• No results found

TABLE 5.10.1.3.4-4 OP5-0 SETPOINTS

In document TM 9-6115-484-14 MEP-PU-810A/B PART 3 (Page 145-148)

SETPOINTS OP5-0 ENGINE/GENERATOR PROGRAMMING

SETPOINT-NAME-DESCRIPTIONS RANGE OF VALUES FACTORY DEFAULT

DPGDS SETPOINT

P001 - Fuel Solenoid Type: type of fuel system solenoid used on the genset.

0- ETR fuel solenoid

1- ETS fuel solenoid 0 0

P002 - Units Shown: type of measurement units shown on the GSC+ display.

0-for English units (PSI, ºF)

1-for metric units (kPa, ºC). 0 0

P003 - Shutdown Override For Engine Fault: GSC+

response to a low engine oil pressure or high coolant temperature fault.

0-for engine shutdown

1-for alarm only (shutdown override, no engine shutdown).

0 0

P004 - Shutdown Override For Sensor Fault: GSC+

response to a diagnostic fault with the engine oil pressure sensor, coolant temperature sensor, oil temperature sensor, sensor power supply or coolant loss sensor.

0-for alarm only shutdown override, no engine shutdown).

1-for engine shutdown.

0 0

P005 - Coolant Loss Sensor Installed: tells whether or not the optional engine coolant loss sensor is installed on the genset.

0-for gensets without a coolant loss sensor

1-for gensets with coolant loss sensor 0 1

P006 - Shutdown Override For Coolant Loss Fault:

GSC+ response to an engine coolant loss fault.

0-for engine shutdown.

1-for alarm only (shutdown override, no engine shutdown).

0 0

P007 - System Voltage, 24 Or 32 Volts: system voltage

(battery voltage) of the genset. 24 or 32. 24 24

P008 - This setpoint is not currently being used by the

GSC+ and cannot be programmed. N/A N/A N/A

P009 - Number Of Ring Gear Teeth: number of teeth on the ring gear of the engine. Used by the GSC+ to determine engine speed.

95 to 350 teeth in increments of one tooth. 136 teeth 136 teeth

P010 - Engine Overspeed: engine speed used by the GSC+ to declare that an engine overspeed fault exists.

The engine overspeed setpoint (for all 60 Hz applications) is 1.18 times the rated speed.

500 to 4330 rpm in increments of 10 rpm. 2120 rpm 2120 rpm

P011 - Crank Terminate Speed: engine speed used by the GSC+ to disengage the starting motor during engine cranking.

100 to 1000 rpm in increments of 10 rpm. 400 rpm 400 rpm

P012 - Oil Step Speed: engine speed used by the GSC+

for distinguishing between rated speed and idle speed when a low oil pressure fault exists.

400 to 1800 rpm in increments of 10 rpm. 1350 rpm 1350 rpm

P013 - Low Oil Pressure Shutdown At Rated Speed:

oil pressure used by the GSC+ to declare that a low oil pressure shutdown fault exists with engine at rated speed (the engine speed must have exceeded the oil step speed for nine seconds).

oil pressure used by the GSC+ to declare that a low oil pressure shutdown fault exists with the engine at idle speed (the engine must have been running for at least 9 seconds and the engine speed must be less than oil step speed).

20 to 336kPa (3 to 49PSI) in increments of 1 10 PSI (70 kPa)

10 PSI (70 kPa)

P015 - High Water Temperature Shutdown: coolant temperature used by the GSC+ to declare a high coolant temperature shutdown fault exists (after a 10 second delay).

185 to 253ºF (85 to 123ºC) in increments of 1

225ºF (107ºC)

225ºF (107ºC)

P016 - Low Water Temperature Alarm: coolant temperature used by the GSC+ to declare that a low coolant temperature alarm fault exists (after a 2 second delay).

32 to 97ºF (0 to 36ºC) in increments of 1 70ºF (21ºC)

70ºF (21ºC)

USA TM 9-6115-484-14 DRS RADIAN CTM: 01646.1R0253/1R0254 TABLE 5.10.1.3.4-4 OP5-0 SETPOINTS (CONTINUED)

SETPOINTS OP5-0 ENGINE/GENERATOR PROGRAMMING

SETPOINT-NAME-DESCRIPTIONS RANGE OF VALUES FACTORY DEFAULT

DPGDS SETPOINT

P017 - Total Cycle Crank Time: cycle crank time used by the GSC+ to declare that an overcrank fault exists.

5 to 120 seconds in increments of 1

second. 90 seconds 90 seconds

P018 - Cycle Crank Time: amount of time the GSC+ cranks and then rests the starting motor during a single crank cycle.

5 to 60 seconds in increments of 1

second. 10 seconds 10 seconds

P019 - Cooldown Time: amount of time the GSC+ allows the engine to run after a normal shutdown is initiated.

0 to 30 minutes in increments of 1

minute. 5 minutes 5 minutes

P020 - AC Voltage: nominal AC voltage of the generator.

The GSC+ measures the AC voltage and shows it on the display.

700, 150, 300, 500, 600, 750, 3.0k, 4.5k, 5.20k, 5.25k, 9.0k, 15.0k, 18.0k,

30.0k 700 5.20k

P021 - AC Current Full Scale: nominal full scale AC current of the generator. AC current full scale is equal to the ratio of the external current transformers in the generator housing.

75, 100, 150, 200, 300, 400, 600, 800, 1000, 1200, 1500, 2000, 2500, 3000, and 4000A

600A 100A

P022 - GSC+ Engine Number: informs other devices on

the CAT Data Link of the engine number for the GSC+. 01 through 08 01 01 (Gen 1) 02 (Gen 2)

SETPOINTS - OP5-0-ENGINE/GENERATOR PROGRAMMING SETPOINT-NAME-DESCRIPTIONS RANGE OF

VALUES

FACTORY

DEFAULT 60HZ

SETPOINT 50HZ SETPOINT

P023 - Engine Type: identifies the engine as a mechanical unit injector (MUI) diesel, spark ignited (gas), or electronic unit injector (EUI) diesel engine.

0 - MUI diesel 1 - Gas 2 - EUI diesel

0 2 2

P024 - Crank Time Delay: amount of time the GSC+ delays activation of the fuel control relay (FCR) during a crank cycle. This setpoint is for Gas engines only. The P024 setpoint only functions when the P023 setpoint is set to 1 (gas engine).

0 to 20 seconds in increments of 1

second. 5 Seconds 5 Seconds 5 Seconds

P025 - Oil Temperature Sensor Installed: tells whether or not the optional engine oil temperature sensor is installed on the genset.

0 - for gensets without an oil temperature sensor 1 - for gensets with an oil temperature sensor

0 0 0

P026 - High Oil Temperature Shutdown: oil temperature used by the GSC+ to declare a high oil temperature shutdown fault exists (after a 10 second delay). Refer to the panel model number.

185 to 253ºF (85 to 123ºC) in

increments of 1 225ºF (107ºC) 225ºF (107ºC) 225ºF (107ºC)

P027 - Shutdown Override For High Oil Temperature Fault: GSC+ response to an engine high oil temperature fault.

0 - for alarm only (shutdown override, no engine shutdown).

1 - for engine shutdown.

0 0 0

P028 - Nameplate Voltage: rated voltage of the generator. This setpoint is used for protective relaying functions.

100 to 25kV in increments of 1 480V 4160V 3800V

P029 - Nameplate Current: rated current output

of the generator. 0 to 4000 A in increments of 1 600A 80A 73A

P030 - Nameplate Power: rated power capability

of the generator. 0 through 10MW in increments of

1kW. 400kW 420kW 350kW

P031 - Rated Frequency: nominal frequency

rating of genset. 50 or 60Hz 60Hz 60Hz 50Hz

P032 - Connection Configuration Of Generator:

wye or delta configuration of generator.

0 - wye

1 - delta 0 0 0

P033 - Number Of Generator Poles. 0 through 254 in increments of 2. 4 4 4

① The setpoints (stored or being programmed) must match the specified DPGDS setpoints.

② When oil pressure drops to within 5PSI (34kPa) of the P013 or P014 setpoint, a low oil pressure alarm is issued by the GSC+.

③ When coolant temperature rises to within 11ºF (6ºC) of the P015 setpoint, a high coolant temperature alarm is issued by the GSC+.

④ The values other than the default (700V) are for switchgear applications and require the use of external potential transformers and the removal of the AC voltage range jumper located in the relay module.

The DPGDS unit is factory configured for the 5.20 K value. See the Caterpillar Electronic Modular Control Panel II+ manual topic AC Voltage Range Selection in the Testing and Adjusting section.

⑤ After setpoint P022 is reprogrammed, the GSC+ must be power cycled (powered down and then powered up)

USA TM 9-6115-484-14 DRS RADIAN CTM: 01646.1R0253/1R0254

In document TM 9-6115-484-14 MEP-PU-810A/B PART 3 (Page 145-148)