T03-02 External alarm

Objective:

Verify that all external alarms can be reported to OMC normally.

Result:

Pass Fail Not Run Zapped

Comment & Remark:

There are 16 external environment alarms on site. All of alarms are Boolean values. If the alarm appears, the alarm can be displayed normally on OMC. When the alarm recovers, the corresponding alarm will disappear on OMC.

Procedure Expected result Result

Check the Intruder alarm Intruder sensor properly installed &

terminated till BTS. Open & close BTS Room Door to generate & clear the intruder alarm respectively & verify from OMCR

Pass Fail Not Run Zapped

Check the Fire Panel alarm

Fire Panel properly installed & terminated till BTS.

As a precaution, the “Gas Activation Switch” is switched off and after the activity changed back to “ON”. Open the main equipment room’s “AC Distribution Box”

and turn the MCB for the “Fire Panel Alarm” to the "OFF" position. After few seconds an audible alarm should be heard

Pass Fail Not Run Zapped

from the “Fire Alarm Panel”.

Check with OMC-R that they can see this alarm. In the “AC Distribution Box” switch ON the “Fire Alarm Panel – MCB”. Check with the OMC-R that the alarm has gone.

Check the Smoke Detector alarm

Smoke sensors are properly installed &

terminated till BTS.

As a precaution, the “Gas Activation Switch” is switched off and after the activity changed back to “ON”.

Open the “Fire Alarm Control Panel” front cover. Pull down the fire alarm "Pull Down Switch" located on the “Equipment Room Wall”, the “Fire Alarm Bell” should start to ring. Silence the bell with the "Silence Bell"

soft key located on the “Fire Alarm Control Panel”.

Check with the OMC-R that they can see this alarm. Reset the “Fire Alarm Control Panel” by pressing the "Reset Alarm" soft key on the “Fire Alarm Control Panel”.

Check with the OMC-R that the alarm has gone.

Close the “Fire Alarm Control Panel” front cover.

Pass Fail Not Run Zapped

Check the Over temp alarm

Over temp sensor properly installed &

terminated till BTS.

On A/C Panel, Set the over temperature threshold below 28 °C. Over Temperature alarm will be reported at the OMCR. Verify from OMCR & set over temperature threshold back to 28 °C.

Pass Fail Not Run Zapped

Check the Humidity alarm

Humidity sensor properly installed &

terminated till BTS.

Locate the “Humidity Sensor”, which is installed on one of the “Equipment Room Walls”.

Pass Fail Not Run Zapped

Set the humidity upper limit at 20% with OMCR. After few seconds, Check with OMC-R that they can see this alarm. Set the humidity upper limit back to 85%, Check with the OMC-R that the alarm has gone.

Check the Water leakage alarm

Water leakage sensor properly installed &

terminated till BTS.

Locate the “Water Leakage Sensor”, located on one of the “Equipment Room Walls” at floor level. Immerse the Water Leakage Sensor into water. After few seconds, Check with OMC-R that they can see this alarm. Take out the Water Leakage Sensor from the water, Check with the OMC-R that the alarm has gone.

Pass Fail Not Run Zapped

Check the Gas release alarm

FSS properly installed & terminated till BTS.

As a precaution, the “Gas Activation Switch” is switched off and after the activity changed back to “ON”.

The Test will be done by using “LOOP Test Method”.

Remove the [Jumper] cables of “Gas Released” on EMU, the alarm of “Gas Released” will be reported to OMCR.

Reconnect the [Jumper] cables; the alarm should be cleared in OMCR

Pass Fail Not Run Zapped

Check the Generator Running alarm

Open the “Main Switch DB” in Genset Room. Disconnect the WAPDA supply from the Main Switch. Genset will be started. Generator Running alarm will be reported at the OMCR. Verify from OMCR

& Switch ON the MCB.

Pass Fail Not Run Zapped

Check the Tower light alarm

Tower light sensor properly installed &

terminated till BTS.

Cover the sun switch with a cloth. Tower

Pass Fail Not Run Zapped

lights will turn on. Now remove one bulb from the holder & Tower light failure alarm will be reported at OMCR. Clear the alarm once bulb is installed back & verify from OMCR.

Check Air Conditioner Failure Alarm

Air Con Panel properly installed &

terminated till BTS. Alarm to be actuated when both Air Conditioners are operating

Pass Fail Not Run Zapped

Check Mains Failure Alarm

Alarm to be actuated when Input Commercial Supply for Rectifier has suspended / failed

Pass Fail Not Run Zapped

Check Low Battery Voltage alarm

Alarm to be actuated when Battery Bank

discharge voltage <= 49 volts Pass Fail Not Run Zapped Check the

Rectifier Major alarm

No: of Rectifier modules having faults=>1,

Pass Fail Not Run Zapped

Check the Rectifier Minor Alarm

Condition: Alarm to be actuated when lightning surge has affected the system

Pass Fail Not Run Zapped

Check the Generator Failure alarm

Open the “Main Switch DB” in Genset Room. Disconnect the WAPDA supply from the Main Switch. Genset will be started. Wait for consistent response of the Genset, for some time.

Locate the “OutPut Switch” on the Front Panel of Genset. Change the Output Switch to “OFF” position. The Output supply of the Genset will be disconnected.

The alarm of “Generator Failure” (Alarm – 15) will be reported in OMCR. Change the position of “Output Switch” to “ON”

position. The supply of Genset will be again commenced. Reconnect the WAPDA supply by changing position of Main Switch to “ON” position.

Pass Fail Not Run Zapped

Check the Gen Low Fuel alarm

Take the fuel float with the cover out of the

tank. Check with OMC-R that they can see Pass Fail Not Run Zapped

this alarm. At the fuel float with cover inserted to the tank. Check with the OMC-R that the alarm has gone.