When common switch ON/OFF status is applied as a manipulated signal from a sequence table block and logic chart block or from a designated function block in sequence connec-tion via its signal output terminal, the common switch status reflecting the manipulated signal status is referred to as common switch status manipulation.
Two types of manipulation signal outputs are available: a “latched” type and a “non-latched”
type.
The syntax form for status manipulation is shown below.
%SWnnnn.PV.H or %SWnnnn.PV.L
nnnn: Element number H: Latched type (*1) L: Non-latched type
*1: Latched type output is only supported by sequence table block.
SEE ALSO
For details on condition testing and status manipulation, see the following:
D3, “Sequence Control”
For details on latched type and non-latched type output, see the following:
“■ Manipulating Status Output of I/O Module” in A3.2.2, “Contact Output”
■ System Common Switches : PFCS/SFCS
Common switches (element numbers: %SW0001 to %SW0200) are fixed as system switches with fixed functions. The statuses of these common switches can be referred to by users.
The data for common switches %SW0001 to %SW0007 that are used as the station start ID switches and %SW0031, which is used as an extension common switch, are written by users.
Common switches %SW0097 to %SW0200 are valid only when the extension common switch is set to 1 (valid).
SEE ALSO
For details on station start ID common switches and enhanced common switches, see the followings:
“■ Station Start ID Switches”
“■ Extension Common Switch”
A list of system common switch is given below.
Table System Common Switches (1/3) : PFCS/SFCS
Switch No. Name Description
0001 initialization 1 (initial cold start), the previous value is retained in the case of restart.
0002 Restart 1 (restart), 0 (initial cold start)
0003 0
0004 Sequence table initial cold start command 1 (re-execution from start step) 0005 Sequence table restart command 1 (restart from the current step)
0006 0
0007 Momentary power failure/prolonged power failure
1 (power failure within the momentary power failure tolerant time); 0 (reset and start, power failure exceeds the momentary power failure tolerant time)
0008 to 0016 (Reserved)
0017 L-side CPU status 0 (normal), 1 (abnormal)
0018 R-side CPU status 0 (normal), 1 (abnormal)
0019 to 0020 (Reserved)
0021 Power status 0 (normal), 1 (abnormal either right or left side) 0022 to 0026 (Reserved)
0027 R-side CPU control status 1 (control), 0 (other) 0028 L-side CPU control status 1 (control), 0 (other) 0029 to 0030 (Reserved)
0031 Common switch extension 1 (enabled), 0 (disabled) 0032 to 0064 (Reserved)
0065 to 0072 CPU idle time (second) per minute 8 bit short integer 0073 to 0080 Communication load against one second 8 bit short integer 0081 to 0096 (Reserved)
0097 1st unit 1st slot IOM status
0 (normal or not defined), 1 (abnormal) 0098 1st unit 2nd slot IOM status
0099 1st unit 3rd slot IOM status 0100 1st unit 4th slot IOM status 0101 1st unit 5th slot IOM status 0102 1st unit 6th slot IOM status 0103 1st unit 7th slot IOM status 0104 1st unit 8th slot IOM status 0105 1st unit 9th slot IOM status 0106 1st unit 10th slot IOM status 0107 1st unit 11th slot IOM status 0108 1st unit 12th slot IOM status 0109 1st unit 13th slot IOM status 0110 1st unit 14th slot IOM status 0111 1st unit 15th slot IOM status 0112 1st unit 16th slot IOM status
Switch No. Name Description
Table System Common Switches (2/3) : PFCS/SFCS
Switch No. Name Description
0113 2nd unit 1st slot IOM status
0 (normal or not defined), 1 (abnormal) 0114 2nd unit 2nd slot IOM status
0115 2nd unit 3rd slot IOM status 0116 2nd unit 4th slot IOM status 0117 2nd unit 5th slot IOM status 0118 2nd unit 6th slot IOM status 0119 2nd unit 7th slot IOM status 0120 2nd unit 8th slot IOM status 0121 2nd unit 9th slot IOM status 0122 2nd unit 10th slot IOM status 0123 2nd unit 11th slot IOM status 0124 2nd unit 12th slot IOM status 0125 2nd unit 13th slot IOM status 0126 2nd unit 14th slot IOM status 0127 2nd unit 15th slot IOM status 0128 2nd unit 16th slot IOM status 0129 3rd unit 1st slot IOM status 0130 3rd unit 2nd slot IOM status 0131 3rd unit 3rd slot IOM status 0132 3rd unit 4th slot IOM status 0133 3rd unit 5th slot IOM status 0134 3rd unit 6th slot IOM status 0135 3rd unit 7th slot IOM status 0136 3rd unit 8th slot IOM status 0137 3rd unit 9th slot IOM status 0138 3rd unit 10th slot IOM status 0139 3rd unit 11th slot IOM status 0140 3rd unit 12th slot IOM status 0141 3rd unit 13th slot IOM status 0142 3rd unit 14th slot IOM status 0143 3rd unit 15th slot IOM status 0144 3rd unit 16th slot IOM status
Switch No. Name Description
A040102E.EPS
Table System Common Switches (3/3) : PFCS/SFCS
Switch No. Name Description
0145 4th unit 1st slot IOM status
0 (normal or not defined), 1 (abnormal) 0146 4th unit 2nd slot IOM status
0147 4th unit 3rd slot IOM status 0148 4th unit 4th slot IOM status 0149 4th unit 5th slot IOM status 0150 4th unit 6th slot IOM status 0151 4th unit 7th slot IOM status 0152 4th unit 8th slot IOM status 0153 4th unit 9th slot IOM status 0154 4th unit 10th slot IOM status 0155 4th unit 11th slot IOM status 0156 4th unit 12th slot IOM status 0157 4th unit 13th slot IOM status 0158 4th unit 14th slot IOM status 0159 4th unit 15th slot IOM status 0160 4th unit 16th slot IOM status 0161 5th unit 1st slot IOM status 0162 5th unit 2nd slot IOM status 0163 5th unit 3rd slot IOM status 0164 5th unit 4th slot IOM status 0165 5th unit 5th slot IOM status 0166 5th unit 6th slot IOM status 0167 5th unit 7th slot IOM status 0168 5th unit 8th slot IOM status 0169 5th unit 9th slot IOM status 0170 5th unit 10th slot IOM status 0171 5th unit 11th slot IOM status 0172 5th unit 12th slot IOM status 0173 5th unit 13th slot IOM status 0174 5th unit 14th slot IOM status 0175 5th unit 15th slot IOM status 0176 5th unit 16th slot IOM status 0177-0200 (Reserved)
Switch No. Name Description
A040103E.EPS
■ System Common Switches : KFCS2/KFCS £
Common switches (element numbers: %SW0001 to %SW0400; If the number of system common switches is not increased, %SW0001 to %SW0200) are fixed as system switches with fixed functions. The statuses of these common switches can be referred to by users.
Only the data for common switches %SW0001 to %SW0007 that are used as station start ID switches in a CS 3000 KFCS2/KFCS, are written by users.
A list of the system common switches in a CS 3000 KFCS2/KFCS is shown below.
Table System Common Switches (1/2) : KFCS2/KFCS £
Switch No. Name Description
0001 initialization 1 (initial cold start), the previous value is retained in the case of restart.
0002 Restart 1 (restart), 0 (initial cold start)
0003 0
0004 Sequence table initial cold start command 1 (re-execution from start step) 0005 Sequence table restart command 1 (restart from the current step)
0006 0
0007 Momentary power failure/prolonged power failure
1 (power failure within the momentary power failure tolerant time); 0 (reset and start, power failure exceeds the momentary power failure tolerant time)
0008 to 0016 (Reserved)
0017 R-side CPU status 0 (normal), 1 (abnormal)
0018 L-side CPU status 0 (normal), 1 (abnormal)
0019 FCU Fan status 0 (all normal), 1 (one or more abnormalities) 0020 FCU Temperature status 0 (all normal), 1 (one or more abnormalities) 0021 Power status 0 (normal), 1 (abnormal either right or left side)
0022 (Reserved)
0023 (Reserved)
0024 (Reserved)
0027 0028 0029
R-side CPU control status 1 (control), 0 (other)
0030
L-side CPU control status 1 (control), 0 (other)
FIO system 1 status 0 (normal or undefined), 1 (abnormal) FIO system 2 status 0 (normal or undefined), 1 (abnormal) 0031 to 0032 (Reserved)
Switch No. Name Description
A040104E.EPS
0025 (Reserved)
0026 (Reserved)
Table System Common Switches (2/2) : KFCS2/KFCS £ Switch
No. Name Description
0033 to 0048
FIO system 1 NODE1 to 16
status 0 (NODE ready, communication possible), 1 (NODE fail, communication impossible) 0049 to
0064
FIO system 2 NODE1 to 16
status 0 (NODE ready, communication possible), 1 (NODE fail, communication impossible)
0097 Node1 Slot1 Status (*1) 0 (Ready or Undefined), 1 (IOM Error)
Switch
No. Name Description
A040105E.EPS
0065 to 0072
CPU idle time (second)
per minute 8 bit short integer 0073 to
0080
Communication load against one second
0081 to
0096 (Reserved)
8 bit short integer
0098 Node1 Slot2 Status (*1) 0 (Ready or Undefined), 1 (IOM Error)
0176 Node10 Slot8 Status (*1) 0 (Ready or Undefined), 1 (IOM Error)
...
0177
(*2) Node11 Slot1 Status 0 (Ready or Undefined), 1 (IOM Error)
0216
(*2) (*3) Node15 Slot8 Status 0 (Ready or Undefined), 1 (IOM Error) 0217 to
0400 (*3)
(Reserved)
...
*1: %SW0097 to %SW0176 are used for indicating IOM status.
*2: Only when the option [Increase Number of System Common Switches] is checked on FCS properties sheet , the common switches between %SW0177 and %SW0216 are indicating the IOM status.
*3: If the option [Increase Number of System Common Switches] is not checked on FCS properties sheet, the common switches between %SW0201 and %SW0400 are not system common switches but user-defined common switches.
TIP
The common switches from %SW0097 to %SW0176 take the following actions under the following circumstances.
• When both SB301 cards or both communication cards of the node fail, the corresponding common switch keep the previous status.
• When serial and Ethernet communication card do not communication properly, the corresponding switch is set to 1.
■ System Common Switches : LFCS2/LFCS £
Common switches (element numbers: %SW0001 to %SW0400; If the number of system common switches is not increased, %SW0001 to %SW0200) are fixed as system switches with fixed functions. The statuses of these common switches can be referred to by users.
Only the data for common switches %SW0001 to %SW0007 that are used as station start ID switches in a CS 3000 LFCS2/LFCS, are written by users.
A list of the system common switches in a CS 3000 LFCS2/LFCS is shown below.
Table System Common Switches (1/2) : KFCS2/LFCS £
Switch No. Name Description
0001 initialization 1 (initial cold start), the previous value is retained in the case of restart.
0002 Restart 1 (restart), 0 (initial cold start)
0003 0
0004 Sequence table initial cold start command 1 (re-execution from start step) 0005 Sequence table restart command 1 (restart from the current step)
0006 0
0007 Momentary power failure/prolonged power failure
1 (power failure within the momentary power failure tolerant time); 0 (reset and start, power failure exceeds the momentary power failure tolerant time)
0008 to 0016 (Reserved)
0017 R-side CPU status 0 (normal), 1 (abnormal)
0018 L-side CPU status 0 (normal), 1 (abnormal)
0019 FCU Fan status 0 (all normal), 1 (one or more abnormalities) 0020 FCU Temperature status 0 (all normal), 1 (one or more abnormalities) 0021 Power status 0 (normal), 1 (abnormal either right or left side) 0022 RIO Power status 0 (all normal), 1 (one or more abnormalities) (*1)
0023 (Reserved)
0024 (Reserved)
0025 RIO Fan status 0 (all normal), 1 (one or more abnormalities) 0026 RIO Temperature status 0 (all normal), 1 (one or more abnormalities) 0027 R-side CPU control status 1 (control), 0 (other)
0028 L-side CPU control status 1 (control), 0 (other)
0029 RIO system 1 status 0 (normal or undefined), 1 (abnormal) 0030 RIO system 2 status 0 (normal or undefined), 1 (abnormal) 0031 to 0032 (Reserved)
Switch No. Name Description
A040107E.EPS
*1: If the RIO power supply is configured in a single loop circuit, the value of %SW0022 is always 1.
Table System Common Switches (2/2) : LFCS2/LFCS £ Switch
No. Name Description
0033 RIO system 1 NODE1 status
0 (NODE ready, communication possible), 1 (NODE fail, communication impossible) 0034 RIO system 1 NODE2 status
0035 RIO system 1 NODE3 status 0036 RIO system 1 NODE4 status 0037 RIO system 1 NODE5 status 0038 RIO system 1 NODE6 status 0039 RIO system 1 NODE7 status 0040 RIO system 1 NODE8 status 0041 RIO system 1 NODE9 status 0042 RIO system 1 NODE10 status 0043 RIO system 1 NODE11 status 0044 RIO system 1 NODE12 status 0045 RIO system 1 NODE13 status 0046 RIO system 1 NODE14 status 0047 RIO system 1 NODE15 status 0048 RIO system 1 NODE16 status 0049 RIO system 2 NODE1 status 0050 RIO system 2 NODE2 status 0051 RIO system 2 NODE3 status 0052 RIO system 2 NODE4 status 0053 RIO system 2 NODE5 status 0054 RIO system 2 NODE6 status 0055 RIO system 2 NODE7 status 0056 RIO system 2 NODE8 status 0057 RIO system 2 NODE9 status 0058 RIO system 2 NODE10 status 0059 RIO system 2 NODE11 status 0060 RIO system 2 NODE12 status 0061 RIO system 2 NODE13 status 0062 RIO system 2 NODE14 status 0063 RIO system 2 NODE15 status 0064 RIO system 2 NODE16 status
Switch
Name Description
0065 to 0072
CPU idle time (second)
per minute 8 bit short integer 0073 to
0080
Communication load against one second