SIMIT is a powerful simulation platform which is integrated into the SIMATIC PCS 7 engineering by means of open interfaces, but which remains open for functional expansions as a result of its modular design. You do not need to be a specialist to gener-ate and apply simulations with SIMIT. It is merely necessary to use SIMIT’s graphic user interface – all mathematical and IT pro-cedures of a simulation are carried out by SIMIT in the back-ground.

As a platform for virtual commissioning of SIMATIC user soft-ware, SIMIT provides a wide range of performance: For exam-ple, SIMIT can be automatically configured for signal tests, or it can be used to simulate processes and complete plants of any complexity in real-time. SIMIT provides the appropriate simula-tion environment, from simple key-triggered PLC signal tests, testing of the drive level, physical simulation of the process re-sponse for a complete plant test, all the way to operator training.

SIMIT is designed such that its functionality and scope can be specifically adapted to individual requirements. The basic sys-tem already provides powerful simulation functions. Hardware and software modules can be used to specifically expand the SIMIT functionalities.

Simulation is supported by appropriate automated functions. For example, importing of a symbol table or a list of signal names is sufficient for automatic configuration of the signal links. If the Im-port/Export Assistant (IEA) is used in SIMATIC PCS 7 projects, the IEA data can be used in SIMIT for automatic establishment of a simulation environment. The standard patterns suitable for SIMATIC PCS 7 are already included in SIMIT.

Note:

SIMIT can be used together with SIMATIC PCS 7 V5, V6 and V7.

Function

A simulation is produced with SIMIT simply by "combining" indi-vidual components on a GUI. The predefined components are selected from a library, connected together, and parameterized.

Engineering on the PC with SIMIT

The SIMATIC user program generated in SIMATIC PCS 7 is loaded into the PLC simulation S7-PLCSIM, and receives the simulated I/O signals from SIMIT via the PLCSIM coupling. The interface is configured automatically in SIMIT by importing the symbol table from SIMATIC PCS 7. SIMIT can also generate the corresponding simulation environment automatically using the PCS 7 Import/Export Assistant (IEA). Simulation examples matched to example automation solutions are used for this. The complete interaction between automation and process (model) is completed by means of a process model.

If the SIMATIC PCS 7 operator station is coupled to PLCSIM, the complete automation function from the sensor to the automation and visualization systems and back again to the actuator can al-ready be tested on the SIMATIC PCS 7 engineering system in the technical office without the actual existence of the automa-tion hardware.

Factory Acceptance Test (FAT) of the overall plant with SIMIT The Factory Acceptance Test (FAT) tests the complete automa-tion funcautoma-tions. The actual automaautoma-tion systems (SIMATIC S7 con-troller) are loaded with the SIMATIC user software. SIMIT then simulates the input/output signals, instrumentation and field de-vices. The simulation values are transmitted as PROFIBUS DP telegrams to the individual automation systems via the SIMIT in-terface modules (IM-1, IM-2). The link between SIMIT and the automation level is carried out automatically by the SIMATIC PCS 7 hardware configuration. As already described for engi-neering on the PC, the IEA mechanisms can also be used to au-tomatically generate the test environment. If SIMIT handles the process simulation in addition, the FAT then becomes a plant test. Commissioning can already be carried out in the virtual pro-cess in an early phase of the project.

PCS 7 Add-on

fit for SIMATIC PCS 7 V7

T I M I S

PCS 7 engineering PCS 7 HMI

S7-PLCSIM

SIMIT: Simulation-based engineering

8

Training simulation with SIMIT

In conjunction with SIMATIC PCS 7 and S7- PLCSIM, SIMIT forms the simulation platform for a training system. Plant opera-tors can then be trained even before the real plant is fully func-tional.

The simulation models used provide a realistic plant response under various operating conditions (e.g. start-up and shutdown, safety-related shut-down, etc.). If necessary, special simulators can also be linked to SIMIT via the standardized OPC cli-ent/server coupling.

Additional features

Apart from the standard library, FlowNet provides a comprehen-sive library for simulation of material flows in single-material sys-tems. Individual library components or macro components can be created using editors. SIMIT’s scope of performance is rounded-off by animated, user-configured graphics as well as trend windows for visualization of simulation values.

T I M I S

PCS 7 engineering PCS 7 HMI

Hardware

Selection and Ordering Data Order No.

Basic system SIMIT Basic

SIMIT basic system for Windows 2000/XP Professional, 2 lan-guages (German, English)

9AP1 413-2AA40 D)

SIMIT ATS

Preferred configuration for test-ing of PCS 7 user software, com-prising:

• SIMIT Basic (9AP1 413-2AA40)

• PROFIBUS DP coupling (9AP1 434-2AA10)

• MCE (9AP1 440-2AA10)

• DGE (9AP1 442-2AA10)

9AP1 414-2AA30 D)

SIMIT couplings MPI coupling

Software module for linking SIMIT to SIMATIC S7 controllers via the multi-point interface

Can only be used in conjunction with MPI card or MPI adapter (USB, RS 232)!

9AP1 430-2AA10 C)

OPC server coupling

Software module for linking SIMIT to clients with OPC capability

9AP1 431-2AA10 D)

OPC client coupling

Software module for linking SIMIT to servers with OPC capability

9AP1 432-2AA10 C)

PLCSIM coupling

Software module for linking SIMIT to S7 PLCSIM

Can only be used in conjunction with S7 PLCSIM Version 5.2 or higher!

9AP1 433-2AA10

PROFIBUS DP coupling Software module for linking SIMIT to the PROFIBUS DP of SIMATIC S7 PLCs

Can only be used for and in con-junction with SIMIT interface mod-ules 9AP2 423-2AA10 and 9AP2 424-2AA10!

9AP1 434-2AA10 D)

C) Subject to export regulations: AL: N, ECCN: EAR99S D) Subject to export regulations: AL: N, ECCN: 5D992B1

SIMIT: Simulation-based engineering

8

D) Subject to export regulations: AL: N, ECCN: 5D992B1

More information Siemens AG Industry Sector Erlangen

Phone: +49 9131 7 43406 Fax: +49 9131 7 44060

E-mail: [email protected]

Additional information is available in the Internet under:

http://www.siemens.de/simit

SIMIT expansions ACI

Auto Control Interface, SIMIT expansion module for generation and implementation of auto-mated simulation procedures

9AP1 436-2AA10

MCE

Macro Component Editor, SIMIT expansion module for generation of macros from standard library elements

9AP1 440-2AA10

CTE

Component Type Editor, SIMIT expansion module for generation of libraries and library elements

9AP1 441-2AA10

DGE

Dynamic Graphics Editor, SIMIT expansion module for graphic processing of model charts and operating screens; animated graphics

9AP1 442-2AA10

TME

Trend & Message Editor, SIMIT expansion module for graphic display of signal trends and mes-sages

9AP1 443-2AA10

SMD

Structured Model Diagrams, SIMIT expansion module for gen-eration of models from templates and tables (PCS 7 Import/Export Assistant)

9AP1 444-2AA10

SIMIT library FlowNet

SIMIT library for modeling mate-rial flows in single-matemate-rial sys-tems using flow networks;

contains process engineering components for modeling such as equipment, tanks, pumps, pipes, etc.

9AP1 450-2AA10

Documentation

Complete documentation in elec-tronic form (PDF files) with SIMIT Basic software on CD--ROM; also available as hard copy on request

Selection and Ordering Data Order No.

SIMIT interface modules IM-1

Interface module for SIMIT for simulation of PROFIBUS DP slaves:

single-channel PCI plug-in card for simulation of one DP segment with max. 125 DP slaves; same design as SIMBApro PCI Can only be used with PROFIBUS DP coupling module 9AP1 434-2AA10!

9AP2 423-2AA10 D)

IM-2

Interface module for SIMIT for simulation of PROFIBUS DP slaves:

two-channel PCI plug-in card for simulation of two DP segments with max. 125 DP slaves each;

same design as SIMBApro PCI Can only be used with PROFIBUS DP coupling module 9AP1 434-2AA10!

9AP2 424-2AA10

Service

Software updating contract Provision of updates and upgrades, access to SIMIT hot-line

9AP1 470-2AD00

SIMIT consulting

Consulting on a daily basis, cus-tomer-specific training

9AP1 471-2AD00

Selection and Ordering Data Order No.

8

9/2 BANY:

Bus analysis for SIMATIC Ethernet and PROFIBUS networks

9/4 Amprolyzer:

Bus monitor for PROFIBUS diagnostics

9/5 System diagnostics for PROFIBUS DP/PA slaves 9/7 ibaPDA/ibaAnalyzer:

Fault tracking log - recording and analysis

Diagnostics

BANY: Bus analysis for SIMATIC Ethernet and