• No results found

14. CONFIGURATION SETTINGS

14.2 POWER QUALITY MEASUREMENT FUNCTION

14.2.3 VOLTAGE & CURRENT ALARM

14.2.3 VOLTAGE & CURRENT ALARM

The Total Harmonic Distortion, or THD, of a sigmal is a measurement of the harmonic distortion present and is defined as the ratio of the sum of the powers of all harmonic components to the power of the fundamental frequency.

ISO 9001 certified Jin Kwang E & C Corp.

Speed 1200/2400/4800/9600/19200 1200

Slave Adderss 1~65534 1 1

Protocol DNP/IEC101/IEC104 DNP

Port RS232C/RS485 RS232C

DIAL UP DIAL UP

Item Range Def. Step Unit

Dial-up Mode DISABLE/ENABLE DISABLE

Phone Number 20 Digit 1

Subnet Mask - 255.255.255.

0

Gateway - 0.0.0.0

DNP Port 0~65535 20000 1

IEC Port 0~65535 2404 1

ISO 9001 certified Jin Kwang E & C Corp.

MODEM CONTROL MODEM CONTROL

Item Range Def. Step Unit

Line 2-WIRE/4-WIRE 4-WIRE

RTS Off Delay 10~500 50 10 ms

D/L Confirm NO/YES/SOMETIMES SOMETIMES

A/L Retries 0~2 1 1

A/L Timeout 1~255 40 1 sec

Initial Unsolicited MSG NO/YES NO

Unsolicited Class 1

Unsolicited Address 0~65534 65534 1

Multi Frame Interval 10~500 100 10 ms

Unsolicited Class 1 DISABLE/ENABLE DISABLE

Unsolicited Class 2 DISABLE/ENABLE DISABLE

Unsolicited Class 3 DISABLE/ENABLE DISABLE

ISO 9001 certified Jin Kwang E & C Corp.

14.3.3 IEC

14.3.3 IEC PARAMETERSPARAMETERS

EC Parameters Range Def. Step Unit

Cyclic Period 0~60 0 1 sec

Arm Timeout 1~255 15 1 sec

Single Point Class CLASS1/CLASS2 CLASS1

Double Point Class CLASS1/CLASS2 CLASS1

Measured Point Class CLASS1/CLASS2 CLASS2

IEC101 PARAMETERS IEC101 PARAMETERS

Link Address Size 0~2 2 1

Common Address Size 1~2 2 1

Object Address Size 1~3 2 1

COT Address Size 1~2 1 1

Time Marker NONE/CP24/CP56 CP56

Single NACK Control NO/YES YES

IEC104 PARAMETERS IEC104 PARAMETERS

t0 Off Line Poll Period 1~255 30 1 sec

t1 Ack Period 1~255 15 1 sec

t2 SFrame Period 1~255 10 1 sec

t3 Test Period 1~255 20 1 sec

ISO 9001 certified Jin Kwang E & C Corp.

15. STATUS MONITORING & CONTROL 15. STATUS MONITORING & CONTROL

15.1 SWITHCH CONTROL 15.1 SWITHCH CONTROL

Recloser can be controlled from remote or local operator place. Operator place can be changed only at local front panel. ‘REMOTE CONTROL’ push button is to select the operator place. Operator place is toggled between local and remote by pushing button. LED is lit if remote position is selected. FTU-R200 begins with remote position at power-up. Control is allowed only at the position selected.

Local switch control requires two-step operation. It’s for security of operation. ‘SELECT’ button should be pushed before ‘CLOSE’ or ‘OPEN’. SELECT LED is lit if SELECT operation is valid. SELECT can be canceled by pushing SELECT button again or automatically after SBO timeout without operation. CLOSE or OPEN operation is valid while this LED is lit. Pushing CLOSE or OPEN button outputs switch control signal with fixed time pulse which is configurable. Switch status change input which is auxiliary contacts of switch stops continuing to output pulse. There are some interlock conditions to inhibit FTU from outputting pulse signal.

Gas low, Switch handle lock, same status of switch auxiliary contacts ‘a’, ‘b’ are those. Close or open pulse width shall be set longer than switch operating time.

Remote switch control is possible by using SCADA protocol DNP3.0 or IEC60870-5-101, IEC60870-5-104 FTU-R200 supports SBO (Select Before Operate) or Direct operate. If the operator place is set to ‘Local’, remote control commands are refused. Pulse width of remote control command shorter than setting will be overridden by local configuration

15.2 SWITCH STATUS MONITORING 15.2 SWITCH STATUS MONITORING

FTU monitors switch open/close, gas and lock status through auxiliary contacts. FTU scans these contacts input every 5 milliseconds. Switch open/close status is determined by double binary input, normally open and closed contacts. Changes of all input status are saved as events with time tag in history buffer. For each contact input, on-delay time can be applied. It’s adjustable within 10~500ms by 5ms step.

15.3 BATTERY MONITORING 15.3 BATTERY MONITORING

FTU monitors external Lead-acid battery through the control unit, which are mounted on inner back-side of control box. Battery voltage is supervised continuously during external AC supply loss. If over-discharge condition occurred, the control unit sends alarm signal to RTU and disconnect battery in order

ISO 9001 certified Jin Kwang E & C Corp.

to protect battery cell damage after 1-minute delay. The delay enables RTU to send alarm state to remote station via communication. Also while AC supply is applied, battery test control activates this function with connecting dummy battery load during test pulse, which is configurable. The test control command can be ordered at local or remote.

16. MEASUREMENT 16. MEASUREMENT

16.1 BASIC ELECTRIC QUANTITIES 16.1 BASIC ELECTRIC QUANTITIES

FTU has 3-phase currents and 6 voltages input. DSP digitizes these signals and calculates various electric quantities. These are basically based on fundamental frequency components. DSP use FFT (Fast Fourier Transform) algorithm to get the components. Also DSP calculates true RMS of 3-phase currents and voltages which include system frequency components and 2nd~31th harmonics. Actually harmonic components over than 31th are attenuated by analog filters. Electric quantities calculated are listed in the following.

RMS, Phase Angle, True RMS

l

l Apparent Power A-Phase, B-Phase, C-Phase, 3-Phase Total, l

l Active Power A-Phase, B-Phase, C-Phase, 3-Phase Total, l

l Reactive Power A-Phase, B-Phase, C-Phase, 3-Phase Total, l

l Power Factor A-Phase, B-Phase, C-Phase, 3-Phase Total, l

l Va-Vr Phase Angle Difference

l

l Current, Voltage Unbalance

l

l Frequency, Temporature

In the above items listed, active power, reactive power values are signed integer. Sign represents power flow or if loads are inductive or capacitive. Also power factor has lead/lag state value separately.

Currents and voltages have phase angles, which are relative phase angles compared to the reference Va. These angles are useful to monitor the phase sequence and imbalance of distribution line.

16.2 SEQUENCE COMPONENTS 16.2 SEQUENCE COMPONENTS

FTU provides the sequence components of 3-phase currents and voltages. They are positive sequence current (I1) and voltage (V1), negative sequence current (I2) and voltage (V2), and zero sequence voltage

ISO 9001 certified Jin Kwang E & C Corp.

16.3 HARMONICS 16.3 HARMONICS

FTU extracts harmonic components from 3-phase current and voltage signals by using FFT (Fast Fourier Transform). It provides 2nd to 31st harmonic magnitudes and THDs (Total Harmonic Distortion) for each phase. THD is the total harmonic percentage to the fundamental frequency component. FTU also calculates and provides 3-phase THD. These values may be used to monitor the power quality of distribution line.

16.4 ENERGY 16.4 ENERGY

FTU provides active energy, reactive energy for each phase or 3-phase total. Also import, export energy are accumulated on separate register. Units of energy are kWh, kVarh, which represent primary distribution line energy flow. The values are represented by 16-bit rollovers kWh, kVarh counters which are available at remote or local. Power calculation for energy is based on the fundamental frequency component. It’s not for billing purpose, but for load management. Proper energy accumulation needs that SCADA read energy counter with reset from FTU and accumulate it on SCADA’s local register by periods shorter than the expected rollover time of the counter.

[Four-quadrant power flow directions ]

16.5 DEMAND CURRENTS AND POWER 16.5 DEMAND CURRENTS AND POWER

FTU calculates and stores average of currents and active, reactive powers during the demand interval, which is configurable as 5, 10, or 15 minutes. The buffer has 1023 demands. Also FTU stores daily peak demand up to 1023.

ISO 9001 certified Jin Kwang E & C Corp.

17. MAINTENANCE SOFTWARE 17. MAINTENANCE SOFTWARE 17.1 OVERVIEW

17.1 OVERVIEW

FTU-R200 has a dedicated setting and operation tool, FTUManFTUMan. This tool is operated on PC or Notebook, and through RS232C port on front panelRS232C port on front panel of FTU-R200. For this communication, MODBUS protocol is used.

It supports the follwing features.

ü

ü Setting & Configuration changes

ü

ü Event & Waveform load

ü

ü Measurement & Status display

ü

ü Waveform File upload and convert

ü

ü SCADA monitors protocol data frame between devices

[ Overview of FTUMans ]

ISO 9001 certified Jin Kwang E & C Corp.

New Closes the current file and allows the creation of a new file Open

Open Closes the current file and opens a standard window file selection dialog. An existing FTU File (*.f2s)FTU File (*.f2s) can be selected and opened.

Save

Save Saves the current file to the hard drive. If the file is new and this is the first time it has been saved, the Save As dialog will be opened allowing the user to type in a name before saving.

Save As

Save As Opens a standard Windows Save As dialog box. This allows an existing file to be saved under a new name.

Exit

Exit Closes the current file and exits the tool.

n

n CommComm

Comm.Config

Comm.Config Opens a window for communication configuration dialog.

Comm.Connection

Comm.Connection Starts communication with FTU-R200 Comm.Disconnection

Comm.Disconnection Stops connecting with FTU-R200

[ Comm. Configuration Window ]

Port

Port Select a serial Port of Laptop Baud

Baud RateRate Make to the transmission medium per second of in a digitally signal

Retry

Retry Set up the count if it failed to connect Timeout

Timeout Set up the time to connect

ISO 9001 certified Jin Kwang E & C Corp.

n

n CommandCommand

Clock Setting

Clock Setting Set RTC Time of FTU-R200

[ Clock Setting Window ]

Device Time

Device Time Gets the current time per 1 second from FTU-R200.

Setting Time

Setting Time The operator can set aside time.

Use System Time

Use System Time The operator can use PC’s time.

Write

Write Write RTC time to FTU-R200

Close

Close Close this window

Factory Initialization

Factory Initialization Reset to factory defaults.

Warning

Warning: Restoring FTU-R200 to factory defaults will eraseerase all previous setting, configuration and event

all previous setting, configuration and event.

ISO 9001 certified Jin Kwang E & C Corp.

Toolbar Show or hide the toolbar.

Status Bar

Status Bar Show or hide the status bar.

Monitoring Bar

Monitoring Bar Show or hide the monitoring bar. The monitoring bar shows communication status with FTU-R200.

n n HelpHelp

The Help MenuHelp Menu opens a window for FTUManFTUMan’s program version and information.

17.2.2 TOOLBAR 17.2.2 TOOLBAR

Below the menu is a toolbar with 9 buttons.

[ Toolbar of FTUMan ]

Upload

Upload Read input or ouput data from FTU-R200.

Download

Download Write input or ouput data to FTU-R200.

About

About Opens a window for FTUManFTUMan’s program version and information.

Protocol Monitoring

Protocol Monitoring Protocol monitoring command activation or deactivation.

IO Configuration

IO Configuration Run the IOConfigIOConfig program for I/O setting.

The IOConfigIOConfig is explained in the Section 10.Section 10.

DNP3.0 DNP3.0

Index Configuration Index Configuration

Run the DNPConfigDNPConfig program for DNP index configuration.

The DNPConfigDNPConfig is explained in the Section 11.Section 11.

Waveform Waveform Evaluation Tool Evaluation Tool

Run the EvalToolEvalTool program for analysis waveform data.

The EvalToolEvalTool is explained in the Section 12.Section 12.

ISO 9001 certified Jin Kwang E & C Corp.

PORT Serial Port Number and Speed

MODE

Wirtes the setting value on FTU-R200 When Factory Initialization occurs.

Error of connection or operation

Connect or Disconnect between PC and FTU-R200 When the time set is completed

17.2.5 FUNCTION AND CONFIGURATION SETTING 17.2.5 FUNCTION AND CONFIGURATION SETTING

In Function and Configuration window, existing setting values of FTU-R200 can be viewed through

‘Upload’ button, or setting values are edited and downloaded to FTU-R200 by clicking ‘Download’

button to apply new setting values to FTU-R200.

ISO 9001 certified Jin Kwang E & C Corp.

If you set up the ADGS (Auto Detection Group Setting) Function ‘ON’, you can check the current direction ‘Forward’ or ‘Reverse’.

[ Tree View for function and configuration ]

Function has 5 contents, 4 setting groups and active group setting. Each group has protection setting value for FTU-R200.

Configuration has 3 contents for I/O, PQM and communication. Communication seperated 3 contens, for Port, DNP3.0 and IEC protocol parameter to communication for SCADA.

In tree view, if you choose some content, icon will be replaced with a red icon from a blue icon. And show setting parameters related content.

How to edit the setting value? Click the content in tree view and editing value using double-click or Enter-Key. If you changed value, the text color is changed in red.

[ before the Change ]

[ after the Change ]

ISO 9001 certified Jin Kwang E & C Corp.

And, in event window has a following pop-up menu. In the Tree View, select ‘FUNCTIONFUNCTION’or

‘CONFIGURATIONCONFIGURATION’ or all sub contens, and press the right-click pop-up menu is avaliable.

[ Pop-up Menu for Event Window ]

If you click ‘Upload’ Button, the setting parameters related selected contents in the tree view reads from FTU-R200.

Also, if you click ‘Download’ Button, the setting parameters related selected contents in the tree view writes to FTU-R200.

[ Input Password Dialog ]

When the Factory Initialization or all of information are changed, Input Password Window will be appeared.

Note:

Note: Default Password is ‘ftumanftuman’.

17.2.6 EVENT 17.2.6 EVENT

In Event window, operators can list up all the event records, which are stored in the memory of FTU-R200 by clicking ‘Upload’ button. Also 8 kinds of events are stored. Each event type of event can be separately uploaded from FTU-R200 and can save to CSV format file. Time Resolution for event recording is 5 msec and scanning interval is 1 msec.

ISO 9001 certified Jin Kwang E & C Corp.

[ Pop-up Menu for Event Window ]

Upload

Upload Reads the selected events in the tree view.

Clear All Events

Clear All Events Delete all event stored.

Clear Fault Events

Clear Fault Events Delete only fault events.

Save to CSV File

Save to CSV File Current event saves to CSV (CComma-SSaperated VValues file) file format.

ü

ü CSV FileCSV File

A Comma-Seperated Values (CSV) file is used for the digital storage of data structed in a table of lists form, where each associated item (member) in a group is in association with others also seperated by the commas of its set.

Each line in the CSV file corresponds to a row in the table. Within a line, fields are seperated by commas, each field belonging to one table column. Since it is a common and simple file format, CSV files are often used for moving tabular data between two different computer programs, for example between a database program and a spreadsheet program.

ISO 9001 certified Jin Kwang E & C Corp.

n

n I/O EventI/O Event

[ I/O Event Window ]

Index

Index Event sequence number, the recent events that occurred is displayed on top.

Date & Time

Date & Time Event occurred time.

Description

Description Information of generated binary event.

Status

Status Occured contact points and binary status, OFF/ON/AUTO

ISO 9001 certified Jin Kwang E & C Corp.

n

n FUNCTION EVENTFUNCTION EVENT

[ Function Event Window ]

Index

Index Event sequence number, the recent events that occurred is displayed on top.

Date & Time

Date & Time Event occurred time.

Description

Description Operation of protection functions.

Status

Status Occurred function event status, OFF/ON.

ISO 9001 certified Jin Kwang E & C Corp.

n

n SYSTEM EVENTSYSTEM EVENT

[ System Event Window ]

Index

Index Event sequence number, the recent events that occurred is displayed on top.

Date & Time

Date & Time Event occurred time.

Description

Description Information of generated event like set value changed, triggered by power reset and system error or self-diagnosis.

Status

Status Occurred event position and detailed description of system error or self-diagnosis.

ISO 9001 certified Jin Kwang E & C Corp.

n

n FAULT EVENTFAULT EVENT

[ Fault Event Window ]

Index

Index Event sequence number, the recent events that occurred is displayed on top.

Date & Time

Date & Time Event occurred time.

OC

OC Detecting over-current.

SEF

SEF Detecting Sensitive Earth Fault.

UFR

UFR Detecting Under Frequency.

DIR

DIR Fault current direction.

Inrush

Inrush Detecting inrush restraint.

IIaa, I, Ibb, I, Icc, I, Inn, V, V00 Fault current and zero-sequency voltage Group

Group Current setting group

ISO 9001 certified Jin Kwang E & C Corp.

n

n PQM EVENTPQM EVENT

[ PQM Event Window ]

Index

Index Event sequence number, the recent events that occurred is displayed on top.

Date & Time

Date & Time Event occurred time.

Description

Description The occurance history of power quality function change.

Value

Value RMS value of voltage when moment voltage change occurs.

Unit: kV Duration

Duration Duration time of moment voltage change by msec.

Unit: msec

ISO 9001 certified Jin Kwang E & C Corp.

n

n DEMAND CURRENT EVENTDEMAND CURRENT EVENT

[ Demand Current Event Window ]

Index

Index Event sequence number, the recent events that occurred is displayed on top.

Date & Time

Date & Time Event occurred time.

IIaa, I, Ibb, I, Icc, I, Inn Demand current of each phase and neutral.

ISO 9001 certified Jin Kwang E & C Corp.

n

n DEMAND POWER EVENTDEMAND POWER EVENT

[ Demand Power Event Window ]

Index

Index Event sequence number, the recent events that occurred is displayed on top.

Date & Time

Date & Time Event occurred time.

kW

kWaa, kW, kWbb, kW, kWcc, kW, kW3ph3ph 3-phase total and each phase kW.

kVAR kVAR aa, kVAR , kVAR bb,, kVAR kVAR cc, kVAR , kVAR 3ph3ph

3-phase total and each phase kVAR.

ISO 9001 certified Jin Kwang E & C Corp.

n

n DAILY MAXIMUM CURRENT EVENTDAILY MAXIMUM CURRENT EVENT For more details, refer to Demand Current Event.Demand Current Event.

n

n DAILY MAXIMUM POWER EVENT

For more details, refer to Demand Power Event. Demand Power Event.

17.2.7 MEASUREMENT 17.2.7 MEASUREMENT

Operators can monitor all kinds of measurement values such as current, voltage, sequence value, power and energy, etc. And, FTU-R200 has the function of Harmonic Analysis, therefore up to 31st harmonics RMS value and THD for current and voltage are measured and displayed. Lastly, counter values and accumulation data are displayed.

FTUMan has 6 kinds of Mesurement window. The measurement value updates per 1 second.

n

n BASIC VALUEBASIC VALUE

Operators can check the basic value like load or source volatage, current including RMS, Phase Angle and True RMS also apparent, active and reactive power. And it shows unbalance frequency, temperature and so on.

[ Basic Mesurement Window ]

ISO 9001 certified Jin Kwang E & C Corp.

n

n SEQUENCE VALUESEQUENCE VALUE

It shows zero, positive and negative sequence of source or load voltage and current.

[ Sequence Value Window ]

ISO 9001 certified Jin Kwang E & C Corp.

n

n POWERPOWER

You can check active, reactive and apparent power of each phase or 3-phase. It also shows lag of each phase or lead.

[ Power Winodw ]

ISO 9001 certified Jin Kwang E & C Corp.

n

n ENERGYENERGY

FTU-R200 provies imported or exported energy according to conductive, inductive energy of each phase or 3-phase total.

[ Energy Window ]

ISO 9001 certified Jin Kwang E & C Corp.

n

n RMONICSRMONICS

It displays THD and each harmonics value of voltage and current. It shows from 2nd to 31st per 1 second.

[ Harmonics Window ]

ISO 9001 certified Jin Kwang E & C Corp.

n

n COUNTERCOUNTER

It basically shows restart, fault, PQM and THD counter and total interruption time.

[ Counter Window ]

Restart

Restart Show restarts time and its count.

Fault Counter

Fault Counter Show the total fault count of each, neutral phase and Switch Trip.

PQM Counter

PQM Counter Show the short-duration voltage variation event count.

Total Interruption Time

Total Interruption Time Show the total interruption time.

THD Counter

THD Counter Show the each or total phase’s current and voltage THD counts.

ISO 9001 certified Jin Kwang E & C Corp.

17.2.8 STATUS 17.2.8 STATUS

In status window, all the status indications and command are displayed.

[ Status Window ]

When operator supervises some command in status window, this window generated. Upper box shows device name, bottom box displays command name. If you click the ‘OK’ button, command will be operated and window will be disappeared.

[ Commnad Window ]

ISO 9001 certified Jin Kwang E & C Corp.

17.2.9 WAVEFORM 17.2.9 WAVEFORM

In waveform window displays Fault and PQM waveforms list stored in FTU-R200.

FTU-R200 can record and store the data for up to 8 faults, up to 6 PQM and 1 waveform by manual triggering. And each waveform has the data of 20 cycles at 128 samples.

How to upload waveforms are as follow. First, by using the ‘Upload’ command reads a list of stored waveforms on the FTU-R200.

How to upload waveforms are as follow. First, by using the ‘Upload’ command reads a list of stored waveforms on the FTU-R200.

Related documents