Operating a project
9.2 Controlling graphic objects
9.2.8 Simple alarm view
9.2.8.1 Description Purpose
Layout
The display of the simple alarm view depends on the configuration.
• The display shows all current, departed or acknowledged alarms of the selected alarm classes.
• The number of lines per alarm and number of visible lines are specified in the configuration.
Operator controls
The buttons have the following functions:
Button Function
This button is used to acknowledge an unacknowledged alarm.
This button triggers the function assigned to the "Edit" event for the selected alarm. Use this button to call the configured operator note for the selected alarm.
Use this button to browse upwards alarm by alarm.
Use this button to browse upwards through the alarm display page by page. Use this button to browse downwards through the alarm display page by page. Use this button to browse downwards alarm by alarm.
9.2.8.2 Touch control Procedure
Touch the desired control object in the alarm view on the touch screen of the HMI device.
9.2.8.3 Keyboard control Procedure
The simple alarm view also has a tab order for the list showing displayed alarms and all configured buttons.
Proceed as follows to acknowledge an alarm using the keys.
1. Activate the simple alarm view using TAB , according to the tab order.
2. Select the alarm to be acknowledged. The HOME, END , and keys can be used
4. Press the ENTER key.
9.2.8.4 Mouse and keyboard control Procedure
Mouse
Click the relevant button.
Keyboard
There is also a tab sequence also for the list with displayed alarms and all configured buttons within the alarm display.
For example, do the following to acknowledge an alarm using the keyboard.
1. Activate the screen display, for example with <Tab> according to the tab sequence. 2. Select the alarm to be acknowledged. You can use the keys <Home>, <End>, <Page
Up>, <Page Down>, <Up> and <Down> for this.
3. Hold the <Tab> key pressed until the button to be acknowledged is selected. 4. Press the <Return> button.
9.2.9 Recipe view
9.2.9.1 Description Purpose
The recipe view is a screen object that is used in runtime to display and edit recipe records.
Layout
The functions of the recipe view can be configured. To use the Recipe view on small panels, a simple view is also available, for example.
Different settings are also possible for whether the recipes available in the recipe view can only be selected or can also be changed.
Behavior
If you change to another screen and have not yet saved changes to the recipe data in the recipe view, you will be prompted to save the recipe data. The recipe name and the name of the recipe record are displayed to show which recipe data have not been saved yet.
When you change to a screen that contains a recipe view loaded with recipe data, the recipe data is automatically updated.
Operator controls
The following operator controls can be configured in the recipe view:
Operator control
element Function
Displays the configured operator notes of the given recipe view.
Creates a new recipe record in the recipe that is displayed in the specified recipe view. The recipe record values are preset with the values that were specified as "Default value" when the recipe was configured.
Saves the recipe data record which is currently displayed in the recipe view. The storage location is determined during configuration in the properties view for the recipe.
Saves the recipe record currently being displayed in the recipe view under a new name. The storage location is determined during configuration in the properties view for the recipe.
Deletes the recipe record that is displayed in the recipe view from the data medium of the HMI device.
Synchronizes the values of the recipe record that is currently displayed in the recipe view with the associated tags.
During synchronization, all values of the recipe record are written to the associated tags. Then the values are read from the tags and used to update the values in the recipe view.
Transfers the recipe record, which is currently displayed in the recipe view, to the connected PLC. Transfers the recipe record, which is currently loaded in the PLC, to the HMI device and displays it in the recipe view.
9.2.9.2 Touch control Procedure
Touch the desired operating element in the Recipe view on the touchscreen of the HMI device.
9.2.9.3 Keyboard control Procedure
Activate the recipe view using TAB , according to the configured Tab order.
The table below shows the shortcut keys used to control the recipe view:
Shortcut keys Function
CTRL + Creates a new recipe record in the recipe that is displayed in the
specified recipe view. The recipe record values are preset with the values that were specified as "Default value" when the recipe was configured.
CTRL + ENTER Saves the recipe data record which is currently displayed in the recipe
view. The storage location is determined during configuration in the properties view for the recipe.
CTRL
+ * Saves the recipe record currently being displayed in the recipe view under a new name. The storage location is determined during configuration in the properties view for the recipe.
CTRL + DELINS Deletes the recipe record that is displayed in the recipe view from the
data medium of the HMI device.
CTRL + = Synchronizes the values of the recipe record that is currently displayed in the recipe view with the associated tags.
During synchronization, all values of the recipe record are written to the associated tags. Then the values are read from the tags and used to update the values in the recipe view.
CTRL
+ Transfers the recipe record, which is currently displayed in the recipe view, to the connected PLC.
CTRL + Transfers the recipe record, which is currently loaded in the PLC, to the
HMI device and displays it in the recipe view.
9.2.9.4 Mouse and keyboard control Procedure
Mouse
Keyboard
Activate the recipe view, for example with <Tab> according to the tab sequence. The table below shows the shortcut keys used to control the recipe view:
Shortcut keys Function
<Ctrl+Space> Creates a new recipe record in the recipe that is displayed in the specified recipe view. The recipe record values are preset with the values that were specified as "Basic value" when the recipe was configured.
<Ctrl+Return> Saves the recipe data record which is currently displayed in the recipe view. The storage location is determined during configuration in the properties view for the recipe.
<Ctrl+*> Saves the recipe record currently being displayed in the recipe view under a new name. The storage location is determined during configuration in the properties view for the recipe.
<Ctrl+Del> Deletes the recipe record that is displayed in the recipe view from the data medium of the HMI device.
<Ctrl+=> Synchronizes the values of the recipe record that is currently displayed in the recipe view with the associated tags.
During synchronization, all values of the recipe record are written to the associated tags. Then the values are read from the tags and used to update the values in the recipe view.
<Ctrl+Down> Transfers the recipe record, which is currently displayed in the recipe view, to the connected PLC.
<Ctrl+Up> Transfers the recipe record, which is currently loaded in the PLC, to the HMI device and displays it in the recipe view.