Trackfeeder Cable

In document Cable Handbook (Page 54-68)

Application

Standards Conductor

Separator Sheath

Sheath Colour Voltage Rating Temperature Rating

Provides the 650/750 volt D.C. supply from traction substations and track paralleling huts to conductor rails, negative cable connections and where appropriate, bonding.

NR/PS/ELP/21101 (formerly RT/E/S/21101)

Class 2 stranded aluminium or tinned copper to BS EN 60228:2005 (previously BS6360)

PETP (Polyethylene Terephthalate)

CSP (Chlorosulphonated Polyethylene) Type RS4 to BS6899

Black

650/750V

-25°C to +85°C

Minimum Bending

Radius Aluminium conductor: 10 x overall diameter Copper conductor: 8 x overall diameter

Dimensions

Rail Catalogue

Number Nominal

Cross Sectional

Area mm²

Conductor

Material No. and Nominal Diameter of

Strands

# / mm

Nominal Diameter of

Conductor mm

Nominal Overall Diameter mm

Assigned Continuous

Current Rating

Amps

006/116610 1000 Aluminium 127/3.20 41.6 53.0 1500

006/116612 630 Copper 127/2.52 32.8 44.2 1500

006/132840 500 Aluminium 61/3.20 28.8 40.2 800

Positive Track Cables

Rail Catalogue

Number Nominal

Cross Sectional

Area mm²

Conductor

Material No. and Nominal Diameter of

Strands

# / mm

Nominal Diameter of

Conductor mm

Nominal Overall Diameter mm

Assigned Continuous

Current Rating

Amps

006/132991 800 Aluminium 127/2.85 37.1 48.5 1200

006/132990 240 Aluminium 61/2.25 20.3 28.3 550

006/132340 161 Copper 91/1.53 16.8 24.8 550

006/116601 150 Aluminium 37/2.25 15.8 19.4 430

Negative Track Cables

6491B Cable

Application

Standards Conductor

Insulation Insulation Colour Voltage Rating

Suitable for use in conduit and for fixed, protected installation. For installation where fire, smoke emission and toxic fumes create a potential threat to life and equipment.

BS7211

Class 2 stranded plain copper conductors to BS EN 60228:2005 (previously BS6360)

LSZH (Low Smoke Zero Halogen)

Black, Blue, Green/Yellow, Red, Yellow, White, Violet, Brown, Grey, Orange, Pink

450/750V

Temperature Rating Minimum Bending Radius

0°C to +90°C

Up to 10mm²: 3 x overall diameter 10mm² to 25mm²: 4 x overall diameter Above 25mm²: 5 x overall diameter

Dimensions

No. of Cores x Nominal Cross Sectional Area

# x mm²

Nominal Thickness of Insulation

mm

Nominal Overall Diameter

mm Nominal Weight

kg/Km

1 x 1.5 0.7 3.4 22

1 x 2.5 0.8 4.2 35

1 x 4.0 0.8 4.8 50

1 x 6.0 0.8 5.4 72

1 x 10.0 1.0 6.8 121

1 x 16.0 1.0 8.0 182

1 x 25.0 1.2 9.8 285

1 x 35.0 1.2 11.0 390

1 x 95.0 1.6 17.0 980

1 x 120.0 1.6 19.0 1220

1 x 150.0 1.8 21.0 1500

1 x 185.0 2.2 23.5 1910

1 x 240.0 2.2 26.5 2490

1 x 300.0 2.4 29.5 3100

1 x 400.0 2.6 33.5 3950

1 x 500.0 2.8 37.0 5000

1 x 630.0 2.8 41.0 6350

Conductors

Class 2 stranded conductors for single core and multi-core cables

1 2 3 4 5 6 7 8

Nominal Cross Sectional

Areamm²

Minimum Number of Wires in the Conductor Maximum Resistance of Conductor at 20ºC Circular Circular

Compacted Shaped Annealed Copper Conductor

Cu Al Cu Al Cu Al Plain Wires

ohms/Km

1.50 7 - 6 - - - 12.1000

2.50 7 - 6 - - - 7.4100

4.00 7 - 6 - - - 4.6100

6.00 7 - 6 - - - 3.0800

10.00 7 7 6 6 - - 1.8300

16.00 7 7 6 6 - - 1.1500

25.00 7 7 6 6 6 6 0.7270

35.00 7 7 6 6 6 6 0.5240

95.00 19 19 15 15 15 15 0.1930

120.00 37 37 18 15 18 15 0.1530

150.00 37 37 18 15 18 15 0.1240

185.00 37 37 30 30 30 30 0.0991

240.00 37 37 34 30 34 30 0.0754

300.00 61 61 34 30 34 30 0.0601

400.00 61 61 53 53 53 53 0.0470

500.00 61 61 53 53 53 53 0.0366

600.00 91 91 53 53 53 53 0.0283

Table in accordance with BS EN 60228:2005 (previously BS6360).

6491B Cable

Nominal Cross Sectional

Areamm²

Reference Method 4 (enclosed in conduit in thermally insulating

wall etc)

Reference Method 3 (enclosed in conduit

on a wall or in trunking etc.)

Reference Method 1

(clipped direct) Reference Method 11 (on a perforated cable

tray horizontal or vertical)

Reference Method 12 (free air) Horizontal

Flat Spaced

Vertical Flat Spaced

Trefoil

2 Cables Single Phase AC or AmpsDC

3 or 4 Cables

Three Phase AmpsAC

2 Cables Single Phase AC or AmpsDC

3 or 4 Cables

Three Phase AmpsAC

2 Cables Single Phase Cables Three Phase AC

Flat and Touching or Trefoil

Amps

2 Cables Single Phase Cables Three Phase AC

Flat and Touching or Trefoil Amps

2 Cables Single Phase AC

or DC or 3 Cables Three Phase AmpsAC

2 Cables Single Phase AC

or DC or 3 Cables Three Phase AC

Amps

3 Cables Three Phase AmpsAC

1 2 3 4 5 6 7 8 9 10 11 12

-25.0 100 91 126 111 143 130.0 158 140 183 163 138

35.0 124 111 156 138 176 161.0 195 176 226 203 171

50.0 149 135 189 168 228 209.0 293 215 274 246 209

70.0 189 170 240 214 293 268.0 308 279 351 318 270

95.0 228 205 290 259 355 326.0 375 341 426 389 330

120.0 263 235 336 299 413 379.0 436 398 495 453 385

150.0 300 270 375 328 476 436.0 505 461 570 524 445

185.0 341 306 426 370 545 500.0 579 530 651 600 511

240.0 400 358 500 433 644 590.0 686 630 769 711 606

300.0 459 410 573 493 743 681.0 794 730 886 824 701

400.0 - - 683 584 868 793.0 915 849 1065 994 820

500.0 - - 783 666 990 904.0 1044 973 1228 1150 936

630.0 - - 900 764 1130 1033.0 1191 1115 1423 1338 1069

800.0 - - - - 1288 1179.0 1358 1275 1581 1485 1214

1000.0 - - - - 1443 1323.0 1520 1436 1775 1671 1349

Electrical Characteristics

Current Carrying Capacity (amperes)

Ambient temperature: 30°C

Conductor operating temperature: 90°C

Voltage Drop (per ampere per metre)

Nominal Cross - Sectional Area mm²

2 Cables, Single Phase AC 2 Cables

mV/A/mDC

Reference Methods 3 & 4 (enclosed in conduit etc,

in or on a wall) mV/A/m

Reference Methods 1 & 11 (clipped direct or on trays, touching)

mV/A/m

Reference Method 12 (spaced*) mV/A/m

25.0 1.850 1.850 0.31 1.90 1.850 0.190 1.850 1.850 0.28 1.85

35.0 1.350 1.350 0.29 1.35 1.350 0.180 1.350 1.350 0.27 1.35

50.0 0.990 1.000 0.29 1.05 0.990 0.180 1.000 0.990 0.27 1.00

70.0 0.680 0.700 0.28 0.75 0.680 0.175 0.710 0.680 0.26 0.73

95.0 0.490 0.510 0.27 0.58 0.490 0.170 0.520 0.490 0.26 0.56

120.0 0.390 0.410 0.26 0.48 0.390 0.165 0.430 0.390 0.25 0.47

150.0 0.320 0.330 0.26 0.43 0.320 0.165 0.360 0.320 0.25 0.41

185.0 0.250 0.270 0.26 0.37 0.260 0.165 0.300 0.250 0.25 0.36

240.0 0.190 0.210 0.26 0.33 0.200 0.160 0.250 0.195 0.25 0.31

300.0 0.155 0.175 0.25 0.31 0.160 0.160 0.220 0.155 0.25 0.29

400.0 0.120 0.140 0.25 0.29 0.130 0.155 0.200 0.125 0.24 0.27

500.0 0.093 0.120 0.25 0.28 0.105 0.155 0.185 0.098 0.24 0.26

630.0 0.072 0.100 0.25 0.27 0.086 0.155 0.175 0.078 0.24 0.25

800.0 0.056 - 0.072 0.150 0.170 0.640 0.24 0.25

1000.0 0.045 - 0.063 0.150 0.165 0.054 0.24 0.24

6491B Cable

Conductor operating temperature: 90°C r = Resistive Component

x = Reactive Component z = Impedance Value Notes

1. Where the conductor is to be protected by a semi-enclosed fuse to BS3036, see item 6.2 of the preface to appendix 4 within 16th edition regs.

2. The current-carrying capacities in columns 2 to 5 are also applicable to flexible cables BS7211 table 3(b) where the cables are used in fixed installations.

Voltage Drop (per ampere per metre)

3 or 4 Cables, Three Phase AC Reference Methods 3 & 4

(enclosed in conduit etc, in or on a wall)

mV/A/m

Reference Methods 1, 11 & 12 (in trefoil) mV/A/m

Reference Method (flat and touching)

mV/A/m

Reference Methods 12 (flat spaced*)

mV/A/m

6 7 8 9

40.0 40.0 40.0 40.0

27.0 27.0 27.0 27.0

16.0 16.0 16.0 16.0

10.0 10.0 10.0 10.0

6.8 6.8 6.8 6.8

4.0 4.0 4.0 4.0

2.5 2.5 2.5 2.5

r x z r x z r x z r x z

1.600 0.27 1.650 1.600 0.165 1.60 1.600 0.190 1.600 1.600 0.27 1.65

1.150 0.25 1.150 1.150 0.155 1.15 1.150 0.180 1.150 1.150 0.26 1.20

0.870 0.25 0.900 0.860 0.155 0.87 0.860 0.180 0.870 0.860 0.26 0.89

0.600 0.24 0.650 0.590 0.150 0.61 0.590 0.175 0.620 0.590 0.25 0.65

0.440 0.23 0.500 0.430 0.145 0.45 0.430 0.170 0.460 0.430 0.25 0.49

0.350 0.23 0.420 0.340 0.140 0.37 0.340 0.165 0.380 0.340 0.24 0.42

0.290 0.23 0.370 0.280 0.140 0.31 0.280 0.165 0.320 0.280 0.24 0.37

0.230 0.23 0.320 0.220 0.140 0.26 0.220 0.165 0.280 0.220 0.24 0.33

0.190 0.22 0.290 0.170 0.140 0.22 0.170 0.165 0.240 0.170 0.24 0.29

0.150 0.22 0.270 0.140 0.140 0.20 0.135 0.160 0.210 0.135 0.24 0.27

0.130 0.22 0.250 0.110 0.135 0.18 0.110 0.160 0.195 0.110 0.24 0.26

0.100 0.22 0.240 0.090 0.135 0.16 0.088 0.160 0.180 0.085 0.24 0.25

0.090 0.21 0.230 0.074 0.135 0.15 0.171 0.160 0.170 0.068 0.23 0.24

- 0.062 0.130 0.15 0.059 0.155 0.165 0.055 0.23 0.24

- 0.055 0.130 0.14 0.050 0.155 0.165 0.047 0.23 0.24

3. For cable in rigid PVC conduit the values stated in table 4D1 are applicable (see Regulation 512-02).

4. Where a conductor operates at a temperature exceeding 70°C, it shall be ascertained that the equipment connected to the conductor is suitable for the conductor operating temperature (see Regulation 512-02).

5. Where cables in this table are connected to equipment or accessories designed to operate at a temperature not exceeding 70°C, the current ratings given in the equivalent table for 70°C PVC insulated cables BS6004, BS6346 shall be used (see Reg 523-01-01).

* Spacings larger than those specified in Method 12 (see table 4A 16th edition regs) will result in larger volt drop.

6491X Cable

Application

Standards Conductor

Insulation Insulation Colour Voltage Rating

For use in conduit and fixed, protected installation in switchgear, lighting and appliances.

BS6004

H07V-R: Class 2 stranded plain copper conductors to BS EN 60228:2005 (previously BS6360)

H07V-U: Class 1 solid plain copper conductor to BS EN 60228:2005 (previously BS6360)

PVC (Polyvinyl Chloride) Type TI1 to BS7655

Red, Black, Blue, Yellow, Brown, White, Green/Yellow, Grey

450/750V

Temperature Rating Minimum Bending Radius

0°C to +70°C

Up to 10mm²: 3 x overall diameter 10mm² to 25mm²: 4 x overall diameter Above 25mm²: 5 x overall diameter

Dimensions

No. of Cores x Nominal Cross Sectional Area

# x mm²

Nominal Thickness of Insulation

mm

Maximum Overall Diameter

mm

Nominal Weight kg/Km

1 x 1.5 0.7 3.3 22

1 x 2.5 0.8 3.9 32

1 x 4.0 0.8 4.6 50

1 x 6.0 0.8 5.2 71

1 x 10.0 1.0 6.7 120

1 x 16.0 1.0 7.8 180

1 x 25.0 1.2 9.7 280

1 x 35.0 1.2 10.9 380

1 x 50.0 1.4 12.8 510

1 x 70.0 1.4 14.6 710

1 x 95.0 1.6 17.1 970

1 x 120.0 1.6 18.8 1200

1 x 150.0 1.8 20.9 1480

1 x 185.0 2.0 23.3 1900

1 x 240.0 2.2 26.6 2480

1 x 300.0 2.4 29.6 3100

Conductors

Class 2 stranded conductors for single core and multi-core cables

1 2 3 4 5 6 7 8

Nominal Cross Sectional

Areamm²

Minimum Number of Wires in the Conductor Maximum Resistance of Conductor at 20ºC Circular Circular

Compacted Shaped Annealed Copper Conductor

Cu Al Cu Al Cu Al Plain Wires

ohms/Km

1.00 7 - - - - - 18.1000

1.50 7 - 6 - - - 12.1000

2.50 7 - 6 - - - 7.4100

4.00 7 - 6 - - - 4.6100

6.00 7 - 6 - - - 3.0800

10.00 7 7 6 6 - - 1.8300

16.00 7 7 6 6 - - 1.1500

25.00 7 7 6 6 6 6 0.7270

35.00 7 7 6 6 6 6 0.5240

50.00 19 19 6 6 6 6 0.3870

70.00 19 19 12 12 12 12 0.2680

95.00 19 19 15 15 15 15 0.1930

120.00 37 37 18 15 18 15 0.1530

150.00 37 37 18 15 18 15 0.1240

185.00 37 37 30 30 30 30 0.0991

240.00 37 37 34 30 34 30 0.0754

300.00 61 61 34 30 34 30 0.0601

630.00 91 91 53 53 53 53 0.0283

Table in accordance with BS EN 60228:2005 (previously BS6360).

6491X Cable

Conductor Cross Sectional

Areamm²

Reference Method A (enclosed in conduit in thermally insulating

wall etc.) Amps

Reference Method B (enclosed in conduit on a wall or in a

trunking etc.) Amps

Reference Method C (clipped direct)

Amps

Reference Method F (in free air or on a perforated cable tray etc.

horizontal or vertical) Amps

Touching Spaced by one

Diameter 2 Cables

Single Phase AC or DC

3 or 4 Cables

Three Phase AC

2 Cables Single Phase AC or DC

3 or 4 Cables

Three Phase AC

2 Cables Single Phase AC or DC

Flat or Touching

3 or 4 Cables Three Phase AC Flat &

Touching or Trefoil

2 Cables Single Phase

2 Cables Single Phase AC or DC or 3 Cables Three Phase AC Flat Horizontal Vertical

1 2 3 4 5 6 7 8 9 10 11 12

-25.0 80.0 73.0 101.0 89.0 114.0 104.0 131 114 110 146 130

35.0 99.0 89.0 125.0 110.0 141.0 129.0 162 143 137 181 162

50.0 119.0 108.0 151.0 134.0 182.0 167.0 196 174 167 219 197

70.0 151.0 136.0 192.0 171.0 234.0 214.0 251 225 216 281 254

95.0 182.0 164.0 232.0 207.0 284.0 261.0 304 275 264 341 311

120.0 210.0 188.0 269.0 239.0 330.0 303.0 352 321 308 396 362

150.0 240.0 216.0 300.0 262.0 381.0 349.0 406 372 356 456 419

185.0 273.0 245.0 341.0 296.0 436.0 400.0 463 427 409 521 480

240.0 321.0 286.0 400.0 346.0 515.0 472.0 546 507 485 615 569

300.0 367.0 328.0 458.0 394.0 594.0 545.0 629 587 561 709 659

400.0 - - 546.0 467.0 694.0 634.0 754 589 656 852 795

500.0 - - 626.0 533.0 792.0 723.0 868 789 749 982 920

630.0 - - 720.0 611.0 904.0 826.0 1005 905 855 1138 1070

Current Carrying Capacity (amperes)

Ambient temperature: 30°C

Conductor operating temperature: 70°C

The above table is in accordance with Table 4D1A of the 17th Edition of IEE Wiring Regulations.

Electrical Characteristics

Voltage Drop (per ampere per metre)

Conductor Cross Sectional

Area mm²

2 Cables mV/A/mDC

2 Cables, Single Phase AC mV/A/m Reference Methods

A & B (enclosed in conduit or

trunking)

Reference Methods C, F, & G (clipped direct, on tray or in free air)

Cable Touching Cable Spaced*

1 2 3 4 5

1.0 44.000 44.0 44.0 44.0

1.5 29.000 29.0 29.0 29.0

2.5 18.000 18.0 18.0 18.0

4.0 11.000 11.0 11.0 11.0

6.0 7.300 7.3 7.3 7.3

10.0 4.400 4.4 4.4 4.4

16.0 2.800 2.8 2.8 2.8

r x z r x z r x z

25.0 1.750 1.800 0.33 1.80 1.750 0.200 1.750 1.750 0.29 1.80

35.0 1.250 1.300 0.31 1.30 1.250 0.195 1.250 1.250 0.28 1.30

50.0 0.930 0.950 0.30 1.00 0.930 0.190 0.950 0.930 0.28 0.97

70.0 0.630 0.650 0.29 0.72 0.630 0.185 0.660 0.630 0.27 0.69

95.0 0.460 0.490 0.28 0.56 0.470 0.180 0.500 0.470 0.27 0.54

120.0 0.360 0.390 0.27 0.47 0.370 0.175 0.410 0.370 0.26 0.45

150.0 0.290 0.310 0.27 0.41 0.300 0.175 0.340 0.290 0.26 0.39

185.0 0.230 0.250 0.27 0.37 0.240 0.170 0.290 0.240 0.26 0.35

240.0 0.180 0.195 0.26 0.33 0.185 0.165 0.250 0.185 0.25 0.31

300.0 0.145 0.160 0.26 0.31 0.150 0.165 0.220 0.150 0.25 0.29

400.0 0.105 0.130 0.26 0.29 0.120 0.160 0.200 0.115 0.25 0.27

500.0 0.086 0.110 0.26 0.28 0.098 0.155 0.185 0.093 0.24 0.26

630.0 0.068 0.094 0.25 0.27 0.081 0.155 0.175 0.076 0.24 0.25

6491X Cable

Voltage Drop (per ampere per metre)

r = Resistive Component x = Reactive Component z = Impedance Value

Conductor operating temperature: 70°C

* Spacings larger than one cable diameter will result in a larger voltage drop.

The above table is in accordance with Table 4D1B of the 17th Edition of IEE Wiring Regulations.

For cables having conductors of 16mm² or less cross-sectional area, their inductances can be ignored and (mV/A/m)r values only are tabulated. For cables having conductors greater than 16mm² cross-sectional area, the impedance values are given as (mV/A/m)z, together with the resistive component (mV/A/m)r and the reactive component (mV/A/m)x.

The above paragraph is extracted from Appendix 4 of the 16th Edition of IEE Wiring Regulations. 3 or 4 Cables, Three Phase AC

mV/A/m Reference Methods

A & B (enclosed in conduit or

trunking)

Reference Methods C, F, & G (clipped direct, on tray or in free air) Cable Touching

Trefoil Cable Touching

Flat Cable Spaced*

Flat

6 7 8 9

38.0 38.0 38.0 38.0

25.0 25.0 25.0 25.0

15.0 15.0 15.0 15.0

9.5 9.5 9.5 9.5

6.4 6.4 6.4 6.4

3.8 3.8 3.8 3.8

2.4 2.4 2.4 2.4

r x z r x z r x z r x z

1.500 0.29 1.55 1.500 0.175 1.500 0.150 0.25 1.55 1.500 0.32 1.55

1.100 0.27 1.10 1.100 0.170 1.100 1.100 0.24 1.10 1.100 0.32 1.15

0.810 0.26 0.85 0.800 0.165 0.820 0.800 0.24 0.84 0.800 0.32 0.86

0.560 0.25 0.61 0.550 0.160 0.570 0.550 0.24 0.60 0.550 0.31 0.63

0.420 0.24 0.48 0.410 0.155 0.430 0.410 0.23 0.47 0.400 0.31 0.51

0.330 0.23 0.41 0.320 0.150 0.360 0.320 0.23 0.40 0.320 0.30 0.44

0.270 0.23 0.36 0.260 0.150 0.300 0.260 0.23 0.34 0.260 0.30 0.40

0.220 0.23 0.32 0.210 0.145 0.260 0.210 0.22 0.31 0.210 0.30 0.36

0.170 0.23 0.29 0.160 0.145 0.220 0.160 0.22 0.27 0.160 0.29 0.34

0.140 0.23 0.27 0.130 0.140 0.190 0.130 0.22 0.25 0.130 0.29 0.32

0.120 0.22 0.25 0.105 0.140 0.175 0.105 0.21 0.24 0.100 0.29 0.31

0.100 0.22 0.25 0.086 0.135 0.160 0.086 0.21 0.23 0.081 0.29 0.30

0.080 0.22 0.24 0.072 0.135 0.150 0.072 0.21 0.22 0.066 0.28 0.29