SEV offset

In document E500 FD Rel11 Part6 RTU Functions (Page 97-108)

LED indications for 560RTC03

SEV offset

System message

Value Detailed description

Cause Error status

#016 At least one data points of RTU are valid. RTU is invalid.

Note:

Overflow is not considered by this SEV. failure has occurred.

Warning

The analog settings are not correct.

Warning

SEV offset

System message

Value Detailed description

Cause Error status All analog values

correct

OFF There is no I/O bus error. All I/O boards and CVT modules with configured analog values are operable. No live zero underflow was detected.

- OK

#018 At least one digital value faulty

ON At least one local DMI or BSI data point of RTU is invalid or a wrong BCD coding was detected. failure has occurred.

Warning

A warning with regard to BCD coding or

configuration has occurred.

Warning

All digital values correct

OFF There is no I/O bus error. All I/O boards with configured digital values are operable. RTU is invalid.

The I/O board or failure has occurred.

Warning

All pulse counters correct RTU is invalid and not operable.

Function Description Release 11 System data interface

Value Detailed description

Cause Error status A command

supervision board (e.g., 23BA22 or 23BA23) is without process voltage. or RCO data points of the RTU are valid invalid and not operable.

All analog outputs correct

OFF All local ASO and SOC data points of the RTU are valid the RTU is invalid and not operable.

The I/O board is

All digital outputs correct

SEV offset

System message

Value Detailed description

Cause Error status RTU not active OFF The RTU cannot invalid data or required data are missing from the files.

Error

#025 RTU

synchronized

ON The RTU is

synchronized by the time master as configured.

- -

RTU not synchronized

OFF The time of the RTU is not synchronized and may deviate from the time of the time master.

No time

synchronization signal is received from the time master

-

The minute pulse is missing.

-

The RTC is missing, has an error or has not yet been synchronized.

-

The SNTP server is not available or has not been

synchronized.

-

#026 External clock inoperable

ON The configured external RTC clock is inoperable.

The RTU has not been synchronized yet by 560RTC0x.

Warning

An RTC or minute pulse is missing.

Warning

An RTC antenna error has occurred.

Warning

External clock operable

OFF The configured external RTC clock is operable.

- OK

#027 Local printer offline

ON The local printer is not working or out of order.

A printer connection failure has occurred.

- point is oscillating (Oscillating

suppression active).

The input signal oscillates within the configured limits.

Warning

All indications stable

OFF All configured SPI or DPI data points are stable.

- OK

Function Description Release 11 System data interface

Value Detailed description

Cause Error status

#029 Battery voltage low

ON Backup battery is not charged.

The battery is defect.

Warning

Check connection to battery.

Warning

Battery voltage OK

OFF Backup battery is charged.

- OK

#030 AC power supply failure

ON AC power supply is defective. RTU is running on backup battery.

No AC power is available.

Warning

The power supply unit is defect.

Warning

AC power supply OK equipment (DCE) is missing or not responding.

The DCE is switched off. are connected to the RTU.

- -

#0451 Device connected ON The connection to the device is

OFF The connection to the device via dial-up is currently not established.

No reportable data were received from the device.

-

No cyclic dial-up call from the RTU to the device is pending.

- function of the RTU is not running.

No boot project was loaded.

Warning

A PLC license is missing on the CMU,

Warning

An exception in a PLC user program has occurred.

Warning

SEV offset

System message

Value Detailed description

Cause Error status All PLC functions

running

OFF All configured PLC functions of the RTU are running.

- OK

#047 At least one PLC function cycle time exceeded

ON The cycle watchdog time of at least one PLC task was exceeded.

The PLC execution cycle time was longer than the watchdog time. The PLC function is restarted.

Warning

All PLC function cycle time OK

OFF All PLC task cycle times are within the configured

watchdog times.

- OK

#0481 RTU inoperable ON A subordinate device (RTU, IED, etc.) is inoperable or not connected.

A device address mismatch (such as link address, station address) has occurred.

-

RTU is operable OFF The subordinate device (RTU, IED, etc.) is operable and the connection to the RTU is established.

- -

#0491 RTU is out of service

ON The subordinate device (RTU, IED, etc.) was put out of service and is not being processed.

The subordinate device (RTU, IED, etc.) was put out of service with SSC#001.

-

RTU is in service OFF The subordinate device (RTU, IED, etc.) is being processed.

- -

#059 Power supply failure in RTU central sub-rack

ON Failure of one configured power supply unit (e.g., 560PSU01) in rack

A hardware failure of the power supply unit has occurred.

Warning

Not all configured power supply units are plugged in.

Warning

Power supply OK in RTU central sub-rack

OFF The configured power supply units are error-free.

- -

Function Description Release 11 System data interface

Value Detailed description

Cause Error status

#060 RTU A active ON Included only for RTU A inoperable OFF Included only for

compatibility RTU B inoperable OFF Included only for

compatibility supervision circuit of a command

supervision board (e.g., 23BA22 or 23BA23) is defective.

A hardware failure of command

supervision board has occurred.

-

The command supervision board is not plugged in or was inserted at the wrong rack or slot position.

No process voltage is available.

-

The measured resistance of the connected coil is outside of the configured limits.

-

SEV offset

System message

Value Detailed description

Cause Error status The

LOCAL/REMOTE switch of the command

supervision board is in LOCAL position.

- supervision circuit is okay again.

This message is generated when a command is server is available with a plausible time.

#100 Local control authority active

ON The command from HCIs that are configured to interlock with local control authority of RTU will be blocked.

The local control authority is currently requested, e.g. by integrated HMI or by client on IEC 61850 station bus.

-

Local control authority available

OFF The local control authority can be requested by integrated HMI of the client on the IEC 61850 station bus.

Host #x offline [x= 1...16]

Line addressing is incorrect.

-

Function Description Release 11 System data interface

Value Detailed description

Cause Error status

#117 of the corresponding HCI is lost due to queue overflow.

See chapter ‘Host communication interface’

-

Hostinterface x:

All changes of information processed [x= 1...16]

OFF All information changes are reported to the connected host.

See chapter ‘Host communication

At least one pulse counter lost [x= 1...16]

At least one pulse counter is lost due to queue overflow or replacement.

See chapter ‘Host communication interface’.

-

Hostinterface x:

All pulse counters processed [x= 1...16]

All pulse counters are reported to the connected host.

See chapter ‘Host communication

CMU #x operable [x= 1...16]

The CMU is started and alive on the reachable on the system bus.

A hardware failure of CMU has occurred.

Error

The CMU is not plugged in.

Error

The redundant rack with the CMU is switched off

Error

The CMU is starting up. on redundant line x

[x= 1...4]

ON The subordinate devices (RTU, IED, etc.) are marked as reachable if a link to the device can be established according to the procedures described in the supporting SCIs.

- -

Device not reachable on redundant line x [x= 1...4]

OFF The subordinated device (RTU, IED, etc.) cannot be reached on line.

The physical connection to the device is defective.

-

A device failure has occurred.

-

#1841

#1871

Device active on redundant line x [x= 1...4]

SEV offset

System message

Value Detailed description

Cause Error status Device not active

on redundant line x

A link with higher priority is reachable, and is therefore the active link.

-

Another link was set as the preferred link using an

SSC#004…#007 system command.

-

Another link was set as the active link using an on redundant line x

[x= 1...4]

ON Link to subordinate device (RTU, IED, etc.) is considered as the preferred link during line

switchover

The link is the preferred link by configuration.

-

The link was set as the preferred link using an redundant line x [x= 1...4]

ON Supervised network element is

OFF Supervised network element (e.g.

Ethernet switch supervised by SNMP) is not connected or not operable

The network element is not running.

-

A physical or logical connection to redundant pair of CMUs.

OK

Function Description Release 11 System data interface

Value Detailed description

Cause Error status The CMU is a

non-redundant CMU.

No command collision with host no x

command is already in use. The collision with web server

The issued

command is already in use. The

transmitted command was negatively acknowledged.

A command issued by the RTU500 series' web server is already being executed.

No command collision with web server

- - -

#2601 Command collision with PLC

The issued

command is already in use. The

transmitted command was negatively acknowledged.

A command issued by a PLC function is already being executed.

No command collision with PLC

- - -

Table 30: System event messages

1Generated for directly connected subordinate devices by the SCI of the RTU. For more detailed information on the supported devices, refer to the corresponding Protocol Description manual.

2Generated for directly connected subordinate devices by the SCI of the RTU, or by the RTU itself.

10.2 System commands

The behavior of subordinate devices connected to a subdevice communication interface can be controlled with the help of system commands.

This table shows the available system commands (SSC = System Single Command).