LED indications for 560RTC03
SEV offset
System message
Value Detailed description
Cause Error status
#016 At least one data points of RTU are valid. RTU is invalid.
Note:
Overflow is not considered by this SEV. failure has occurred.
Warning
The analog settings are not correct.
Warning
SEV offset
System message
Value Detailed description
Cause Error status All analog values
correct
OFF There is no I/O bus error. All I/O boards and CVT modules with configured analog values are operable. No live zero underflow was detected.
- OK
#018 At least one digital value faulty
ON At least one local DMI or BSI data point of RTU is invalid or a wrong BCD coding was detected. failure has occurred.
Warning
A warning with regard to BCD coding or
configuration has occurred.
Warning
All digital values correct
OFF There is no I/O bus error. All I/O boards with configured digital values are operable. RTU is invalid.
The I/O board or failure has occurred.
Warning
All pulse counters correct RTU is invalid and not operable.
Function Description Release 11 System data interface
Value Detailed description
Cause Error status A command
supervision board (e.g., 23BA22 or 23BA23) is without process voltage. or RCO data points of the RTU are valid invalid and not operable.
All analog outputs correct
OFF All local ASO and SOC data points of the RTU are valid the RTU is invalid and not operable.
The I/O board is
All digital outputs correct
SEV offset
System message
Value Detailed description
Cause Error status RTU not active OFF The RTU cannot invalid data or required data are missing from the files.
Error
#025 RTU
synchronized
ON The RTU is
synchronized by the time master as configured.
- -
RTU not synchronized
OFF The time of the RTU is not synchronized and may deviate from the time of the time master.
No time
synchronization signal is received from the time master
-
The minute pulse is missing.
-
The RTC is missing, has an error or has not yet been synchronized.
-
The SNTP server is not available or has not been
synchronized.
-
#026 External clock inoperable
ON The configured external RTC clock is inoperable.
The RTU has not been synchronized yet by 560RTC0x.
Warning
An RTC or minute pulse is missing.
Warning
An RTC antenna error has occurred.
Warning
External clock operable
OFF The configured external RTC clock is operable.
- OK
#027 Local printer offline
ON The local printer is not working or out of order.
A printer connection failure has occurred.
- point is oscillating (Oscillating
suppression active).
The input signal oscillates within the configured limits.
Warning
All indications stable
OFF All configured SPI or DPI data points are stable.
- OK
Function Description Release 11 System data interface
Value Detailed description
Cause Error status
#029 Battery voltage low
ON Backup battery is not charged.
The battery is defect.
Warning
Check connection to battery.
Warning
Battery voltage OK
OFF Backup battery is charged.
- OK
#030 AC power supply failure
ON AC power supply is defective. RTU is running on backup battery.
No AC power is available.
Warning
The power supply unit is defect.
Warning
AC power supply OK equipment (DCE) is missing or not responding.
The DCE is switched off. are connected to the RTU.
- -
#0451 Device connected ON The connection to the device is
OFF The connection to the device via dial-up is currently not established.
No reportable data were received from the device.
-
No cyclic dial-up call from the RTU to the device is pending.
- function of the RTU is not running.
No boot project was loaded.
Warning
A PLC license is missing on the CMU,
Warning
An exception in a PLC user program has occurred.
Warning
SEV offset
System message
Value Detailed description
Cause Error status All PLC functions
running
OFF All configured PLC functions of the RTU are running.
- OK
#047 At least one PLC function cycle time exceeded
ON The cycle watchdog time of at least one PLC task was exceeded.
The PLC execution cycle time was longer than the watchdog time. The PLC function is restarted.
Warning
All PLC function cycle time OK
OFF All PLC task cycle times are within the configured
watchdog times.
- OK
#0481 RTU inoperable ON A subordinate device (RTU, IED, etc.) is inoperable or not connected.
A device address mismatch (such as link address, station address) has occurred.
-
RTU is operable OFF The subordinate device (RTU, IED, etc.) is operable and the connection to the RTU is established.
- -
#0491 RTU is out of service
ON The subordinate device (RTU, IED, etc.) was put out of service and is not being processed.
The subordinate device (RTU, IED, etc.) was put out of service with SSC#001.
-
RTU is in service OFF The subordinate device (RTU, IED, etc.) is being processed.
- -
#059 Power supply failure in RTU central sub-rack
ON Failure of one configured power supply unit (e.g., 560PSU01) in rack
A hardware failure of the power supply unit has occurred.
Warning
Not all configured power supply units are plugged in.
Warning
Power supply OK in RTU central sub-rack
OFF The configured power supply units are error-free.
- -
Function Description Release 11 System data interface
Value Detailed description
Cause Error status
#060 RTU A active ON Included only for RTU A inoperable OFF Included only for
compatibility RTU B inoperable OFF Included only for
compatibility supervision circuit of a command
supervision board (e.g., 23BA22 or 23BA23) is defective.
A hardware failure of command
supervision board has occurred.
-
The command supervision board is not plugged in or was inserted at the wrong rack or slot position.
No process voltage is available.
-
The measured resistance of the connected coil is outside of the configured limits.
-
SEV offset
System message
Value Detailed description
Cause Error status The
LOCAL/REMOTE switch of the command
supervision board is in LOCAL position.
- supervision circuit is okay again.
This message is generated when a command is server is available with a plausible time.
#100 Local control authority active
ON The command from HCIs that are configured to interlock with local control authority of RTU will be blocked.
The local control authority is currently requested, e.g. by integrated HMI or by client on IEC 61850 station bus.
-
Local control authority available
OFF The local control authority can be requested by integrated HMI of the client on the IEC 61850 station bus.
Host #x offline [x= 1...16]
Line addressing is incorrect.
-
Function Description Release 11 System data interface
Value Detailed description
Cause Error status
#117 of the corresponding HCI is lost due to queue overflow.
See chapter ‘Host communication interface’
-
Hostinterface x:
All changes of information processed [x= 1...16]
OFF All information changes are reported to the connected host.
See chapter ‘Host communication
At least one pulse counter lost [x= 1...16]
At least one pulse counter is lost due to queue overflow or replacement.
See chapter ‘Host communication interface’.
-
Hostinterface x:
All pulse counters processed [x= 1...16]
All pulse counters are reported to the connected host.
See chapter ‘Host communication
CMU #x operable [x= 1...16]
The CMU is started and alive on the reachable on the system bus.
A hardware failure of CMU has occurred.
Error
The CMU is not plugged in.
Error
The redundant rack with the CMU is switched off
Error
The CMU is starting up. on redundant line x
[x= 1...4]
ON The subordinate devices (RTU, IED, etc.) are marked as reachable if a link to the device can be established according to the procedures described in the supporting SCIs.
- -
Device not reachable on redundant line x [x= 1...4]
OFF The subordinated device (RTU, IED, etc.) cannot be reached on line.
The physical connection to the device is defective.
-
A device failure has occurred.
-
#1841
…
#1871
Device active on redundant line x [x= 1...4]
SEV offset
System message
Value Detailed description
Cause Error status Device not active
on redundant line x
A link with higher priority is reachable, and is therefore the active link.
-
Another link was set as the preferred link using an
SSC#004…#007 system command.
-
Another link was set as the active link using an on redundant line x
[x= 1...4]
ON Link to subordinate device (RTU, IED, etc.) is considered as the preferred link during line
switchover
The link is the preferred link by configuration.
-
The link was set as the preferred link using an redundant line x [x= 1...4]
ON Supervised network element is
OFF Supervised network element (e.g.
Ethernet switch supervised by SNMP) is not connected or not operable
The network element is not running.
-
A physical or logical connection to redundant pair of CMUs.
OK
Function Description Release 11 System data interface
Value Detailed description
Cause Error status The CMU is a
non-redundant CMU.
No command collision with host no x
command is already in use. The collision with web server
The issued
command is already in use. The
transmitted command was negatively acknowledged.
A command issued by the RTU500 series' web server is already being executed.
No command collision with web server
- - -
#2601 Command collision with PLC
The issued
command is already in use. The
transmitted command was negatively acknowledged.
A command issued by a PLC function is already being executed.
No command collision with PLC
- - -
Table 30: System event messages
1Generated for directly connected subordinate devices by the SCI of the RTU. For more detailed information on the supported devices, refer to the corresponding Protocol Description manual.
2Generated for directly connected subordinate devices by the SCI of the RTU, or by the RTU itself.
10.2 System commands
The behavior of subordinate devices connected to a subdevice communication interface can be controlled with the help of system commands.
This table shows the available system commands (SSC = System Single Command).
SSC