• No results found

STANDARD VECTOR GROUP

In document Electrical Data (Page 59-69)

IEC 56 Rated operating

4.7.18 STANDARD VECTOR GROUP

Group Phase Displace Symbols Group (1)

Group (2) Group (3) Group (4)

00 1800 -300; 3300

+ 300

Yyo, Ddo, Dzo, Zdo Yy6, Dd6, Dz6, Zd6 Dy1, Yd1, Yz1, Zy1 Dy11,Yd11,Yz11, Zy11

4. 7.19 PARALLEL OPERATION OF TRANSFORMER 4. 7.19.1 Terminal Marking (Viewed from H.T. Side)

(1) 1φ transformer: - Subscripts are marked in DESCENDING ORDER.

FROM LEFT TO RIGHT.

(2) 3φ transformers: - Neutral is on extreme left and then phases are in sequence (R, Y, and B).

(3) Autotransformer: Neutral is on extreme left and then phases are in sequence (R, Y, and B).

4. 7.19.2 CONDITIONS FOR PARALLEL OPERATION

i. Same inherent phase angle difference between primary and secondary terminals.

(ii) Same voltage ratio (iii) Same frequency (iv) Same polarity (v) Same phase rotation

4. 7.20 LOAD SHARING BY TRANSFORMERS IN PARALLEL 4. 7.20(A) For two Transformers

PA = P (QA.ZB) / (ZA.QB + ZB.QA), PB = P (QB.ZA) / (ZA.QB + ZB.QA) Where PA = Load shared by TFR (A),

PB = Load shared by TFR (B) P = Total Load, QA = Rating of transformer (A)

QB = Rating of transformer (B),

ZA = % of impedance of transformer (A) ZB = % impedance of transformer (B)

Note. Currents are also shared by same proportionate as loads.

4. 7.20(B) For 3 Transformers

PA = P (QA.ZB ZC) / , PB = P (QB.ZC ZA) / , Pc = P (QC.ZA.ZB) /

Where = (QA.ZB ZC + QB.ZC ZA + QC.ZA.ZB)

Note: - Currents are also shared by same proportionate as loads.

4. 7.21. CIRCULATING CURRENTS 4. 7.21.(A) Two Transformers in Parallel

(i) For impedance having same ratio (R /X) ICr = (VA-VB) / (ZA+ZB)

(ii) For impedance having different ratio (R/X) ICr = (VA-VB)/Z,

Where Z = (RA +RB)2+(XA +XB)2

VA = Secondary terminal voltage of transformer (A) (Lower ratio) VB = Secondary terminal voltage of transformer (B) (Higher ratio), ZA = (VZA.VA) / (100 X IA), IA = F.L. current

VZA = % Imp. Voltage drop at F.L. Rating

4. 7.21 (B) Three Transformers in Parallel (i) For impedance having same ratio (R/X) ICrA = (VA – M ) / ZA ICrB = (VB – M) / ZB

ICrC = (VC-M) / ZC

Where M = (VA.ZB.ZC + VB.ZC.ZA +VC.ZA.ZB)/(ZA.ZB+ZB.ZC+ZC.ZA) 4. 7.22. TRANSFORMER TAPPINGS

Note: - (1) For 2 – winding transformer, tap changer is generally provided on the H.T. side i.e.

L.T. side voltage remains constant.

(2) For Autotransformer, tap changer is generally provided on the L.T. side i.e. H.T. side voltage remains constant.

Transformer % Winding under gone Tap change

Standard No. Of tap from normal tap

1. Distribution Transformer (11/0.4 or

11/6.6 KV) 2. 33/11KV

3. 132 / 33 KV 132 / 11KV 4. 220 / 132KV

220 / 33KV

10%

15%

20%

20%

20%

20%

20%

20%

+5% Up, -5% Below +5% Up, -10% Below

+10% Up, -10% Below +5% Up, -15% Below +10% Up, -10% Below

+5% Up, -15% Below +10% Up, -10% Below

+5% Up, -15% Below

4. 7.23 TRANSFORMER OIL DATA

4. 7.23.1 CHARACTERISTIC REQUIREMENTS OF IS, IEC, & BS SPECIFICATION FOR UNIHIBITED TRANSFORMER OIL DATA

Sl No

CHARACTERISTICS IS:335 1993 1 APPEARANCE Oil should be clear, transparent, free from suspended mater and sediments

2 DENSITY gm/cc Max@ 4 Inter facial Tension( N/m

Min. 1. Neutralization Value (mg KOH/ gm Max) 11 Neutralization Value

1. Total Acidity(mg KOH/

gm )

2. Inorganic Acidity

0.03 Max

12 Corrosive Sulphur Non- Corrosive

Non- corrosive Non- Corrosive Non- corrosive Non- Corrosive 13 Oxi. Inhibitor 0.05% Max Not-Detectable Not-Detectable Not-Detectable Not-Detectable 14 Water Content (ppm) Max

Bulk / Drum Delivery

50 40 40 20/30 20/30

15 S.K. Value Under

Consideration

- - - -

16 Accl. Ageing Test (Open Beaker Method with Copper Catalyst)

1. Tan Delta @ 90 0 C Max.

2. Resistivity Ohm-cm. @ 90 0 C

3. Resistivity Ohm-cm. @ 27 0 C

4. Total Acidity 5. Sludge Cont. (% / wt

20 Poly cyclic Aromatic Wt%, Max

- - - 3.0 3.0

4.7.23.2 CHARACTERISTIC REQUIREMENTS OF IS, IEC, & BS SPECIFICATION FOR INHIBITED TRANSFORMER OIL DATA

Sl No

CHARACTERISTICS IS:

12463/1988 1 APPEARANCE Oil should be clear, transparent, free from suspended mater and sediments 2 DENSITY gm/cc Max@ 29.5 4 Interfacial Tension

( N/m Min.

11 Neutralization Value 1. Total Acidity (mg KOH/ gm Max) 2. Inorganic Acidity

0.03

12 Corrosive Sulphur Non-

Corrosive

Non- Corrosive

Non- Corrosive Non- Corrosive

Non- Corrosive Oxi. Stability 164 Hrs

1. Neutralization Value ( mg KOH/ gm Max) 2. Sludge Cont.

(% / wt Max)

3. Volatile Acidity Max

0.4

Oxi. Stability 500 Hrs 1. Neutralization Value (mg KOH/ gm Max) Bulk / Drum Delivery

50 30/40 30/40 20/30 20/30

15 Accl. Ageing Test (Open Beaker Method with Copper Catalyst)

4. Total Acidity

5. Sludge Cont. (% / wt Max)

19 Poly cyclic Aromatic Wt%, Max

- - - 3.0 3.0

4.7.23.3 +HIGH QUALITY TRANSFORMER OILS FOR POWER TRANSFORMERS

Sl No

CHARACTERISTICS ASTM D 3487

TYPE-1

1 APPEARANCE CLEAR &BRIGHT

2 DENSITY gm/cc Max 0.91 @ 15 0 c 0.885 @ 20 0 c 0.895 @ 200 c 0.895 @ 200 c Min. Needle Neg. to Sphere grounded (25.4mm gap)

145 150 - - 2 Ageing Resistance as per

Badder (140 Hrs / 110 0 c) Saponification No. mg KOH /mg 3 Oxi. Stability Max. (Rotating

Bomb Test ) Minutes Min.

195 - - -

4 Oxi. Inhibitor % Mass/Max 0.08-0.3 - - 0.15-0.4

5 Corrosive Sulphur Non- Corrosive Non- Corrosive Non- Corrosive Non- Corrosive

6 Water Content (ppm) Max 35 10 - 30(Bulk)/40

4.7.23.4 TEST ON TRANSFORMER OIL IN SERVICE

Sl.

No

CHARACTERISTICS Voltages Test Method PERIODICITY PERMISSBLE LIMIT refilling prior to energizing then after 3 Months and after one

year 30 KV ( Min. ) refilling prior to energizing then after 3 months and after one Refilling prior to Energizing then after 3 Months and after 2

IS 6262/1971 After filling or Refilling prior to Energizing then after 2 years

1.0

5. Neutralization Value 1. Total Acidity MAX

ALL refilling prior to Energizing then after 3 Months and after one year

REFER IS 10593/1993/DGA

CHART

4. 7.24 DISOLVED GAS ANALYSIS

4.7.24.1 INTERPRETATION OF RESULTS 4.7.24.1.1 DOERNENBURGE RATIO METHOD

SUGGESTED FAULT DIAG.

CH4/H2 C2H2/C2H4 C2H2/CH4 C2H6/C2H2 Thermal Decomposition > 1.0 < 0.75 <0.3 >0.4 Corona (Low intensity P.D) <0.1 - <0.3 > 0.4 Arching (High intensity

P.D)

>0.1

<1.0

>0.75 >0.3 <0.4

4.7.24.1.2 ROGER’ S RATIO METHOD Method-I

SUGGESTED FAULT DIAGNOSIS

C2H2/C2H4 CH4/H2 C2H4/C2H6

Normal 0.1to 1.0 < 0.1 <1.0

Low Energy Density Arching <0.1 <0.1 <1.0 Arching (High intensity P.D) 0.1 to 3.0 0.1 to 1.0 >3.0 Low Temp. Thermal <0.1 0.1 to 1.0 1.0 to 3.0 Thermal >700 0 c <0.1 >1.0 1.0 to 3.0 Thermal <700 0 c <0.1 >1.0 >3.0 4. 7.24.1.2 ROGER’ S RATIO METHOD

Method-II

SUGGESTED FAULT DIAGNOSIS

CH4/H2 C2H6/CH4 C2H4/C2H6 C2H2/C2H4 If CH4 /H2 <0.1, then P.D

other wise Normal Deterioration

0 0 0 0

Slight Over Heating Below 150 0 c

1 0 0 0

Slight Over Heating Below 150 0 c to 200 0 c

1 1 0 0

Slight Over Heating Below 200 0 c to 300 0 c

0 1 0 0

General Conductor Overheating

0 0 1 0

Circulating Currents / Overheated

1 0 1 0

Flashover without power flow current

0 0 0 1

Tap Changer selector breaking current

0 1 0 1

Arc with Power flow 0 0 1 1

REMARKS

Ratio <1.0 is taken as 0, Ratio >1.0 is taken as 1

A given Ratio can be taken for Diagnosis if the concentration of one gas is at least equal to the limit values as below

Value in ppm

H2=200, CH4= 50, C2H6=15, C2H4=60, C2H2=15

4.7.24.2 KEY GAS METHOD

Decomposition of Oil

C2H4 > 150ppm 3. .Electric Discharge

H2 (60-70%), 2. Partial Discharge

H2 (80 –90 %)

2. Thermal ageing of oil

CO (90 –95 %)

> 350 ppm

H2 (5-10 %), C2H6 (1 –2 %), CH4 (2 - 5 %)

6. 1. Arching in Cellulose 2. Decomposition of Insulation

4.7.24.3 TOTAL DISSOLVED COMBUSTIBLE GAS LIMITS (TDCG) TDCG LIMITS in ppm INTERPRETATIONS

(0 – 720) Satisfactory operation – Unless individual gas acceptance values are exceeded

(721 – 1920) Normal Ageing / Slight Decomposition Unless individual gas acceptance values are exceeded (1921 – 4630) Significant Decomposition fault is to be

monitored

>4630 Very Substantial decomposition of oil.

Immediate action to be taken

4. 7.24.4 PERMISSIBLE LIMIT (IN ppm) OF GASSES FOR SERVICE TRANSFORMERS

GASSES TRANSFORMER

WITHIN 4 YEARS

TRANSFORMER 4-10 YEARS

TRANSFORMER AFTER 10 YEARS

C02 2000-3000 3000-4000 4000-6000

CO 150-300 300-450 400-550

C2H4 100-150 150-200 200-300

C2H2 20-30 30-50 30-60

H2 100-150 150-250 200-300

CH4 50-70 70-150 70-150

4.7.24.5OTHER INFORMATIONS DISINTIGRATION OF

TRANSFORMER OIL AT ORD. TEMP

RELATION OF EVOLVED GAS WITH TEMPERATURE

NATIONAL SPECIFICATIONS

GAS % TEMP. IN 0 C GAS COUNTRY SPECIFICATIONS

C02 1.17 >120 METHANE (CH4) USA ASTM D 1040 –73

Heavy Hydro Carbon

4.86 >120 ETHANE (C2H6) FRANCE N.F Cir. C 1.03

O2 1.36 >150 ETHYLENE

(C2H4)

GERMANY VDE – 0370

CO 19.21 >700 ACETYLENE

(C2H2)

INDIA IS 335

H2 59.10 SWEDEN SEN-14

N2 10.10 ITALY A.E.1.7

CH4 4.2 SWITZERL

AND

S.E.V.124

Total 100 UK BS 148

USSR GOST-981

IEC IEC: 296

4.7.25 TYPICAL VALUE OF CAPACITANCE & TAN OF TRANSFORMERS Voltage Rating Configuration Capacitance in nF Tan

HV – LV 4 - 5 0.002 - 0.005 HV - Tank 13 - 15 0.007 - 0.009 400/220 KV

LV - Tank 23 - 24 0.004 - 0.008

HV – LV 5 - 7 0.003 - 0.006

HV - Tank 10 - 12 0.005 - 0.010 220/132 KV

LV - Tank 19 - 22 0.004 - 0.010

HV – LV 5 - 7 0.003 - 0.006

HV - Tank 10 - 12 0.005 - 0.010 132/33 KV

LV - Tank 19 - 22 0.004 - 0.010

HV – LV 5 - 7 0.003 - 0.006

HV - Tank 10 - 12 0.005 - 0.010 132/11 KV

LV - Tank 19 - 22 0.004 - 0.010

HV – LV 5 - 6 0.003 - 0.006

HV - Tank 2.9 - 3.5 0.006 - 0.008 66/11 KV

LV - Tank 6 - 10 0.005 - 0.008 HV – LV 8 - 10 0.015 - 0.018 HV - Tank 11 - 13 0.015 - 0.020 33/11 KV

LV - Tank 15 - 17 0.015 - 0.020

In document Electrical Data (Page 59-69)

Related documents