• No results found

UPS Test screen

In document Ups (Page 193-200)

UPS test software

6 of 12 JUD411293 First Issue 24/01/09

2.3.1 MEASURES

On the area “Measures” all the analog measurements inherent to the UPS are shown, in the following order:

BYP_V_R Æ Emergency bypass voltage Ph. R (V) BYP_V_S Æ Emergency bypass voltage Ph. S (V) BYP_V_T Æ Emergency bypass voltage Ph. T (V) OUT_V_R Æ UPS output voltage Ph. R (V)

OUT_V_S Æ UPS output voltage Ph. S (V) OUT_V_T Æ UPS output voltage Ph. T (V) INV_V_R Æ Inverter voltage Ph. R (V) INV_V_S Æ Inverter voltage Ph. S (V) INV_V_T Æ Inverter voltage Ph. T (V) ACDC_V Æ Battery voltage (V) DC_CUR Æ Inverter Input current (A)

IB_BOO Æ Battery Recharging Current ( A ) F_BYP Æ Emergency bypass frequency (Hz) F_INV Æ Inverter frequency (Hz).

In the area below, the field “NUMBER” represents the serial n° of the equipment and the field “VER. SW.” represents the revision of the UPS control software installed.

On the area “TX Check” the transmission control indicator is represented. If the connection is correct the figures increases cyclically up to 250 automatically.

2.3.2 UPS DATA

The area titled “UPS data” represents the relevant characteristics and settings. The first 7 lines contain the nominal values for:

POT_NOM Æ UPS nominal power (kVA).

VOLT_NOM Æ UPS nominal output voltage (V).

CURR_NOM Æ UPS nominal output current (A).

VDC_NOM Æ Battery nominal voltage (V).

IDC_NOM Æ Inverter nominal input current at full load (A).

BAT_TYP Æ Battery capacity (Ah).

AUT_NOM Æ Nominal autonomy (min).

The following 4 groups represent the limit values (for the voltage to be declared available) and the histeresys for:

BYP Æ Emergency bypass (V) #1 INV Æ Inverter Output (V) #2 OUT Æ UPS Output (V) #3 VDC Æ Inverter input (V) #4

The following 3 groups represent the limit values (for the frequency to be declared in tolerance) and the histeresys for emergency bypass as follows:

First Issue 24/01/09 JUD411293 7 of 12 FREQ Æ Emergency bypass nominal frequency (Hz)

FREQ MIN Æ Emergency bypass lower frequency (Hz)

FREQ MAX Æ Emergency bypass higher frequency (Hz) #5 The last 2 lines contain the following information:

AUT. MIN Æ Residual Battery autonomy (min)

AUT. % Æ Residual Battery autonomy (as % of the nominal).

2.3.3 VARIABLES

The area titled “Variables” represents the relevant internal status variables of the UPS. The meaning of each variable is described below:

INV_ON Æ When active the command inverter on is active too SSW_ON Æ When active the command inverter SSW on is active too IOK Æ If active the inverter is ready to supply the load

ROK_X Æ If active the bypass is in tolerance (ROK = RMSOK+FROK) O_LOAD Æ If active an overload has stopped the inverter

HITE Æ If active an over temperature (thermal protection) is active too

FROK Æ If active the emerg. byp. frequency is in tolerance (see limit group #5) RMS_OK Æ If active the emerg. byp. voltage is in tolerance (see limit group #1) COK Æ If active the UPS output voltage is in tolerance (see limit group #3) VUOK Æ If active the Inverter output voltage is in tolerance (see limit group #2) SYNCOK Æ If active the inverter is synchronized with the emergency bypass I_OVER Æ If active an overload (output current > nominal) is active too IMTERM Æ If active the thermal image counter (time vs current) is active too VDC_OK Æ If active the Inverter input voltage is in tolerance (see limit group #4)

2.3.4 OUTPUTS

The area titled “Outpus” represents the relevant digital outpus of the UPS. The meaning of each variable is described below:

COK Æ If active the UPS output voltage is in tolerance (see limit group #3) BY_BL Æ When active the load is blocked on the emergency bypass IFL Æ When active the inverter SSW is closed

CONAC Æ When active the PWM of the inverter IGBT bridge is on RESET_RITR_BL Æ When active the BY_BL condition is reset

R3_INV_FEED Æ When active relay Inv. Feeds Load is active too (ARC card) R4_BYP_FEED Æ When active relay Bypass Feed Load is active too (ARC card) R5_LOW_BATT Æ When active relay Low Battery is active too (ARC card)

R6_MAINS_FAU Æ When active relay Mains Fault is active too (ARC card)

2.3.5 INPUTS

The area titled “Inputs” represents the relevant digital inputs of the UPS. The meaning of each variable is below described:

MBY_CLOSE Æ When active the MBCB (manual bypass) is closed

EPO_BUS Æ When active the EPO (emergency power off) is not active BO_BUS Æ When active the BCB (battery breaker) is open

BYP_SW (FUSE) Æ When active the Bypass Switch (commutation test) is active TERMO_SW Æ When active the Thermal switch (bridge protection) is active OCB Æ When active the OCB (output breaker) is closed

MCS Æ When active the IGBT’s desaturation protection is active

UPS test software

8 of 12 JUD411293 First Issue 24/01/09 MRR Æ When active Mains fault signal (from the rectifier) is not active

RECT_FAIL Æ When active Rectifier fault sign. (from the rectifier) is not active ERR_SC Æ When active Input wrong seq. sign. (from the rectifier) is not active BF_RECT Æ When active Blown fuse sign. (from the rectifier) is active

PUL_UP Æ When active the up arrow key on the front panel is pressed PUL_DOWN Æ When active the down arrow key on the front panel is pressed PUL_ENTER Æ When active the enter key on the front panel is pressed

PUL_ BUZZ Æ When active the buzzer key on the front panel is pressed PUL_RESET Æ When active the reset key on the front panel is pressed

2.3.6 ALARMS AND STATUS

On the areas named “Alarms” and “Status”, the 25 alarms and 6 operating status are represented. For a detailed explanation of them, see the Operating Manual.

2.3.7 ACTIVE KEYS

The push button “Dip Sw” visualizes the mapping of the dip switches for configuration on the μP board (see foregoing paragraphs).

By clicking on the relevant country on the flags area the language on the display of the UPS can be changed.

2.3.8 GAUGES

The two gauges located under the third column represents the following values:

EN. CAR Æ Stored energy in the battery as % of the total

ACCUMU Æ Thermal image progress as % of the total (100 % Æ inverter stopped)

2.3.9 CONTROLS

The area above the flags contains the following control parameters:

FEFO Æ Must be 180

KF_BY Æ Must be between 800 and 900 KF_OU Æ Must be between 800 and 900

2.3.10 PARALLEL

If the UPS is working in parallel mode the relevant area “MASTER” under the second column and the active key “Par. Data” are active. For the description of the relevant functions refers to the Parallel Redundant Operating Manual.

BOOST OPERATION

If the Boost function is active, the push button “BOOST“ visualizes the parameter of the Boost Operation

IB_TR Æ Battery current limit for Floating to Boost Charge ( A ) IB_RT Æ Battery current limit for Boost to Float Charge ( A )

First Issue 24/01/09 JUD411293 9 of 12

2.4 SERIAL MESSAGES FOR PERSONALISATION AND SETTING

WARNING

Before sending any message insure that the computer writes with capital letters (CAPS). All commands consist in 4 letters and 3 numbers LLLLXXX.

After having sent a message, wait for an acoustic confirmation signal (BEEP) before sending new strings. If the signal does not arrive it means that the operation has had a negative result, so the last message must be repeated.

VERY IMPORTANT

The usage of these messages is recommended to specialized personnel only.

Don’t forget to send the command MEEE000 to store the variations on the UPS memory.

UPS test software

10 of 12 JUD411293 First Issue 24/01/09

2.4.1 BYPASS

TBFRXXX (XXX=100/250) phase R voltage (for UPS 1Ph and 3Ph) TBFSXXX (XXX=100/250) phase S voltage (only for UPS 3Ph) TBFTXXX (XXX=100/250) phase T voltage (only for UPS 3Ph)

2.4.2 OUTPUT

TUFRXXX (XXX=100/250) phase R voltage (for UPS 1Ph and 3Ph) TUFSXXX (XXX=100/250) phase S voltage (only for UPS 3Ph) TUFTXXX (XXX=100/250) phase T voltage (only for UPS 3Ph) ZCFR000 phase R zero current (for UPS 1Ph and 3Ph) ZCFS000 phase S zero current (only for UPS 3Ph) ZCFT000 phase T zero current (only for UPS 3Ph) TCFRXXX (XXX=005/999) phase R current (for UPS 1Ph and 3Ph) TCFSXXX (XXX=005/999) phase S current (only for UPS 3Ph) TCFTXXX (XXX=005/999) phase T current (only for UPS 3Ph)

2.4.3 INVERTER

ZIFR000 phase R zero voltage (for UPS 1Ph and 3Ph) ZIFS000 phase S zero voltage (only for UPS 3Ph) ZIFT000 phase T zero voltage (only for UPS 3Ph) TIFRXXX (XXX=100/250) phase R voltage (for UPS 1Ph and 3Ph) TIFSXXX (XXX=100/250) phase S voltage (only for UPS 3Ph) TIFTXXX (XXX=100/250) phase T voltage (only for UPS 3Ph)

2.4.4 BATTERY

TVBAXXX (XXX=100/600) Voltage TCBAXXX (XXX=010/999) Current

TYBAXXX Battery type (i.e.: batt. 24Ah = TYBA024) TAUTXXX (XXX=002/999) Nominal auton. (i.e.: aut. 20’ = TAUT020) LOBA XXX (XXX=100/600) Low battery level

BATT000 Forces to the 100% battery autonomy

ZCBA000 zero current

2.4.5 BATTERY TEST

TEBAXXX (XXX=000/002) battery test choice STDBXXX (XXX=000/999) battery test length setting

TBOF000 battery test stop

TBONXXX (XXX=000/999) battery test for XXX minutes

2.4.6 BOOST CHARGE

TCRBXXX (XXX=010/999) battery current for boost adjustment TBTRXXX (XXX=000/999) current limit for floating to boost TBRTYYY (XXX=000/999) current limit for boost to floating BOST000 boost charge ON

ZCRB000 zero battery current for boost charge

First Issue 24/01/09 JUD411293 11 of 12

2.4.7 GENERAL COMMANDS

TFFRXXX (XXX=010/060) frequency window: for values see (1) TVLX000 fast voltage monitor

MEEE000 Store the value in E2PROM

REHI000 reset HISTORY

BUZZ000 BUZZER quieting

RESE000 reset UPS

INON000 on inverter

INOF000 off inverter

PHASXXX (XXX=000/999) set the phase shifting between inverter and the bypass normal setting.

Single unit

PHAS270 set phase = 2700 Parallel unit

PHAS400 set phase = 4000

2.4.8 IDENTIFICATION

CNAMXXX (XXX=000/005) Set the name of the unit CLANXXX (XXX=000/005) UPS language

XXX = 000 (Italian) XXX = 001 (German) XXX = 002 (French) XXX = 003 (English) XXX = 004 (Portuguese) XXX = 005 (Spanish)

UPS test software

12 of 12 JUD411293 First Issue 24/01/09

2.4.9 TIMER SETTING

TMINXXX (XXX = 000/059) minutes setting THOUXXX (XXX = 000/023) hour setting TDAYXXX (XXX = 000/031) day setting TMONXXX (XXX = 000/012) month setting TYEAXXX (XXX = 000/099) year setting (*) Values not to be modified.

(1) TFFR +

060 +/- 6%

055 +/- 5,5%

050 +/- 5%

045 +/- 4,5%

040 +/- 4% standard setting 035 +/- 3,5%

030 +/- 3%

025 +/- 2,5%

020 +/- 2%

015 +/- 1,5%

010 +/- 1%

2.5 HYSTORY OF ALARMS

It is possible to download the alarm history on the computer by typing the following command:

READ XXX XXX = 000 last 100 events XXX = 001 previous 100 events XXX = 002 previous 100 events ...

XXX = 008 first 100 events

During the download the TX CHECK counter on the computer starts to count from 0 to 1800.

To read the history on the computer the F1 key can be pressed.

2.6 SHORTCUT KEYS

Key Description

F1 After the READ000 command allows to read the history on the computer.

F2 Sends RESE000 command.

F3 Sends all the zeroes to the UPS.

F4 Sends E2PROM data storing command : MEEE000.

F5 Sends the buzzer quieting command : BUZZ000.

F6 Sends the inverter ON command : INON000.

F7 Sends the inverter OFF command : INOF000.

F8 Adjusts the limits for the bypass and the output voltage : TVLX000.

F9 Adjusts the limits for the frequency at +/- 4% : TFFR040.

In document Ups (Page 193-200)

Related documents