• No results found

Test-Set Connections

In document Testing Relay (Page 120-127)

Simple Percent Differential (87) Element Testing

A) Test-Set Connections

The test-set connections for a simple slope test are as follows. Some tests require large amounts of current which will require the connection in Figure 12-28.

A Phase Amps

W2 Test Amps 180° Test Hz

W1 RELAY INPUT

Figure 12-27: Simple 87-Element Slope Test-Set Connections

A Phase Amps

W2 Test Amps 180° Test Hz

Figure 12-28: Simple 87-Element High Current Slope Test-Set Connections

Principles and Practice

270

© 2012 Valence Electrical Training Services LLC. All rights reserved.

www.valenceonline.com B) Slope Test Procedure

The test procedure seems straightforward. Apply equal current into Winding-1 and Winding-2 with a 180º phase shift between windings, and raise one current until the relay operates. The difficult part of this procedure is determining what starting current to apply and what the expected pickup should be. We can start by re-plotting the characteristic curve shown in Figure 12-29 using the following relay settings.

• Phase Differential Trip = Unlatched

• Assign Trip Relays = 1

• Differential Trip Minimum Pickup = 0.1 x CT

• Differential Trip Slope-1 = 20%

• Differential Trip Slope-2 = 80%

• Differential Trip Delay = 0 cycles

Differential Protection 20/80% Characteristic Curve

0.00 0.50 1.00 1.50 2.00 2.50 3.00

0.00 1.00 2.00 3.00 4.00 5.00 6.00 7.00 8.00

Restrain Current (Ir) x TAP Operate Current (Iop)xTAP

Trip Area

Restraint Area Slope 1

Slope 2

Figure 12-29: Percentage Differential Protection Dual Slope Characteristic Curve

We first need to change the restraint and operate current values to amps instead of multiples of Tap. Then we can calculate the transition point between the Minimum Pickup and Slope-1 operation. The Minimum Pickup is 0.50A (0.1 CT× ) as we calculated earlier in this chapter. Slope-1 will be enabled when the operate current is greater than the minimum pickup. Different relays have different slope calculations and we can refer to the GE 489 relay instruction manual to determine the relay’s differential calculation as shown in Figure 12-30.

Chapter 12: Simple Percent Differential (87) Element Testing

© 2012 Chris Werstiuk and Valence Electrical Training Services LLC. All rights reserved. 271

FUNCTION:

The 489 percentage differential element has dual slope characteristic. This allows for very sensitive settings when fault current is low and less sensitive settings when fault current is high, more than 2 x CT, and CT performance may produce erroneous operate signals.

The minimum pickup value sets an absolute minimum pickup in terms of operate current. The delay can be fine tuned to an application such that it still responds very fast, but rides through normal operational disturbances.

The Differential element for phase A will operate when:

Operate Restraint

Differential elements for phase B and phase C operate in the same manner.

Figure 12-30: GE 489 Differential Formulas Notice that the Ir current (IRestraint) is defined as

2

I + I for our terminology. The bars on either side of each current indicate that we use

absolute values when calculating the restraint current. We can drop the bars and re-define Ir as 1 2

W 2 W

I +I . The Iop current (IOperate) is defined as IA Ia which can be translated into

1 2

W W

I I for our calculations. The bars above each current indicate a vector sum calculation and we can redefine the Iop calculation as IW1IW2 because our vectors will always be 180º apart.

Use the first IOperate formula to calculate the transition between Minimum Pickup and Slope-1 where Slope-1 begins when Iop exceeds the Minimum Pickup setting (0.5A) defined previously. Notice that our generic formula on the right also works for this relay. Based on these calculations, our restraint current must be greater than 2.505A to test Slope-1.

0.501 20%

100 0.501 50.1 2.505

20% 20

Principles and Practice

272

© 2012 Valence Electrical Training Services LLC. All rights reserved.

www.valenceonline.com

Figure 12-31 displays the revised characteristic curve so far.

Differential Protection 20% Characteristic Curve

0.0 5.0 10.0 15.0 20.0 25.0 30.0 35.0

0 1 2 3 4 5 6 7 8 9 10 11 12 13 14

Restraint Current (Ir in Amps) Operate Current (Iop in Amps)

Trip Area

Restraint Area Slope

1

Min

Transition 1

Figure 12-31: Example Characteristic Curve in Amps with 1st Transition Defined

We also need to determine the maximum restraint current before we accidentally start testing Slope-2 when testing Slope-1. We can use the slope formula (Slope(%) 100 Iop

= × Ir ) to calculate the restraint current (Ir) at the transition point between Slope-1 and Slope-2 but we first need to define the transition point. This is usually the Breakpoint setting, but this setting is not available in the GE 489 relay. A quick review of the manufacturer’s operate description (Figure 12-32) of the manual informs us that the breakpoint is pre-defined as 2 times CT.

where:

IOperate

IRestraint

k IA

Ia

= operate current = restraint current

= characteristic slope of differential element in percent (Slope 1 if IR < 2 X CT, Slope 2 if IR > = 2 X CT) = phase current measured at the output CT = phase current measured at the neutral end CT Differential elements for phase B and phase C operate in the same manner.

Figure 12-32: Percentage Differential Protection Dual Slope Characteristic Curve

Chapter 12: Simple Percent Differential (87) Element Testing

© 2012 Chris Werstiuk and Valence Electrical Training Services LLC. All rights reserved. 273

You can use the same Minimum Pickup formulas to calculate the transition from Slope-1 to Slope-2. This time we’re going to expand the formula to determine the actual W1 and W2 currents instead of operate and restraint currents.

1 2

The maximum amount of Ir

W W

is defined as Ir<10A

2 1.222

9.99 2

19.98 2.222 8.99

Slope 1 expected test currents can be defined by:

1.222

The maximum amount of Ir is defined as Ir<10A

W W W

Principles and Practice

274

© 2012 Valence Electrical Training Services LLC. All rights reserved.

www.valenceonline.com

The new characteristic curve will look like Figure 12-33.

Differential Protection 20/80% Characteristic Curve

0.0 5.0 10.0 15.0 20.0 25.0 30.0 35.0 40.0 45.0 50.0

0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 Restraint Current (Ir in Amps)

Operate Current (Iop in Amps)

Trip Area

Restraint Area Slope 1

Min Transition 1

Slope 2 Transition 2

Figure 12-33: Percentage Differential Protection Dual Slope Characteristic Curve

© 2012 Chris Werstiuk and Valence Electrical Training Services LLC. All rights reserved. 285

Chapter 13

In document Testing Relay (Page 120-127)