Founded in 1947, STULZ acquired Air Technology Sys-tems (ATS) in March 2001, naming the new company Stulz Air Technology Systems, Inc. (SATS). SATS is dedicated to providing innovative solutions for critical temperature and humidity control needs. SATS designs and manufactures specialized environmental control equipment for commercial, industrial and custom military applications. SATS serves a diverse marketplace -including telecommunications, information technology, medical, financial, educational, industrial process and government contracts - utilizing world-class "island" manufacturing processes in a modern, 150,000 ft2 facility.

The addition of SATS to the STULZ family of companies solidifies STULZ as a global leader in the Precision Air Conditioning marketplace. SATS combines a global network of sales and service companies with an extensive factory engineering staff and highly flexible manufacturing resources dedicated to providing world-class quality, innovation and customer service.

ISO-9001:2001 Quality Registered

Stulz-ATS is committed to satisfying customer expectations by meeting and exceeding customer requirements. Our Quality Policy ensures that every Employee is committed to Customer Satisfaction, Teamwork and utilizing continuous Process Improvement methods in order to deliver an exceptional product. We continually measure our performance to improve the effectiveness of our quality management system.

Precision A/C Applications

SATS is dedicated to the manufacturing of supplemental and precision air conditioning products. With an extensive installation base, SATS has earned a solid reputation as a quality supplier and leader in its field.

INDUSTRIES:

„ Telecommunications „ Internet / Web Hosting „ Financial / Banking „ Insurance

„ Legal Services

„ Airlines / Mass Transit „ Entertainment

„ Government

„ Colleges / Universities

APPLICATIONS:

„ Computer / LAN Rooms „ Telecommunications Rooms „ Colocation Centers

„ ISP (Internet Service Providers)

Stulz Air Technology Systems, Inc. (SATS)

Mini-Space™ vertical, floor mounted air conditioning units provide precision temperature and humidity control for computer rooms and other critical areas where continuous 24 hrs/day, 365 days/yr operation is required. Designed for front only access,

Mini-Space systems require minimal floor space. The units are designed with a wide range of options to handle both precision and comfort cooling applications. Typical applications include:

(3)

SECTION - 1

Introduction to SATS ...1-1 Table of Contents ... 1-2

SECTION - 2

Mini-Space SYSTEMS: Outstanding Advantages ... 2-1 User Oriented Features & Options ... 2-2 Available Configurations ... 2-3/4

MODEL NOMENCLATURE:

Nomenclature Chart ... 2-5 Model Nomenclature Specifications ... 2-6

SECTION - 3

GUIDE SPECIFICATIONS:

Standard Features Index ... 3-1 Standard Guide Specifications ... 3-2/6 Standard Equipment Warranty ... 3-7 Optional Features Index ... 3-8 Microprocessor Controls Specifications ... 3-9/10 Optional Features Guide Specifications ... 3-11/13

SECTION - 4

PERFORMANCE / CAPACITY SPECIFICATIONS:

Performance Data Index ... 4-1 DX - Air Cooled Systems ... 4-2/3 DX - Water Cooled Systems ... 4-4/5 DX - Glycol Cooled Systems ... 4-6/7 Chilled Water Systems ... 4-8/9

SECTION - 5

ELECTRICAL DATA: (FLA / MCA / MFS)

DX - Compressorized Systems:

Air Cooled Systems ... 5-1 Water Cooled Systems ... 5-1 Glycol Cooled Systems ... 5-1

Chilled Water Systems:

Chilled Water Systems ... 5-2

SECTION - 6

DIMENSIONAL / INSTALLATION DRAWINGS:

Dimensional Data Index ... 6-1

Standard Mini-Space Systems:

1 to 3.5 Ton, Up-Flow Systems ... 6-2 1 to 3.5 Ton, Down-Flow Systems ... 6-3 5 to 7 Ton, Up-Flow Systems ... 6-4 5 to 7 Ton, Down-Flow Systems ... 6-5

(4)

Mini-Space Systems

Mini-Space Systems Offer Outstanding Advantages

Flexibility

A wide variety of types are available to meet your unique requirements.

DX - Air Cooled (w/ Remote Condensers)

DX - Water Cooled (Packaged Units)

DX - Glycol Cooled (w/ Remote Drycoolers & Pump Packages)

Chilled Water Air Handling Units

Versatility

Plenum Box Spot Cooling & Ducted systems • Self-Contained & Split systems

100% Front Service Access

From 1 to 7 tons, Mini-Spacesystems are designed for 100% Front Only Access. The compact 23.6" x 23.6" (1 to 3.5 ton) and 39.4" x 31.9" (5 to 7 ton) foot-prints require minimal floor space and are easily tucked into a corner, between cabinetry or side-by-side.

Wide Size Range

1 to 7 tons capacity in six incremental sizes.

Non-Proprietary Parts

Mini-Space systems incorporate non-proprietary compo-nents where possible. Most major HVAC, refrigeration and electrical distributors stock an exact model cross reference or an alternate to most factory provided components.

Mini-Space floor mounted A/C's are de-signed to be the compact solution to your Precision Air Conditioning requirements. Systems are available in six incremental sizes from 1 to 7 tons in the following cabinet foot-prints:

1 to 3.5 tons = 23.6" W x 23.6" D 5 to 7 tons = 39.4" W x 31.9" D

Smartly designed for 100% front service access, Mini-Spaceunits can easily be tucked into a corner, between cabinetry or side-by-side. Mini-Space units are espe-cially adaptable to raised floors and are available in both up-flow and down-flow air pattern configurations. Up-Flow Air Patterns Down-Flow Air Patterns

Microprocessor Controls

Precision temperature and/or humidity control with unrivaled, user-friendly C-1002 series controls, offer a wide range of functions and alarms.

Complete Temperature & Humidity

Control

• Electrode Canister Steam Humidification • Dehumidification Mode with

- Electric Reheat/Heat

- Optional Hot Gas Reheat (Energy $aver) - Optional Hot Water Reheat/Heat

Capacity Modulation Options

• Hot Gas Bypass Systems

• Modulating Chilled Water Valves (Standard)

Code (UL / CSA) Conformance

- NYC MEA Approved (MEA-433-00-E) - CSA Compliance / Chicago Code Approved

BMS Connection Two-Unit Sequencing ... and more!

(5)

User Oriented Features & Options

Scroll Compressors

Mini-Space DX A/C's incorporate Scroll Compressor Technology. Scroll Compressors provide higher efficiency, higher reliability and lower sound power than other compressor technologies.

24/7 Year Round Operation

Option offerings available with Mini-Space A/C's allow for year-round, 24 hrs-a-day A/C operation in any environ-ment in the world:

Low Ambient Control (DX - Air Cooled)

• 0°F Pressure Fan Cycling • -20°F Variable Fan Speed • -30°F Flooded Head Pressure

Modular Motor

Controllers

Mini-Space systems incorporate modular motor controllers with motor circuit breakers in lieu of inconvenient replaceable fuses, eliminating the need for any motor fusing.

Quiet Operation

Low sound power Scroll compressors coupled with low RPM blowers, acoustically lined cabinets and low velocity grilles provide the optimum in quiet operation.

Warranty

- 2 Year Parts Standard - Optional 5 Year Compressor

Selected Standard Features:

Main Power Non-Fused Disconnect Switch

Modular Motor Controllers (w/ motor circuit breakers)

Acoustical / Thermal Insulation

Aluminum Finned / Copper Tube Coils

Thermal Expansion Valve

Refrigerant Sight Glass

Filter / Drier Strainer

Liquid Refrigerant Reclaim Valves

Non-Corroding Aluminum Drain Pan

High / Low Refrigerant Pressure Switches

Other Available Options:

2 & 3-way Grilled Plenum Boxes

Floor Stands

Condensate Pumps

Firestats

Smoke Detectors

Water Leak Detectors

Special High Efficiency, ASHRAE rated Filtration

High Pressure DX - Water/Glycol Cooled Condenser Regulating Valves

Many more options available (see page 3-8)!

Mini-Space

(Model CCU-110-CW Shown)

100% Front Access

(6)

Application Dependent Configuration Choices

CHILLED WATER SYSTEMS

AIR COOLED SYSTEMS

WATER / GLYCOL COOLED

CCU/D- ( 41/121)-(A)

WCS-( )

CCU/D- ( 171/201)-(A)

WCS-( ) SPLIT AIR COOLED -with REMOTE OUTDOOR Air Cooled Condenser

(compressor located with evaporator section)

WATER COOLED GLYCOL COOLED

CCU/D- ( 41/121)-(W)

CCU/D- ( 171/201)-(W)

CCU/D- ( 41/121)-(G)

CCU/D- ( 171/201)-(G) Remote Water Source

(supplied by others)

FSS-( )/GPS-( )

CCU/D- 110-CW CCU/D- 200-CW

Remote Liquid Chiller

(supplied by others)

Remote Liquid Chiller

(7)

Flexible Air Pattern Configuration Choices

Up-Flow Systems:

Bottom Discharge Into Raised Floor

Down-Flow Systems:

Bottom Discharge Into Raised Floor

Top "Free" Return with:

Top "Ducted" Return with:

1

2

Top Discharge Through 2 or

3-way Grilled Plenum Box with:

Top "Ducted" Discharge with:

3

4

Front "Free" Return

6

5

Rear "Ducted" Return Front "Free" Return

(8)

Nomenclature

-

Model Nomenclature Chart

Model Nomenclature

-

"CCU/D" Systems

Mini-Space - Vertical Floor Systems

Nominal Capacity in kW CC = Compact Line System WCS = Air Cooled Condenser GPS = Glycol Pump System

U = Up-Flow Air Pattern D = Down-Flow Air Pattern

Up-Flow

Air Patterns

Down-Flow

Air Patterns

A = Air Cooled

CW = Chilled Water System G = Glycol Cooled W = Water Cooled

LGA = Outdoor Glycol Drycooler

CC U-12 1-G

Number of Refrigeration Circuits

Up-Flow

Air Patterns

Down-Flow

Air Patterns

(9)

Model Nomenclature Specifications

"Mini-Space"

Model Nomenclature

Guide Specifications

DX - AIR COOLED SYSTEMS Air Cooled

(Models CCU/D-( )-A)

The system shall be a remote (split) air cooled, floor mounted precision air conditioner evaporator. The evapora-tor section shall house, as a mini-mum, the evaporator coil, expansion valve, compressor, evaporator blower/ motor and associated electrical and refrigeration components.

The CCU/D-( )-A evaporator section shall be located at some distance from its corresponding SATS model WCS-( ) outdoor air cooled con-denser.

The evaporator system shall require only single point main power supply connection; and the system shall ship from the SATS factory with a dry nitrogen holding charge ready for field refrigerant (R-22) charging.

Remote Outdoor Condenser

(Models WCS-( )-( )

The system shall be a remote outdoor air cooled condenser with direct-driven propeller fan(s). The condenser cabinet shall house the condenser coil, fan(s) and fan motor(s) and condenser motor control / enabling box. The

compressor(s) shall be located with the CCU/D-( )-A evaporator section. The condenser shall be sized to provide the total heat of rejection of the system at a 95°F DB ambient temperature for the corresponding Mini-Space model CCU/D-( )-A evaporator.

Note: The outdoor propeller condens-ers are model designated as follows:

Nomenclature

Mini-Space Systems

WCS-( )-P:

Low Ambient Head Pressure Control down to a minimum ambient temperature of 0°F via Fan Cycling Head Pressure Control.

WCS-( )-V:

Low Ambient Head Pressure Control down to a minimum ambient temperature of -20°F via Variable Fan Speed Head Pressure Control.

WCS-( )-F:

Low Ambient Head Pressure Control down to a minimum ambient tempera-ture of -30°F via Flooded Head Pres-sure Control.

DX - WATER COOLED SYSTEMS

Integral Self-Contained

(Models CCU/D-( )-W)

The system shall be a self-contained, floor mounted precision air condi-tioner to include integral water cooled condenser with factory installed head pressure water regulating control valve. Condenser (source) water shall be provided by a cooling tower or some other remote water source. The system shall require only single point supply power connection and shall ship from the SATS factory with a full operating refrigerant (R-22) charge.

Water Regulating Valves:

Head pressure shall be automatically controlled by a factory installed 2-way water regulating valve rated for 150 psig w.w.p.

Note: 3-way and high pressure (350 to

400 psig) rated valves are optionally available, page 3-12.

DX - GLYCOL COOLED SYSTEMS

Integral Self-Contained

(Models CCU/D-( )-G)

The system shall be a self-contained, floor mounted precision air condi-tioner to include integral glycol cooled condenser with factory installed head pressure glycol regulating control valve. Condenser (source) glycol solution shall be provided via a SATS model GPS-( )-( ) / FSS-( ) remote glycol pump package and drycooler system.

The system shall require only single point supply power connection and shall ship from the SATS factory with a full operating refrigerant (R-22) charge.

Glycol Regulating Valves:

Head pressure shall be automatically controlled by a factory installed 2-way glycol regulating valve rated for 150 psig w.w.p.

Note: 3-way and high pressure (350 to

400 psig) rated valves are optionally available, page 3-12.

CHILLED WATER AIR HANDLERS Chilled Water System

(Models CCU/D-( )-CW)

The system shall be a floor mounted chilled water precision air conditioner to include chilled water cooling coil, evaporator blower and motor and chilled water control valve. Chilled water shall be provided by a remote liquid chiller system.

Chilled Water Control Valve:

Cooling capacity shall be controlled with a factory installed 3-way modu-lating control valve rated for 300 psig. Note: 2-way and 3-way high pressure

(to 400 psig) rated modulating valves are optionally available, page 3-12.

(10)

Selected Standard Features -

"CCU/D" Series

"CCU/D" Model

SELECTED STANDARD FEATURES:

41/61

81/110

121

171/201/200

TEMPERATURE CONTROL

• 1-Stage Cooling Mode Standard Standard Standard Standard

• 1-Stage Electric Reheating / Heating Standard Standard N/A N/A

• 2-Stage Electric Reheating / Heating Optional Optional Standard Standard

• Cooling &/or Heating Only (No Humidity Control) Optional Optional Optional Optional

HUMIDITY CONTROL

• Electrode Canister Steam Humidifier Standard Standard Standard Standard

• Dehumidification Mode Electric Reheat Standard Standard Standard Standard

CONTROLS

• C-1002 Advanced Micropressor w/ Alarms Standard Standard Standard Standard

• C-5000 Advanced Micropressor w/ Alarms Optional Optional Optional Optional

CABINET

• Galvannealed Steel, Powder Coated Finish Standard Standard Standard Standard

• Insulated Aluminum Condensate Drain Pan Standard Standard Standard Standard

• 2 lb Density Thermal & Sound Insulation Standard Standard Standard Standard

• Floor Stand (Adjustable, turning vanes optional) Optional Optional Optional Optional

FILTERS / PLENUMS

• 1", 30% Avg. Eff. Pleated Filters Standard Standard Standard N/A

• 2", 30% Avg. Eff. Pleated Filters N/A N/A N/A Standard

• 2", 60% Avg. Eff. Pleated Filters N/A N/A N/A Optional

• 2 or 3-way Plenum Box (Up-Flow Units) Optional Optional Optional Optional

DX-REFRIGERATION CIRCUIT

• HCFC-R22 Refrigerant Standard Standard Standard Standard

• Scroll Compressors Standard Standard Standard Standard

• Rotolock Service Valves Standard Standard Standard Standard

• High Efficiency, Aluminum Fin / Copper Tube Coils Standard Standard Standard Standard

• Thermal Expansion Valves Standard Standard Standard Standard

• Refrigerant Sight Glasses & Filter/Drier Strainers Standard Standard Standard Standard

• HFC-R407 Refrigerant Optional Optional Optional Optional

BLOWERS / MOTORS

• Direct-Drive Evaporator Blower / Motor Standard Standard Standard N/A

• Belt-Drive Evaporator Blower / Motor N/A N/A N/A Standard

ELECTRICAL

• 1 or 3-Phase Power Supply See Electrical Tables Section 5

-• Multi-Voltage Control Transformer (24V Class 2) Standard Standard Standard Standard

SAFETY FEATURES

• C1002 Visual Local & Remote Alarms Standard Standard Standard Standard

• Main Power Non-Fused Disconnect, unit mounted Standard Standard Standard Standard

• High / Low Refrigerant Pressure Switches (DX units) Standard Standard Standard Standard

• Motor Overload Protection Standard Standard Standard Standard

SPECIFIC MODEL STANDARD FEATURES:

AIR COOLED

• Low Ambient Head Pressure Control Three types 0°F, 20°F or 30°F

-• Remote Air Cooled Condenser Standard Standard Standard Standard

WATER / GLYCOL COOLED

• 2-way, 150 psig Water/Glycol Regulating Valves Standard Standard Standard Standard

• High Pressure &/or 3-way Valves Optional Optional Optional Optional

• Stainless Steel Brazed Plate Heat Exchanger Standard Standard Standard Standard

CHILLED WATER SYSTEMS (CCU-110/200-CW)

• 3-way, 300 psig Modulating Valve N/A Standard N/A Standard

• 2-way, 300 psig Modulating Valve N/A Optional N/A Optional

• 2 or 3-way, 400 psig Modulating Valve N/A Optional N/A Optional

Guide S

pecifications

S

tandard Features “Quick-Reference” T

(11)

Guide S

pecifications

S

tandard Equipment

Guide Specifications -

Standard Equipment

munications or other highly sensitive heat load equipment where continu-ous 24 hour-a-day, 365 days-a-year air conditioning is required. De-signed for front-only access, “Preci-sion A/C” systems require minimal floor space.

The supplied system shall be provided with ETL Certification. The environmental control system shall be a SATS Mini-Space, factory-assembled, Precision A/C unit. The unit shall be designed for corner installation, requiring front only access through a removable front access panel. No allowance for side service access shall be re-quired. The Mini-Space Series Precision A/C units are especially adapted to raised floors and are available in both down-flow and up-flow air pattern configurations. The evaporator section shall be specifi-cally designed for high sensible heat ratio.

The system shall be manufactured by Stulz Air Technology Systems, Inc. in Frederick, Maryland, USA.

100% Front Access

The air conditioner shall require front only access for all routinely

maintenanced components. No allowance for side service access shall be required.

Cabinet Construction

Access panels shall be fabricated from heavy gauge steel and shall be securely attached to the base and top plates. Both access panels shall be powder coated to match and provide corrosion protection. The panels shall be lined with 1/2" (13 mm), 2 lb (.90 kg), high-density sound and thermal insulation and sealed with self-extinguishing gasketing conforming to NFPA 90A and 90B.

GENERAL GUIDE

SPECIFICATION

General Description

The SATS Mini-Space vertical floor-mounted air conditioning system shall provide precision temperature and humidity control for computer rooms or rooms containing

telecom-Electrical System

Modular Motor Controllers

The system shall incorporate modular motor controllers utilizing motor start protectors and circuit breakers eliminating the need for fusing, as well as providing:

„ Motor branch circuit short circuit protection

„ Motor load switching controllers (contactors)

„ Motor overload protection The system shall incorporate over-current and overload protection in accordance with UL 1995 require-ments. Each blower motor, com-pressor, electric heater stage and humidifier (if applicable) shall be provided with a factory mounted and wired starter/contactor.

The control circuit shall be a 24 VAC Class 2 low voltage circuit including a circuit breaker for protection. Low voltage, high voltage and grounding wires shall be color coded and shall be individually numbered at each end for ease of service tracing. All wiring shall be in accordance with the National Electric Code (NEC).

QUALITY ASSURANCE

(ISO-9001:2001 Registered)

SATS operates in an ISO-9001:2001 registered quality control environment. Each SATS employee is committed to satisfy-ing his or her customer expecta-tions with the highest level of consistent, measurable and continuous quality improvement.

(12)

DX Evaporator Coils

The system shall be configured for a draw-thru air pattern to provide uniform air distribution over the coil face. The coils shall be designed to provide maximum coil surface area and minimum depth to provide a high sensible cooling capacity. The coils shall be seamless drawn copper tubes, mechanically bonded to tempered aluminum fins with a raised lanced fin design for maxi-mum heat transfer. Coil end plates shall be hot dipped galvanized steel. The evaporator coil shall be mounted in an insulated aluminum condensate drain pan. Refrigerant flow shall be controlled by an externally equalized thermostatic expansion valve.

pressor shall be complete with charging and service schraeder ports, internal vibration isolation, internal thermal overloads, an internal pressure relief valve, an internal discharge gas vibration eliminator and external vibration mounting isolation.

Chilled Water System

(Models CCU/D-( )-CW)

Cooling Coil:

The chilled water coil shall be con-structed of seamless drawn copper tubes, mechanically bonded to tempered aluminum fins for maxi-mum heat transfer. Coil end plates shall be hot dipped galvanized. The cooling coil shall be mounted in an insulated aluminum condensate drain pan.

CW Control Valve:

Cooling capacity shall be controlled by a factory installed 3-way, modulat-ing control valve rated for a maximum 300 psig w.w.p.

Note: 2-way valves are optionally available, page 3-12.

Blowers / Motors

Direct-Driven Systems

(Models CCU/CCD-41 to 121)

The blower shall be direct-driven with double-width, double-inlet housing and forward-curved blades. The blower shall be dynamically and statically balanced to minimize vibration and operate in the Class 1

Guide Specifications -

Standard Equipment

Guide S

pecifications

S

tandard Equipment

Thermal Expansion Valves Sight Glasses Filter Drier/ Strainers Remote Start/ Stop Contacts

Included in the system’s electrical control circuit shall be a 2–pin terminal connection for remote stop/ start of the Mini-Space air condi-tioner by remote source.

Main Power Service Switch

The indoor evaporator shall be provided with a unit mounted main power service switch. The service switch shall be a dust-proof, non-fused type with lockable handle.

DX Refrigeration System

All refrigeration piping shall be refrigerant grade tubing. Each refrigerant circuit shall include, as a minimum a refrigerant drier/strainer, sight glass with moisture detector, a thermal expansion valve with rapid bleed port feature and external equalizer, an evaporator coil, a compressor, a high pressure switch with manual reset and a low pressure switch with automatic reset.

Split/ Remote systems shall have a liquid line solenoid for refrigerant isolation to prevent liquid slugging. All high pressure joints shall be brazed, and the entire system shall be pressure tested at the factory with dry nitrogen, evacuated to at least 50 microns and fully charged with refrigerant.

Note: All split / remote DX systems ship with a dry nitrogen holding charge. All self-contained DX systems ship with a full refrigerant (R-22) operating charge.

Scroll Compressors

The compressor shall be a high efficiency, high reliability and low noise scroll compressor. The

(13)

com-Sensor Location

As a standard, the C-1002 shall be provided with an internal tempera-ture/humidity sensor.

Remote Sensor Option

The C-1002 temperature and humid-ity sensor shall be shipped loose for remote wall mounting. Interconnect cabling shall not be provided as the standard with the remote sensor option, but an optional 75 ft. cable or 150 ft. cable is also available.

Recovery Delay:

After a power loss, the C-1002’s Recovery Delay feature allows the Precision A/C to operate without initiating any high or low temperature or humidity alarms for a delayed period. This feature allows the A/C time (15 to 60 minutes adj.) to “pull-down” the conditioned space’s load without nuisance alarms during initial startup or power loss restart.

Cold Start Time Delay:

Each compressor of a DX Split system shall be provided with the C-1002’s Cold Start compressor time delay. The Cold Start timer delays and therefore, overrides the system’s refrigerant low suction pressure switch during system startup. This allows the system time to build sufficient discharge pressure during cold weather startup.

SECURITY:

Multiple security levels prevent unauthorized adjustment of critical system parameters. The user may select a four-digit password for range. The blower shall be corrosion

protected. The blower motor shall have internal overload protection.

Additionally, the fan speed shall have a manual adjustment via a potenti-ometer to meet specific air-flow requirements. The fan motor shall be 1075 rpm.

Belt Driven Systems

(Models CCU/CCD-171 to 201)

The blower shall be belt driven with a double-inlet housing and forward-curved blades and permanently lubricated ball bearings sized for an average 150,000 hours of service life. The blower shall be dynamically and statically balanced to minimize vibration and operate in the Class 1 range. The blower shall be belt driven with dual belts sized for 200% of the fan motor horsepower. The blower shall have an adjustable base for belt tensioning and a locking system to prevent the motors from moving. The motor’s drive sheaves shall have an adjustable pitch to change the speed of the blowers. The motor shall be 1725 rpm and shall have overload protection and a minimum NEMA service factor of 1.15.

Controls

The standard Mini-Space floor A/C includes the C-1002 Advanced Microprocessor Controller, Canister Steam Humidifier and Dehumidifica-tion Mode with Electric Reheat/Heat providing precision temperature and humidity control.

Guide Specifications -

Standard Equipment

Guide S

pecifications

S

tandard Equipment

C-1002 Controller

(Microprocessor Controller w/ Alarms)

The Mini-Space precision A/C unit shall be provided with SATS’ C-1002

Microprocessor based Temperature and Humidity controller with Alarms. The control shall provide the user with an easy to read, LED display showing operating mode status, set points and actual values.

Display:

The C-1002 shall provide visual indication of the following alarm conditions:

„High Temperature

„Low Temperature

„High Humidity

„Low Humidity

„High Head Pressure

„Low Suction Pressure

„Dirty Filter

„Loss of Airflow

„Sensor Failure

„Summary Alarm- Includes condensate

overflow/water detection, smoke detector, firestat (if applicable).

A standard non-powered summary alarm contact is available for all systems.

The C-1002 shall be provided with a RS-485 Serial Port as a standard.

(14)

Steam Generating Humidifier

Canister Steam Humidification:

(standard)

The humidifier shall be an electrode steam canister type and shall have an adjustable humidity output setting from 25 to 100% of the full rated humidifier capacity. The humidifier shall incorporate an automatic flush cycle that senses the current con-sumption of the humidifier and controls mineral concentration of the water. A “Change Cylinder” light shall notify service personnel when the humidifi-cation output is below rated

requirements and when maintenance is due.

Dehumidification Cycle: (standard)

The floor A/C shall be provided with a refrigeration based dehumidification mode. Moisture is condensed on the cooling coil and discharged through the condensate drain. Reheat (elec-tric, hot gas or hot water) shall be provided to offset sensible cooling during the dehumidification cycle.

Dehumidification Mode

(CCU/CCD 41 to 121)

A factory mounted and wired electric resistance heater element shall be included to provide an automatic sensible reheating mode during the dehumidification cycle and an automatic heating mode as required. Electric heaters shall be provided with thermal / magnetic circuit breakers which shall protect each

conductor. Included shall be one automatic resetting over-temperature safety device (pilot duty), and a non-resettable over-temperature safety device (located in main power line).

(CCU/CCD 171 to 201)

A factory mounted and wired low-watt density, plated fin-tubular design electric resistance heater shall be included to provide automatic sensible re-heating as required during the dehumidification cycle and automatic heating mode. Electric heaters shall be provided with miniature thermal/magnetic circuit breakers, which shall protect each ungrounded conductor. Also included will be one automatic reset and one manual reset over-temperature safety device (pilot duty). Two stages of electric reheat/heat shall be provided as standard.

Evaporator Air Patterns and Filtration

UP-FLOW:

(CCU-( )-( ))

The air conditioner shall be config-ured for an up-flow air pattern with free evaporator return air through front filtered grille and conditioned supply air through the top of the unit.

Top “Ducted” Discharge with:

„ Front “Free” Return; or „ Rear “Ducted” Return

Top Discharge Through two or three-way grille Plenum Box with:

„ Front “Free” Return; or „ Rear “Ducted” Return

Guide Specifications -

Standard Equipment

Guide S

pecifications

S

tandard Equipment

setpoint and configuration changes.

Password Protection:

The C-1002 includes a selectable password protection feature that prevents unauthorized users from making changes to system setpoints and settings available directly from the multi-function keypad/display.

Two Unit Sequencing:

Critical control applications shall be addressed with the C-1002 two-unit sequencing program logic. Under an A/C failure condition the controller will automatically initiate the unit operation of the designated standby/ backup unit, as well as, locally and remotely alert the alarm condition. The two-unit sequencing control logic shall automatically initiate the current standby unit upon a system failure alarm condition.

The control is programmed to automatically change from the current primary unit operation to secondary/standby unit operation via two methods:

1) Automatic Timed (every 7 days) 2) Automatic Changeover on Unit Failure

As well, the control shall also enable the standby/backup unit in the event that the primary unit is not able to handle the cooling requirement. As the maximum room temperature limits are reached with the primary unit, the standby/backup unit shall become enabled to assist in the cooling requirement until room conditions are back within a satisfac-tory range.

(15)

(A top duct connection shall be avail-able as an option. 2 & 3-way top

discharge plenum boxes are available,

page 3-12.)

DOWN-FLOW:

(CCD-( )-( ))

The air conditioner shall be config-ured for a down-flow air pattern with free evaporator return air to the top and conditioned supply air discharge through bottom of the A/C into the raised floor.

(A top flanged return air duct connection is optionally available.)

Air Filtration

The A/C shall have slide out, 1" deep (CCU/D 41 to 121) or 2" deep (CCU/ D 171 to 201), class 2 (per U.L. Standard 900) filters. The filters shall be easily accessed through the front. The filters shall have an average efficiency rating of 30% in accor-dance with ASHRAE Standard 52-76 test method.

DX - Heat Rejection

AIR COOLED

The air-cooled system shall consist of a split air cooled unit with remote outdoor condenser.

Outdoor - Remote Condensers

Models WCS-( )

A remote outdoor, air cooled con-denser, with direct driven propeller fan(s) shall be provided. The con-denser shall be suitable for outdoor installation. Each fan shall be pro-vided with a low RPM, outdoor rated, non-overloading direct driven motor. Each evaporator refrigerant circuit shall be directly connected to an independent condenser coil circuit rated for the full heat of rejection of the air conditioner at a 95°F ambient temperature. The following head

pressure control features are offered: „ WCS-( )-P: Head pressure control to 0°F ambient .

„ WCS-( )-V: Head pressure control to -20°F ambient .

„ WCS-( )-F: Head pressure control to -30°F ambient .

Note: Please refer to page 3-11, for specification details of Mini-Space air cooled condenser "Low Ambient Control" options: 0°F, -20°F & -30°F

WATER COOLED

Integral Water Condensers

(Model CCU/D-( )-W)

SS Brazed-Plated Water Cooled Condensers:

Each evaporator refrigerant circuit shall be provided with a factory installed single pass, counterflow configured, brazed plate heat ex-changer, with integral subcooler, constructed of type 316 stainless steel; designed and tested for a 425 psig. w.w.p.

Head Pressure Control:

Two-Way, 150 psig Regulating Valve

Each refrigerant circuit's head pressure shall be controlled by a factory installed 2-way water regulat-ing valve rated for 150 psig. w.w.p.

Guide Specifications -

Standard Equipment

Guide S

pecifications

S

tandard Equipment

(16)

Guide Specifications -

Standard Equipment Warranty

Guide S

pecifications

S

tandard Equipment W

arranty

GLYCOL COOLED

Integral Glycol Condensers

(Model CCU/D-( )-G)

SS Brazed-Plated Glycol Cooled Condensers:

Each evaporator refrigerant circuit shall be provided with a factory installed single pass, counterflow configured, brazed plate heat ex-changer, with integral subcooler, constructed of type 316 stainless steel; designed and tested for a 425 psig. w.w.p.

Head Pressure Control:

Two-Way, 150 psig Regulating Valve

Each refrigerant circuit's head pres-sure shall be controlled by a factory installed 2-way glycol regulating valve rated for 150 psig. w.w.p.

CHILLED WATER SYSTEMS

Chilled Water System

Com-ponents

(Model CCU/D-( )-CW)

Chilled Water Cooling Coil: The chilled water coil shall be con-structed of seamless drawn copper tubes, mechanically bonded to tempered aluminum fins with a raised lance fin design for maximum heat transfer, and mounted in a stainless steel condensate drain pan. The water circuit shall be designed to distribute water into the entire coil face area.

Chilled Water Control: The water circuit shall include a 3-way modulating valve. Design pres-sure shall be 300 psig. 2-way, 300 psig or 400 psig valves as well as 3-way, 400 psig shall be provided as an option.

PRODUCT WARRANTY:

Stulz Air Technology Systems, Inc., warrants to the original buyer of its products that the goods are free from defects in material and workmanship. Stulz Air Technology Systems, Inc.’s obligation under this warranty is to repair or replace, at its option, free of charge to the customer, any part or parts which are determined by Stulz Air Technology Systems Inc. to be defective for a period of 24 months from date of shipment when a completed start-up form has been submit-ted to Stulz Air Technology Systems, Inc. within 90 days from shipment. In the event that a completed start-up form is not received by Stulz Air Technology Systems, Inc. within 90 days from shipment, the company’s obligation will be for a period of 12 months from date of shipment. Parts repaired or replaced under this warranty are shipped FOB Factory, and warranted for the balance of the original warranty period or for 90 days from the date of installation, whichever is greater.

Stulz Air Technology Systems, Inc.’s warranty does not cover failures caused by improper installation, abuse, misuse, mis-application, improper or lack of maintenance, negligence, ac-cident, normal deterioration (including wear and tear), or the use of improper parts or improper repair.

Purchaser’s remedies are limited to replacement or repair of non-conforming materials in accordance with the written war-ranty. This warranty does not include costs for transportation, costs for removal or reinstallation of equipment or labor for repairs or replacement made in the field.

If any sample was shown to the buyer, such sample was used merely to illustrate the general type and quality of the product, and not to represent that the equipment would necessarily conform to the sample.

This is the only warranty given by the seller, and such war-ranty is only given to buyers for commercial or industrial pur-poses. This warranty is not enforceable until the invoice(s) is paid in full.

THE FOREGOING SHALL CONSTITUTE SATS’ ENTIRE LI-ABILITY AND YOUR EXCLUSIVE REMEDY. IN NO EVENT SHALL SATS BE LIABLE FOR ANY DIRECT, INDIRECT, SPE-CIAL, INCIDENTAL, CONSEQUENTIAL, OR EXEMPLARY DAMAGES, INCLUDING LOST PROFITS (EVEN IF ADVISED OF THE POSSIBILITY THEREOF) ARISING IN ANY WAY OUT OF THE INSTALLATION, USE OR MAINTENANCE OF THE EQUIPMENT. THIS WARRANTY IS IN LIEU OF ALL OTHER WARRANTIES, EXPRESS OR IMPLIED, INCLUD-ING WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE.

(17)

Optional Features -

Guide Specifications

Microprocessor Controls

C-5000 Microprocessor ...3-9/10 - Display/Keypad ... 3-9 - Control Inputs/Outputs ...3-9/10 • Remote BMS Communications ...3-11

Selected Options

Filtration ...3-11 • Reheat Options

- Hot Gas Reheat ... 3-11 - Hot Water Reheat / Heat ... 3-11

Head Pressure Control Options

Air Cooled - Low Ambient Control

• 0°F Ambient ... 3-11 • -20°F Ambient ... 3-11 • -30°F Ambient ... 3-11

Water/Glycol Cooled - Regulating Valves

• 2-way, 150 psig (standard) ... 3-12 • 2-way, 350 psig ... 3-12 • 2-way, 400 psig ... 3-12 • 3-way, 150 psig ... 3-12 • 3-way, 350 psig ... 3-12 • 3-way, 400 psig ... 3-12

DX - Capacity Modulation

Snap-Acting, Hot Gas Bypass... 3-12

Chilled Water Modulating Control Valves

3-way, 400 psig ...3-12

2-way, 300 & 400 psig ...3-12

Accessories

Floor Stands

- Seismic Floor Stand ... 3-12 - Turning Vanes ... 3-12

2 or 3-Way Plenum Discharge Box... 3-12

Condensate Pump... 3-13

Smoke Detection... 3-13

Firestat... 3-13

Remote Water Detector:

- Qty. One, Spot Type ... 3-13 - Qty. Two, Spot Type ... 3-13 - 25 Ft. - Strip/Cable Type ... 3-13

Optional Features Index

Optional Features

(18)

Advanced Microprocessor

Temperature & Humidity

Controller with Alarms

The A/C unit shall be provided with SATS’ CompTrol 5000® Micropro-cessor based Temperature and Humidity controller with Alarms. The controller shall incorporate a “user-friendly” operating environment, to allow easy system setup and opera-tion.

The CompTrol 5000® (C-5000) is a complete microprocessor based control system designed for operat-ing, controlling and monitoring the precision air conditioning unit. The C-5000 controller shall include a full-featured LCD graphical display for visual indication of the unit operating conditions.

USER INTERFACE:

The User Interface shall feature an easy to read, liquid-crystal, graphical display. The attractive unit mounted interface, allows the operator to

visually monitor and customize unit functions and settings. The controller is operated via a 4-key menu-driven windows type structure, in three different modes; Information, Opera-tion, and Service.

FIELD CONFIGURABLE:

The C-5000 controller is field pro-gram configurable and capable of matching the unique needs of any data center, telecommunication or other critical area.

SENSOR LOCATION:

As a standard, the C-5000 tempera-ture and humidity sensor shall be factory unit mounted in the return air stream of the Precision AC unit.

SYSTEM SETUP & ADJUSTMENTS:

The C-5000 shall be completely factory preprogrammed, and there-fore, most applications will require no field setup. However, the “default” set points and their ranges are easily

adjusted from C-5000 keypad/

display.

UNIT STATUS DISPLAY:

The C-5000 keypad displays current unit functions and room status:

„ Current Dry Bulb Temp

„ Current Relative Humidity

„ Actual Time

Current Unit Status:

„ System ON/OFF „ Cooling „ Heating „ Humidifying „ Dehumidifying „ Reheating Run Times

The historical run-time in hours of the following major components is available directly from the C-5000 keypad/display: (if applicable)

• Evaporator Blower Motor • Compressor

• Humidifier

• Chilled Water Valve

ALARM CONDITIONS:

Alarm conditions activate an audible and visual indicator. An alarm shall be acknowledged through a button located on the keypad display. The C-5000 alerts to the following alarm conditions (if applicable):

„High Temperature „Dirty Filter

„Low Temperature „Smoke Detection

„High Humidity „Firestat

„Low Humidity „Leak Detection

„High Head Press „GC Pump Failure

„Low Suction Press „Sensor Failure

„Loss of Air Flow „Comm. Failure

Summary Alarm Contact:

A summary alarm dry-contact (n/o) connection shall be available for remote annunciation of an alarm condition.

Alarm History:

The C-5000 controller provides users with a recorded history of the previ-ous 80 alarms, including the time and date of the alarm.

CONTROL INPUTS / OUTPUTS:

The C-5000 is capable of both digital (on/off) and analog input and output device control. Prior to shipment, each Precision AC unit’s C-5000 is factory program configured to match the unit’s system operational require-ments.

Temperature Anticipation:

The C-5000 shall incorporate a self-calibrating and self-adjusting control logic that adjusts the response of the SATS air conditioner to changes in temperature and humidity. The system shall provide premium

C-5000 Series Controls:

Guide S

pecifications

- Microprocessor Control Options

(19)

setpoint accuracy while controlling the room conditions rate of change, minimizing the equipment energy consumption and maximizing the system’s operating life and reliability.

POWER LOSS RESTART:

In the event of a loss of power to the system, the C-5000 can be config-ured for Automatic or Manual Re-start. The C-5000’s non-volatile memory enables the system to restart when power is restored, without the loss of the “last” stored setpoints and other system configu-ration settings.

Sequential Load Activation:

To minimize the total in rush current loads during system startup/restart, the C-5000 controller shall be configured for time-delay sequence startup. The user can designate specific unit restart time-delays, as well as, each unit’s respective compressor, electric heater and/or humidifier. Unit restart delay can be adjusted from 0 to 10 minutes. Unit compressor, electric heater and/or humidifier restart delay can be adjusted from 0 to 60 seconds.

Recovery Delay:

After a power loss, the C-5000’s Recovery Delay feature allows the Precision A/C to operate without initiating any high or low temperature or humidity alarms for a delayed period. This feature allows the A/C time (15 to 60 minutes adj.) to “pull-down” the conditioned space’s load without nuisance alarms during initial startup or power loss restart.

COMPRESSOR OPERATIONS:

Short Cycle Protection:

Each compressor shall be protected from frequent compressor cycling through the C-5000’s minimum

compressor ON and minimum compressor OFF short cycle timers.

Cold Start Time Delay:

Each compressor of a DX Split System shall be provided with the C-5000’s Cold Start compressor time delay. The Cold Start timer delays, and therefore, overrides the system’s refrigerant low suction pressure switch during system startup. This allows the system time to build sufficient discharge pressure during cold weather startup.

SECURITY:

Multiple security levels prevent unauthorized adjustment of critical system parameters. The user may select a four-digit password for setpoint and configuration changes.

Password Protection:

The C-5000 includes a selectable password protection feature that prevents unauthorized users from making changes to system setpoints and settings available directly from the multi-function keypad/display.

DIAGNOSTICS & SERVICE MODE

The C-5000 incorporates a unique self-diagnostics algorithm that

continually tests system functions and hardware operation. In the event of such a failure, the user will be alerted to the condition via a visual and audible alarm.

Control Board:

Initiates a self-test of the control system.

Input Diagnostics:

All system inputs and output devices are continuously monitored for proper operation.

TWO UNIT SEQUENCING:

Critical control applications shall be addressed with the C-5000 two-unit sequencing program logic. Under an A/C failure condition the controller will automatically initiate the unit operation of the designated standby/ backup unit, as well as, locally and remotely alert the alarm condition. The two-unit sequencing control logic shall automatically initiate the current standby unit upon a system failure alarm condition.

The control is programmed to automatically change from the current primary unit operation to secondary/standby unit operation via two methods:

1) Automatic Timed (every 7 days) 2) Automatic Changeover on Unit Failure

As well, the control shall also enable the standby/backup unit in the event that the primary unit is not able to handle the cooling requirement. As the maximum room temperature limits are reached with the primary unit, the standby/backup unit shall become enabled to assist in the cooling requirement until room conditions are back within a satisfac-tory range.

Guide S

pecifications

- Microprocessor Control Options

(20)

Head Pressure Control

AIR COOLED

- Low Ambient 0

°

F, Pressure Fan

Cycling-The air cooled system shall incorpo-rate a low ambient pressure fan cycling control for year-round A/C system operation down to 0°F DB minimum ambient air temperature.

-20

°

F, Variable Fan

Speed-The air cooled system shall incorpo-rate a low ambient variable speed fan head pressure control for year-round A/C system operation down to -20°F DB minimum ambient air temperature. -30

°

F, Flooded Control-HP LP Flooded Head Pressure Control Valve Equalizer Line Liquid Line Solenoid Valve Refrigerant Reclaim Port Liquid Refrigerant Receiver Relief Valve Sight Glass Refrigerant

Drier / Strainer Thermal Expansion Valve Low Pressure Switch Scroll Compressor Remote Air Cooled Condenser Evaporator Cooling Coil Feeler Bulb High Pressure Switch

The air cooled system shall incorpo-rate a low ambient flooded head pressure control for year-round A/C system operation down to -30°F DB minimum ambient air temperature.

This option shall include a factory installed crankcase heater, cold-start relay, liquid refrigerant receiver with liquid level sight glass and head pressure-regulating valve for flooded condenser option.

Optional Filtration:

Medium Efficiency Filters

(Model CCU/CCD-171 to 201 only)

The system shall be provided with a 2" filter with an average efficiency rating of 60% in accordance with ASHRAE Standard 52-76 test method.

Reheat Options:

Hot Gas Reheat:

(Models available CCU/D-( )-A, W& G)

A factory piped and wired hot gas reheat valve shall be provided to divert the hot compressor discharge gas from the condenser to the hot gas reheat coil during the dehumidi-fication cycle. This energy saving feature shall require no additional energy to offset the sensible cooling capacity while in the dehumidifica-tion mode.

Hot Water Reheat/Heat

A factory installed copper tube aluminum fin heat/reheat coil and two-way (on/off) valve shall be provided to control the flow of hot water for heating the conditioned air.

Mini-Space floor systems include the C-1002 Microprocessor Controller, Electrode Canister Steam Humidifier and Dehumidifi-cation Mode with Electric Reheat/ Heat for total temperature and humidity control, as a standard. However, these standard features can be deleted and/or substituted with alternate features to allow you the flexibility to select the configu-ration best suited for your unique application.

SELECTED OPTIONS

Optional Features -

Guide Specifications

Optional Features

- Guide Specifications

Remote BMS

Connec-tion (C-1002 & C-5000)

MIB GATEWAY

Control Inputs & Outputs shall be remotely monitored (address read-able) and remotely controlled (ad-dress writable) via any building management system (BMS) / local area network (LAN) control system that can communicate via a ModBus protocol. Each unit configured for BMS communication shall incorpo-rate an optional RS-485 Serial Communication Port that is field connected to a factory provided wall mounted ModBus Gateway.

(21)

WATER/GLYCOL COOLED

DX Water Cooled and Glycol Cooled systems are available with following standard and optional head pressure regulating control valves:

• 2-way, 150 psig (standard)

• 2-way, 350 psig(optional)

• 2-way, 400 psig(optional)

• 3-way, 150 psig(optional)

• 3-way, 350 psig(optional)

• 3-way, 400 psig(optional)

Two-Way, 350 psig Regulating Valve

Each refrigerant circuit’s head pressure shall be controlled by a factory supplied, high pressure two-way water /glycol regulating valve rated for 350 psig. w.w.p.

Three-Way, Head Pressure Regu-lating Valve

Each refrigerant circuit’s head pressure shall be controlled by a factory supplied:

„ 3-Way, 150 psig w.w.p. head pressure valve or,

„ 3-Way, 350 psig w.w.p. head pressure valve.

DX- Capacity Modulation/

Freeze-Protection

SNAP-ACTING, Hot Gas Bypass

(Models CCU/D-()-A, W & G only) The floor A/C units shall incorporate a hot gas bypass system to provide modulation of the unit’s cooling capacity. This option shall also

provide evaporator coil freeze protec-tion under low load condiprotec-tions.

HP LP Flooded Head Pressure Control Valve Equalizer Line Liquid Line Solenoid Valve Refrigerant Reclaim Port Liquid Refrigerant Receiver Relief Valve Sight Glass Refrigerant

Drier / Strainer Thermal Expansion Valve Low Pressure Switch Scroll Compressor Remote Air Cooled Condenser Evaporator Cooling Coil Feeler Bulb High Pressure Switch Hot Gas Regulator Valve (Optional)

Chilled Water Control

Valves

Chilled Water cooling shall be con-trolled by the following standard and optional control valves:

Models CCU/D-110/200-CW:

• 3-way, 300 psig(standard)

• 2-way, 300 psig(optional)

• 2-way, 400 psig(optional)

• 3-way, 400 psig(optional) Standard Valve Control:

A ____-way modulating CW cooling control valve rated for a maximum ____ psig w.w.p. shall be factory installed. Precision cooling control shall be accomplished via a C-1002 modulating control signal to the control valve.

Optional Features -

Guide Specifications

Optional Features

- Guide Specifications

ACCESSORIES

Adjustable Floor Stand:

OPTIONAL TURNING VANE

An adjustable floor stand shall be provided to allow for ease of installa-tion of the unit onto a raised floor. Floor stand height shall range (nominal 12", 18", & 24") and shall have field adjustment capability.

Note: For additional floor stand heights,

please contact your local SATS sales representative.

Additional Floor Stand Options:

Seismic Zone-4 Rate:

The adjustable floor stand shall be rated for seismic zone-4 installation.

Turning Vanes:

Turning vanes shall be factory installed to each unit's floor stand.

Top Discharge Plenum Box:

(Up-Flow units only)

(22)

Optional Features -

Guide Specifications

firestat. The firestat will shut down the air conditioner upon sensing a high return air temperature.

Remote Water Detector:

A remote single point water/leak detector shall be included to provide additional safety to the standard condensate pan safety float. Upon sensing a water leak, the normally closed water detector control circuit opens, which will cause the air conditioner to shut down.

Dual (two) - Spot Type Detectors:

Quantity 2 (two) remote spot type water/leak detectors per A/C unit shall be factory provided for remote field installation. Upon sensing a water leak, the normally closed water detector control circuit opens, which will cause the air conditioner to shut down.

Remote Water Detector- Strip Type:

A 25 ft. in length remote strip/cable type water/leak detector shall be provided for remote field installation. Upon sensing a water leak, the normally closed water detector control circuit shall open, thereby shutting down the A/C unit

Optional Features

- Guide Specifications

shall be provided. The plenum box shall include double-deflecting, adjustable grilles.

Condensate Pump:

A high capacity, high temperature condensate pump shall be provided for automatic removal of condensate and humidifier flush water (if appli-cable). The condensate pump shall be specifically designed to operate with the higher condensate tempera-tures caused by the flush and drain cycle of the electrode canister humidifiers. As a standard the condensate pump shall ship loose for field installation on all systems. Factory installation of the conden-sate pump is available as an option on models CCU-171 and CCU-201 (upflow).

Smoke Detection:

A photoelectric smoke detector shall

be factory installed and wired in the evaporator section of the suction side of the evaporator blower. The air conditioner will shut down upon sensing smoke in the return air stream.

Firestat:

The air conditioner shall be provided with a factory wired and mounted

(23)

Performance Data -

Index

Performance Dat

a

-

Index

INDEX

Performance Data:

• Air Cooled, 1- 7 Ton Systems ... 4-2/3 • Water Cooled, 1- 7 Ton Systems ... 4-4/5 • Glycol Cooled, 1- 7 Ton Systems ... 4-6/7 • Chilled Water Cooled, 3- 7 Ton Systems ... 4-8/9

(24)

Performance Dat

a

-

Air Cooled (1 to 7 ton Systems)

Air Cooled -

1 to 7 Ton "CCU/D"

"CCU/D" Model CC( )-41-A CC( )-61-A CC( )-81-A CC( )-121-A CC( )-171-A CC( )-201-A

NET DX COOLING CAPACITY - BTU/H, (includes standard DX evaporator motor heat @ std CFM & e.s.p. ratings)

75°FDB/62.5°FWB, 50% RH Total 17,500 24,900 32,100 44,900 56,300 72,200 Sensible 15,900 21,500 27,800 38,800 53,800 68,500 72°FDB/60°FWB, 50% RH Total 17,000 24,100 31,100 42,700 53,500 68,600 Sensible 15,500 21,100 27,200 37,600 51,400 65,600 70°FDB/58.5°FWB, 50% RH Total 16,000 22,800 29,800 42,200 51,500 66,500 Sensible 14,800 20,200 26,200 37,200 49,600 64,000 75°FDB/61°FWB, 45% RH Total 16,700 24,600 31,700 43,600 54,600 70,000 Sensible 15,600 22,000 28,400 39,700 53,000 68,400 72°FDB/58.5°FWB, 45% RH Total 16,300 23,100 29,800 40,900 52,200 66,900 Sensible 15,300 21,000 27,100 38,000 50,900 65,800 70°FDB/57°FWB, 45% RH Total 16,000 22,100 28,400 39,500 50,700 65,300 Sensible 15,100 20,300 26,100 36,700 49,500 65,300

Reheat/Heat - Performance Capacities Include Evaporator Blower Motor Heat

ELECTRIC REHEAT / HEAT - (Standard)

Htr Kw Rating (No. of Stages) 2 Kw (1-stg) 2 Kw (1-stg) 2 Kw (1-stg) 4 Kw (2-stg) 12 Kw (2-stg) 12 Kw (2-stg) Tot BTU/H (Kw) w/ Evap Mtr Ht: 8,730 (2.6) 8,730 (2.6) 8,730 (2.6) 15,560 (4.6) 48,580 (14.2) 48,580 (14.2)

HOT GAS REHEAT - (Optional)

BTU/H 16,740 16,990 29,720 29,965 48,875 53,350

HOT WATER REHEAT / HEAT - Reheat rated @ 180°F Entering Water Temperature, EAT = 72°F DB, (Optional)

BTU/H 31,465 31,465 63,475 63,475 114,450 124,902

GPM / Press. Drop (ft.wg) 3.2 / (.7) 3.2 / (.7) 6.5 / (.8) 6.5 / (.8) 11.7 / (2.4) 12.8 / (2.8)

Control 2way, 150 psig, Modulating (010 Vdc)

-Humidification - Electrode Steam Canister Humidifier with Adjustable Output, (Standard)

Lbs/Hr, (Kw Input) 2-5, / (1.7) 2-5, (1.7) 2-5, (1.7) 2-5, (1.7) 4-10, (3.4) 4-10, (3.4)

Std Control Cycling Cycling Cycling Cycling Cycling Cycling

Evaporator Blower / Motor - DWDI Centrifugal

Horsepower 3/4 Hp 3/4 Hp 3/4 Hp 3/4 Hp 3.0 Hp 3.0 Hp

CFM @ ext. st. press. 1,180 @ 0.2" 1,180 @ 0.2" 1,180 @ 0.2" 1,890 @ 0.2" 3,450 @ 0.3" 4,130 @ 0.3"

Drive Method Direct Direct Direct Direct Belt Belt

Evaporator Coil - Aluminum Fin, Copper Tube

Rows/Face Area (ft2) 4/ 3.25 4/ 3.25 4/ 3.25 4/ 3.25 4/ 8.3 4/ 8.3

Face Velocity, fpm 363 363 363 581 415 498

Compressor - Heat pump duty rated Scroll - HCFC Ozone Safe R-22

Type, (Qty.) Scroll, (1) Scroll, (1) Scroll, (1) Scroll, (1) Scroll, (1) Scroll, (1)

Power Input (Kw) 2.0 2.5 3.4 4.3 5.0 5.9

(25)

Performance Dat

a

-

Air Cooled (1 to 7 ton Systems)

Air Cooled -

Remote Condenser Data (1 to 7 Ton "CCU/D")

Remote Outdoor Air Cooled Condenser Data:

WCS-( )B - (Remote Outdoor Propeller Fan, Air Cooled Condenser for Evaporator Section)

"CCU/D" Model CC( )-41-A CC( )-61-A CC( )-81-A CC( )-121-A CC( )-171-A CC( )-201-A

Cond. Model @ 95°F Amb. WCS-002B WCS-003B WCS-003B WCS-005B WCS-008B WCS-008B

Condenser Fan Data

CFM @ free discharge 2,840 4,450 4,450 3,900 8,640 8,640

Motor Hp, (Qty.) 1/3 Hp, (1) 1/3 Hp, (1) 1/3 Hp, (1) 1/3 Hp, (1) 1/3 Hp, (2) 1/3 Hp, (2)

Net Weight (lbs.) 86 107 107 116 164 164

Refrigerant Connections - Copper

Liquid Line, (Qty.) 5/8" OD, (1) 5/8" OD, (1) 5/8" OD, (1) 5/8" OD, (1) 5/8" OD, (1) 5/8" OD, (1)

Hot Gas Line, (Qty.) 5/8" OD, (1) 5/8" OD, (1) 5/8" OD, (1) 5/8" OD, (1) 5/8" OD, (1) 5/8" OD, (1)

Cond. Model @105°F Amb. WCS-003B WCS-005B WCS-005B WCS-008B WCS-008B WCS-010B

Condenser Fan Data

CFM @ free discharge 4,450 3,900 3,900 8,640 8,640 7,780

Motor Hp, (Qty.) 1/3 Hp, (1) 1/3 Hp, (1) 1/3 Hp, (1) 1/3 Hp, (2) 1/3 Hp, (2) 1/3 Hp, (2)

Net Weight (lbs.) 107 116 116 164 164 179

Refrigerant Connections - Copper

Liquid Line, (Qty.) 5/8" OD, (1) 5/8" OD, (1) 5/8" OD, (1) 5/8" OD, (1) 5/8" OD, (1) 5/8" OD, (1)

Hot Gas Line, (Qty.) 5/8" OD, (1) 5/8" OD, (1) 5/8" OD, (1) 5/8" OD, (1) 5/8" OD, (1) 5/8" OD, (1)

Low Ambient Control

Std Minimum Oper. Amb. 0°F 0°F 0°F 0°F 0°F 0°F

Head Press. Method Fan Cycling Fan Cycling Fan Cycling Fan Cycling Fan Cycling Fan Cycling

Optional Min. Op. Amb -20°F or -20°F or -20°F or -20°F or -20°F or -20°F or -30°F -30°F -30°F -30°F -30°F -30°F

"CCU/D" Model CC( )-41-A CC( )-61-A CC( )-81-A CC( )-121-A CC( )-171-A CC( )-201-A

Filters - 1" deep (41/121) & 2" deep (171/201), 30% Average Efficiency, throwaway

Up-Flow (Free-Front Return):

Nom. Size (in.), (Qty.) 38x16, (1) 38x16, (1) 38x16, (1) 38x16, (1) 16x24, (2) 16x24, (2)

Down-Flow & Up-Flow (Rear Ducted Return):

Nom. Size (in.), (Qty.) 25x22, (1) 25x22, (1) 25x22, (1) 25x22, (1) 20x25, (2) 20x25, (2)

Connection Sizes - Copper, (Please refer to Mini-Space IOM Manual for proper interconnecting refrigerant line sizing.)

Refrigerant:

Liquid Line, (Qty.) 3/8" OD, (1) 3/8" OD, (1) 1/2" OD, (1) 1/2" OD, (1) 1/2" OD (1) 5/8" OD (1) Hot Gas Line, (Qty.) 1/2" OD, (1) 5/8" OD, (1) 5/8" OD, (1) 7/8" OD, (1) 7/8" OD (1) 7/8" OD (1)

Condensate Drain,(w/ pump) 7/8" OD 7/8" OD 7/8" OD 7/8" OD 7/8" OD(1/2” OD) 7/8" OD(1/2” OD)

Humidifier Inlet 1/4" OD 1/4" OD 1/4" OD 1/4" OD 1/4" OD 1/4" OD

Physical Data

Approx. Weight 410lbs 420lbs 430lbs 450lbs 480lbs 510lbs

Dimensions: (H"xW"xD"), includes access panels, w/o Plenum Box option.

CCU-( )-A(up-flow) 73"x24"x24" 73"x24"x24” 73"x24"x24” 73"x24"x24” 73”x39x’x32” 73”x39x’x32”

(26)

Performance Dat

a

- W

ater Cooled (1 to 7 T

on Systems)

Water Cooled -

1 to 7 Ton "CCU/D"

"CCU/D" Model CC( )-41-W CC( )-61-W CC( )-81-W CC( )-121-W CC( )-171-W CC( )-201-W

NET DX COOLING CAPACITY - BTU/H, (includes standard DX evaporator motor heat @ std CFM & e.s.p. ratings)

75°FDB/62.5°FWB, 50% RH Total 18,800 26,700 33,400 48,000 60,500 76,900 Sensible 16,900 22,700 29,300 40,800 57,500 72,300 72°FDB/60°FWB, 50% RH Total 18,200 24,900 32,100 44,100 57,600 73,900 Sensible 16,500 21,600 27,800 38,400 55,000 69,900 70°FDB/58.5°FWB, 50% RH Total 16,600 23,700 29,200 40,200 53,300 71,800 Sensible 15,200 20,700 25,800 35,900 51,300 68,200 75°FDB/61°FWB, 45% RH Total 18,800 26,300 33,400 46,600 58,700 75,500 Sensible 16,900 23,200 29,600 41,700 56,6600 72,800 72°FDB/58.5°FWB, 45% RH Total 18,200 23,000 29,600 40,700 56,600 72,100 Sensible 16,500 20,900 26,900 37,800 54,700 70,100 70°FDB/57°FWB, 45% RH Total 16,500 22,200 26,900 39,500 49,200 70,200 Sensible 15,100 20,200 25,100 36,700 48,200 68,500

Reheat/Heat - Performance Capacities Include Evaporator Blower Motor Heat

ELECTRIC REHEAT / HEAT - (Standard)

Htr Kw Rating (No. of Stages) 2 Kw (1-stg) 2 Kw (1-stg) 2 Kw (1-stg) 4 Kw (2-stg) 12 Kw (2-stg) 12 Kw (2-stg) Tot BTU/H (Kw) w/ Evap Mtr Ht: 8,730 (2.6) 8,730 (2.6) 8,730 (2.6) 15,560 (4.6) 48,580 (14.2) 48,580 (14.2)

HOT GAS REHEAT - (Optional)

BTU/H 12,060 12,245 21,505 21,685 35,340 38,525

HOT WATER REHEAT / HEAT - Reheat rated @ 180°F Entering Water Temperature, EAT = 72°F DB, (Optional)

BTU/H 31,465 31,465 63,475 63,475 114,450 124,902

GPM / Press. Drop (ft.wg) 3.2 / (.7) 3.2 / (.7) 6.5 / (.8) 6.5 / (.8) 11.7 / (2.4) 12.8 / (2.8)

Control 2way, 150 psig, Modulating (010 Vdc)

-Humidification - Electrode Steam Canister Humidifier with Adjustable Output, (Standard)

Lbs/Hr, (Kw Input) 2-5, (1.7) 2-5, (1.7) 2-5, (1.7) 2-5, (1.7) 4-10, (3.4) 4-10, (3.4)

Std Control Cycling Cycling Cycling Cycling Cycling Cycling

Evaporator Blower / Motor - DWDI Centrifugal

Horsepower 3/4 Hp 3/4 Hp 3/4 Hp 3/4 Hp 3.0 Hp 3.0 Hp

CFM @ ext. st. press. 1,180 @ 0.2" 1,180 @ 0.2" 1,180 @ 0.2" 1,890 @ 0.2" 3,450 @ 0.3" 4,130 @ 0.3"

Drive Method Direct Direct Direct Direct Belt Belt

Evaporator Coil - Aluminum Fin, Copper Tube

Rows/Face Area (ft2) 4/ 3.25 4/ 3.25 4/ 3.25 4/ 3.25 4/ 8.3 4/ 8.3

Face Velocity, fpm 363 363 363 581 415 498

Compressor - Heat pump duty rated Scroll - HCFC Ozone Safe R-22

Type, (Qty.) Scroll, (1) Scroll, (1) Scroll, (1) Scroll, (1) Scroll, (1) Scroll, (1)

References

Related documents

Hence, response time based approaches like (Lin et al. 2009) introduce a control loop using feedback about response times and the throughput as depicted in Figure 2.. A

operating power input/current: as above spec sheet, unit under the condition of dehumidification plus 100% electric reheat; (8) Down flow unit is required and may sink underneath

Explain the terms and concepts used when working with hot-water heating and chilled-water cooling systems5. Identify the major components of hot-water heating, chilled-water

Secondary Pumps Primary Hot/Chilled Water Pump Secondary Hot/Chilled Water Pump Boilers or Chillers Automatic valves at each coil control the flow of water to the coil. Variable flow

Systems are variable volume heating cooling and ventilating air handling unit with chilled water cooling coil, floating dry bulb economizer steam VIFB preheat coil, humidifier,

A este respecto, se demostró que el aumento de la accesibilidad en las ciudades de Japón, por la implantación de nuevas líneas ferroviarias de alta velocidad,

Which pillar of education is being strengthened by a teacher who provides learning opportunities for his/her students to develop their social skills and capacities to work with

•Pump station location / containment pool •Chilled water piping path / redundancy •Chilled water pump redundancy •Chilled water containment / drip pans •Provision for chilled