G r o u p 8
• Press the group number to change the settings and display the "Protection" screen. (In model 100 series, 3 = Autoreclose is not displayed.)
/4 Protection (Group *) 1=Line parameter
2=Trip
3=Autoreclose
Setting the line parameters
Enter the line name, VT&CT ratio and settings for the fault locator as follows:
• Press 1 (= Line parameter) on the "Protection" screen to display the "Line parameter" screen.
/ 5 L i n e p a r a m e t e r ( G r o u p * )
1 = L i n e n a m e 2 = V T & C T r a t i o 3 = F a u l t l o c a t o r
• Press 1 (= Line name) to display the "Line name" screen. • Enter the line name as a text string.
• Press the END key to return the display to the "Line parameter" screen.
/6 VT & CT ratio 1/ 4 VT ( 1- 20000): 2200 _
VTs1 ( 1- 20000): 2200 VTs1 ( 1- 20000): 2200 CT ( 1- 20000): 400
• Enter the VT ratio for protection function and press the ENTER key.
• Enter the VTs1 ratio and/or VTs2 ratio for autoreclose function and press the ENTER key. VTs1 is used for the VT ratio setting for voltage and synchronism check of autoreclose function. VTs2 is used for the VT ratio setting for the other voltage and synchronism check at the time of two-breaker autoreclose.
• Enter the CT ratio for protection function and press the ENTER key.
• Press the END key to return the display to the "Line parameter" screen.
• Press 3 (= Fault locator) to display the "Fault locator" screen.
/ 6 F a u lt l co at o r 1 /1 3 R 1 ( 0 .0 0 - 19 9 . 99) : 0.20 Ω R 0 ( 0 . 0 0 - 19 9 . 99) : 0.20 Ω Kab ( 8 0 - 1 20) : 100 % ( L i n e 0 . 0 - 3 9 9.9) : 8 0.0 k m X 1 ( 0 .0 0 - 19 9 . 99) : 1 0.0 0 Ω X 0 ( 0 . 0 0 - 19 9 . 99) : 3 4.00 Ω 1 X 0m ( 0 . 00 - 9 9 . 99) : 2.00 Ω L ( Z O B - 0 . 00 - 19 9 . 99) : 1 0.00 Ω B Z 0 - R ( 0 . 0 0 - 19 9 . 99) : 1 0.00 Ω Kbc ( 8 0 - 120) : 10 0 % Kca ( 8 0 - 120) : 10 0 % K a ( 8 0 - 120) : 10 0 % K b ( 8 0 - 120) : 10 0 % K c ( 8 0 - 120) : 10 0 %
• Enter the setting and press the ENTER key for each item.
• Press the END key after completing the settings to return the display to the "Line parameters" screen.
Setting the protection function
To set the protection schemes, scheme switches and protection elements, do the following. Protection elements are the measuring elements and timers.
Note: Depending on the selected protection scheme and scheme switch setting, some of the scheme switches and protection elements are not used and so need not be set. The protection function setting menu of the GRZ100 does not display unnecessary setting items. Therefore, start by setting the protection scheme, then set the scheme switch, then the protection elements. As a result of the above, note that some of the setting items described below may not appear in the actual setting.
/ 5 T r i p ( G r o u p * ) 1 = P r o t e c t i o n s c h e m e
2 = S c h e m e s w i t c h
3 = P r o t e c t i o n e l e m e n t
Protection scheme setting
• Press 1 (= Protection scheme) on the "Trip" screen to display the "Protection scheme" screen.
/ 6 P r o t e c t i o n s c h e m e 1 = 3 Z O N E 2 = Z 1 - E X T 3 = P U P 4 = P O P 5 = U O P 6 = B O P 7 = P O P + D E F 8 = U O P + D E F 9 = B O P + D E F C u r r e n t N o . = 2 S e l e c t N o . = 0 = P U P + D E F 1
• Select the protection scheme to be used by entering the number corresponding to the protection scheme and press the ENTER key.
• Press the END key to return to the "Trip" screen.
Setting the scheme switches