CENTUM VP
Installation
IM 33M01A20-40E
IM 33M01A20-40E
1st Editioni
IM 33M01A20-40E
Introduction
The procedure for installing the CENTUM VP function on a recommended personal computer and the setup are described in this document. Be sure to read it when installing the CENTUM VP system.
If a recommended personal computer is used and Windows must be installed or set up, refer to the Windows manual for the procedure. (Note that the loading of the CENTUM VP software is referred to as “installation” and the setting of Windows to run the CENTUM VP system on the personal computer as “setup” throughout this document.)
Chapter 1: Overview
This chapter provides the overview of the installation tasks. Chapter 2: Hardware Setup
This chapter describes the hardware settings that should be carried out before installing the software.
Chapter 3: Setting of Windows
This chapter describes the Windows settings need to be performed before installing CENTUM VP software to the PC.
Chapter 4: Setting of Network
This chapter describes the Windows network setups after installing the communication drivers. Chapter 5: Installing USB driver for Operator Keyboard (OPKB)
This chapter describes the procedure for installing the USB driver for Operator Keyboard (OPKB).
Chapter 6: Installing CENTUM VP Software
This chapter describes the procedure for installing CENTUM VP Software. Chapter 7: IT Security Settings
This chapter describes the settings regarding the IT security strengthening after installing the software.
Chapter 8: Setups Required after Installation
This chapter describes the settings need to be performed after installing CENTUM VP. Chapter 9: Console Type HIS Installation
This chapter describes the procedure for installing Console Type HIS. Chapter 10: Uninstallation of CENTUM VP
This chapter describes the procedures for uninstalling the CENTUM VP software and device drivers.
Chapter 11: Setting of Windows Domain Environment
The required settings when CENTUM VP acts with Windows domain environment will be explained in this chapter.
Chapter 12: Troubleshooting
This chapter describes the troubleshooting methods for various troubles. Chapter 13: Backup
This chapter describes how to backup the system regularly as a precaution against unexpected troubles.
1st Edition : Mar.23,2008-00
ii
IM 33M01A20-40E
CENTUM VP Document Map
HIS Operation IM 33M05D10-40E Engineering Test Guide IM 33M10D20-40E Operating Messages IM 33M05D20-40E Reference IM 33M01A30-40E APCS Documentation Engineering Tutorial IM 33M10D10-40E User's manual
Only available in electronic document Relationship between manuals that must be read in order Relationship to a referred manual Reference manual
Engineering
Operation and
Monitoring
Hardware
Installation
Communication Devices IM 33M50D10-40E Turbomachinery I/O Modules IM 33M10U10-40EInput & Output Modules IM 33M50G10-40E Field Control Stations IM 33M50E40-40E CENTUM VP Installation IM 33M01A20-40E Peripherals IM 33M50C10-40E CENTUM VP Engineering Guidance Fieldbus Documentation CENTUM Data Access Library IM 33M05F10-40E Migrated-FCS (FIO) IM33M50W10-40E Vnet/IP IM33L01A10-40E 1st Edition : Mar.23,2008-00
iii
Safety Precautions
n
Safety, Protection, and Modification of the Product
• In order to protect the system controlled by the product and the product itself and ensure safe operation, observe the safety precautions described in this user’s manual. We assume no liability for safety if users fail to observe these instructions when operating the product. • If this instrument is used in a manner not specified in this user’s manual, the protection
provided by this instrument may be impaired.
• If any protection or safety circuit is required for the system controlled by the product or for the product itself, prepare it separately.
• Be sure to use the spare parts approved by Yokogawa Electric Corporation (hereafter simply referred to as YOKOGAWA) when replacing parts or consumables.
• Modification of the product is strictly prohibited.
• The following symbols are used in the product and user’s manual to indicate that there are precautions for safety:
Indicates that caution is required for operation. This symbol is placed on the product to refer the user to the user’s manual in order to protect the operator and the equipment. In the user’s manuals you will find precautions to avoid physical injury or death of the operator, including electrical shocks.
Identifies a protective grounding terminal. Before using the product, ground the terminal. Identifies a functional grounding terminal. Before using the product, ground the terminal. Indicates an AC supply.
Indicates a DC supply.
Indicates that the main switch is ON. Indicates that the main switch is OFF.
iv
IM 33M01A20-40E
n
Notes on Handling User’s Manuals
• Please hand over the user’s manuals to your end users so that they can keep the user’s manuals on hand for convenient reference.
• Please read the information thoroughly before using the product.
• The purpose of these user’s manuals is not to warrant that the product is well suited to any particular purpose but rather to describe the functional details of the product.
• YOKOGAWA reserves the right to make improvements in the user’s manuals and product at any time, without notice or obligation.
• If you have any questions, or you find mistakes or omissions in the user’s manuals, please contact our sales representative or your local distributor.
n
Warning and Disclaimer
The product is provided on an “as is” basis. YOKOGAWA shall have neither liability nor
responsibility to any person or entity with respect to any direct or indirect loss or damage arising from using the product or any defect of the product that YOKOGAWA can not predict in advance.
n
Notes on Software
• YOKOGAWA makes no warranties, either expressed or implied, with respect to the
software’s merchantability or suitability for any particular purpose, except as specified in the terms of warranty.
• This product may be used on a machine only. If you need to use the product on another machine, you must purchase another product.
• It is strictly prohibited to reproduce the product except for the purpose of backup. • Store the DVD-ROM (the original medium) in a safe place.
• It is strictly prohibited to perform any reverse-engineering operation, such as reverse compilation or reverse assembling on the product.
• No part of the product may be transferred, converted or sublet for use by any third party, without prior written consent from YOKOGAWA.
v
Documentation Conventions
n
Typographical Conventions
The following typographical conventions are used throughout the user’s manuals:
l
Commonly used conventions throughout user’s manuals:
Character string to be entered:
The characters that must be entered are shown in monospace font as follows: Example:
FIC100.SV=50.0
“▼” Mark
This symbol indicates the description for an item for which you should make a setting in the product’s engineering window.
While operating an engineering window, the help information for the selected item can be accessed from “Builder Definition Items” in the Help menu. Listing more than one definition item after this symbol implies that the paragraph on the page describes more than one definition item. Example: ▼ Tag Name, Station Name
“Δ” Mark
Indicates a space between character strings that must be entered. Example:
. ALΔPIC010Δ-SC
Character string enclosed by brackets ({ }):
Indicates an option that can be omitted.Example:
vi
IM 33M01A20-40E
l
Conventions used to show key or button operations:
Characters enclosed by brackets ([ ]):
Characters enclosed by brackets within any description on a key or button operation, indicate either a key on the HIS (Human Interface Station) keyboard, a key on the operation keyboard, a button name on a window, or an item displayed on a window.
Example:
To alter the function, press the [ESC] key.
l
Conventions used in command syntax or program statements:
The following conventions are used within a command syntax or program statement format:
Characters enclosed by angle-brackets:
Indicate character strings that user can specify freely according to certain guidelines. Example:
#define <Identifier><Character string>
“...” Mark
Indicates that the previous command or argument may be repeated. Example:
Imax (arg1, arg2, ...)
Characters enclosed by brackets ([ ]):
Indicate those character strings that can be omitted. Example:sysalarm format_string [output_value ...]
Characters enclosed by separators (| |):
Indicate those character strings that can be selected from more than one option. Example:
opeguide <format_character_string> [, <output_value> ...] OG,<element number>
vii
n
Symbol Marks
Throughout this user’s manual, you will find several different types of symbols are used to identify different sections of text. This section describes these icons.
CAUTION
Identifies instructions that must be observed in order to avoid physical injury and electric shock or death of the operator.
WARNING
Identifies instructions that must be observed in order to prevent the software or hardware from being damaged or the system from becoming faulty.
IMPORTANT
Identifies important information required to understand operations or functions.TIP
Identifies additional information. SEE ALSO Identifies a source to be referred to.Clicking a reference displayed in green can call up its source, while clicking a reference displayed in black cannot.
n
Drawing Conventions
Some drawings may be partially emphasized, simplified, or omitted, for the convenience of description.
Some screen images depicted in the user’s manual may have different display positions or character types (e.g., the upper / lower case). Also note that some of the images contained in this user’s manual are display examples.
viii
IM 33M01A20-40E 1st Edition : Mar.23,2008-00
Copyright and Trademark Notices
n
All Rights Reserved
The copyright of the programs and online manuals contained in the DVD-ROM or CD-ROM shall remain in Yokogawa.
You are allowed to print out the required pages of the online manuals for using the product, however, you are not allowed to print out the entire document. You can purchase the printed manual from Yokogawa.
Except as stated above, no part of the online manual may be reproduced, either in electronic or written form, registered, recorded, transferred, sold or distributed (in any manner including without limitation, in the forms of paper documents, electronic media, films or transmission via the network).
n
Trademark Acknowledgments
• CENTUM and Vnet/IP are registered trademarks of YOKOGAWA.
• Microsoft, Windows, Windows Vista, Visual Basic, Visual C++ and Visual Studio are either registered trademarks or trademarks of Microsoft Corporation in the United States and/or other countries.
• Adobe, Acrobat and Acrobat Reader are either registered trademarks or trademarks of Adobe Systems Incorporated in the United States and/or other countries.
• Ethernet is a registered trademark of XEROX Corporation. • Java is a registered trademark of Sun Microsystems,Inc.
• MELSEC is a registered trademark of Mitsubishi Electric Corporation. • Modicon and Modbus are registered trademarks of Schneider Electric SA. • Memocon-SC is a registered trademark of Yaskawa Electric Corporation. • PLC is a registered trademark of Rockwell Automation, Inc.
• SYSMAC is a registered trademark of OMRON Corporation.
• SIEMENS and SIMATIC are registered trademarks of Siemens Industrial Automation Ltd. • “FOUNDATION” in “FOUNDATION fieldbus” is a registered trademark of Fieldbus
Foundation.
• SmartPlant is a registered trademark of Intergraph Corporation.
• “HART” is a registered trademark of the HART Communication Foundation.
• All other company and product names mentioned in this user’s manual are trademarks or registered trademarks of their respective companies.
• We do not use TM or ® mark to indicate those trademarks or registered trademarks in this user’s manual.
Toc-1
CENTUM VP
Installation
CONTENTS
IM 33M01A20-40E 1st Edition1.
Overview ... 1-1
1.1 Flow Chart of Installation Procedures ...1-3 1.2 Hardware Environment ...1-7 1.3 Software Environment ...1-82.
Hardware Setup ... 2-1
2.1 Control Bus Station Address ...2-2 2.2 Processor Unit ...2-5 2.3 Bus Converter ...2-8 2.4 HF Bus/RL Bus Interface Card...2-9 2.5 V net Interface Card ... 2-11 2.6 Communication Gateway Unit ...2-13 2.7 Installing Ethernet Card ...2-16 2.8 Setup Vnet/IP Station Address On Control Bus ...2-17 2.9 Setup Vnet/IP Station Address On Processor Module ...2-20 2.10 Setup V net Router Addresses ...2-233.
Setting of Windows ... 3-1
3.1 File System ...3-2 3.2 Setting of Virtual Memory ...3-3 3.3 Set Display Properties ...3-5 3.4 Setting of System Properties ... 3-11 3.5 Setting a Power Options ...3-13 3.6 Disable Windows Sidebar ...3-19 3.7 Disable Windows Security Alerts ...3-20 3.8 Disabling Windows Defender ...3-233.9 Notices on Installing CENTUM VP in Windows XP Environment ...3-26
3.10 Disable Scheduled Disk Defragmenter Tool ...3-27 3.11 Cautions on Using CAMS for HIS ...3-28
4.
Setting of Network ... 4-1
4.1 Installation of Control Bus Driver...4-2
4.1.1 Adding Control Bus Driver ...4-3 4.1.2 Updating Control Bus Driver ... 4-11 4.1.3 Removing Control Bus Driver ...4-15 4.1.4 Troubleshooting ...4-17
Toc-2
IM 33M01A20-40E 1st Edition : Mar.23,2008-00
4.2 Installation of Vnet/IP Open Communication Driver ...4-21
4.2.1 Adding Vnet/IP Open Communication Driver ...4-22 4.2.2 Updating Vnet/IP Open Communication Driver ...4-27 4.2.3 Removing Vnet/IP Open Communication Driver ...4-30 4.2.4 Troubleshooting of Vnet/IP Open Communication
Driver Installation ...4-33
4.3 Setup Windows Network Connection ...4-37
4.3.1 Setting Network Connection - Windows Vista ...4-38 4.3.2 Setting Network Connection -
Windows XP/Windows Server 2003 ...4-55 4.3.3 Restrictions on Network Setting ...4-66 4.3.4 Advanced Setup of Windows Network ...4-68
5.
Installing USB driver for Operator Keyboard (OPKB) ... 5-1
6.
Installing CENTUM VP Software ... 6-1
6.1 New Installation ...6-3
6.2 Version Up Installation (from CS 3000 to CENTUM VP) ...6-12
6.2.1 Procedure for Version Up Installation ...6-13 6.2.2 Backup and Restoration of Package Data ...6-19
6.3 Revision Up Installation ...6-25
6.3.1 Procedures for Revision Up Installation ...6-26
6.4 Upgrade Installation from CS 1000 to CENTUM VP ...6-27
6.4.1 Procedures for Upgrading CS 1000 to CENTUM VP ...6-29 6.4.2 Backup and Restoration of Package Data of CS 1000 ...6-30 6.4.3 Migrate from CS 1000 to CENTUM VP ...6-34
6.5 Add Installation ...6-41 6.6 Re-Installation ...6-45
7.
IT Security Settings ... 7-1
7.1 Security Setting Utility ...7-2 7.2 Using Security Setting Utility ...7-8 7.3 Notes on Security Setting ...7-15
7.3.1 Notes on Starting Operation and Monitoring Functions
and Test Functions by Administrative User ...7-16 7.3.2 Security Setting Any CS 3000 R3 HIS is in the System ...7-17 7.3.3 Security Settings when Multiple Projects are Connected ...7-21 7.3.4 Accessing Builder-Related Database for Reference via Network ...7-22 7.3.5 Setting Security related to SOE Server Package (LPC6900) ...7-25 7.3.6 Security Setting for Connection via OPC Interface ...7-26 7.3.7 Succeeding the Security Setting at Reinstallation ...7-27 7.3.8 Security Setting when Additional Package has been Installed ...7-28
7.4 Security Setting Required for Connection with Other Systems ...7-29
8.
Setups Required after Installation ... 8-1
8.1 Setting of Windows ...8-2
Toc-3
8.1.2 Setting of Windows Operating Environment ...8-8 8.1.3 Using OPC Function via Network ...8-108.2 Setting of UPS (Uninterruptible Power Supply) ...8-12
8.2.1 Command for UPS Management of CENTUM VP ...8-13 8.2.2 Setting Example when Using Windows Standard UPS Software ...8-16
8.3 Specific Settings of Package ...8-21
8.3.1 Automatically Start HIS Functions ...8-21 8.3.2 Report Package ...8-23 8.3.3 Settings for Using the Line Printer Support Function ...8-25 8.3.4 Change of the Monitoring-Target Control Station ...8-27 8.3.5 Setting Remote Operation and Monitoring Server ...8-28 8.3.6 Cautions on Setting a HIS IP Address Other Than the Default ...8-29 8.3.7 Setting of CAMS for HIS ...8-30 8.3.8 Setting Single Control Bus on CENTUM VP Entry Class ...8-32 8.3.9 Not Using Ethernet on CENTUM VP Entry Class ...8-33 8.3.10 Setting SOE Server Package ...8-36
8.4 Setup of Server for Remote Operation and Monitoring Function ...8-37
8.4.1 Setup Servers ...8-39
9.
Console Type HIS Installation ... 9-1
9.1 Installations for Console Type HIS ...9-2 9.2 Installation of RS-232C Driver ...9-4
10. Uninstallation of CENTUM VP ... 10-1
10.1 Release the setting for HIS Auto Start, Automatic Logon
and CENTUM Desktop ...10-2 10.2 Restore the various settings for Windows ...10-4
10.2.1 Show Account Icon in Logon display ...10-4 10.2.2 Enabled Fast User Switching ...10-7 10.2.3 Enabled Windows Sidebar ...10-10 10.2.4 Enabled Seucurity Center Alert ... 10-11 10.2.5 Enabled Windows Update ...10-14 10.2.6 Enabled Windows Defender ...10-17
10.3 Uninstallation of CENTUM VP Software ...10-18 10.4 Uninstallation of Device Driver ...10-23
10.4.1 Uninstallation of Control bus driver ...10-23 10.4.2 Uninstallation of USB driver for OPKB ...10-23 10.4.3 Uninstallation of Vnet/IP Open Communication driver ...10-23
11. Setting of Windows domain environment ... 11-1
11.1 Configuring Domain controller ... 11-2 11.2 Adding of Domain User and Group... 11-12 11.3 Incorporate the Client PC in the domain ... 11-2312. Troubleshooting ... 12-1
13. Backup ... 13-1
<1. Overview>
1-1
1.
Overview
In this document, the procedure for installing the CENTUM VP software (including the electronic documents) will be explained. The installation procedures of Windows operating systems, related service packs and Microsoft security patches are beyond the scope of this document.n
Chapters and Sections to Read
You may read different chapters according to what you need for installation, such as procedures, settings and so on.
Below, a simple guidance may direct you to directly find the proper chapters or sections according to what you want to do.
•Console type HIS Installation : Chapter 9 •Installation to Console type HIS : Section 9.1 •Installation of RS-232C driver : Section 9.2
•Hardware Setup : Chapter 2
•Uninstallation of CENTUM VP : Chapter 10 •Troubleshooting : Chapter 12
•Backup : Chapter 13 •Setting of Windows : Chapter 3
•Setting of Network (and Installing Drivers) : Chapter 4
•IT Setting Security : Chapter 7
•Activities after the installation : Chapter 8 Chapter 1
•Installation of USB driver for Operator Keyboard (OPKB) : Chapter 5
•Setting of Windows domain environment : Chapter 11 For Installation
Must Read
For Various Setups • Installation of CENTUM VP Software : Chapter 6
•New Installation : Section 6.1
•Version Up Installation (from CS 3000 to CENTUM VP) : Section 6.2
•Revision Up Installation : Section 6.3 •Upgrade Installation from CS 1000 to CENTUM VP : Section 6.4
•Add Installation : Section 6.5 •Re-Installatiton : Section 6.6
For Environment Setup
Read when Needed
010001E.ai
For Installing Console Type HIS
Figure Chapters and Sections to Read
n
Administrative User
For the initial logon of Windows Vista, no account of administrative user can be used to logon. In this case, the administrative user account created during the installation of Windows Vista should be used.
The account for the administrative user of Windows XP and Windows Server 2003 are the Administrator account.
In this document, the users that have the administrator privileges in various Windows operating systems are all referred to as the administrative users. The user who is installing the CENTUM VP will be one of the administrative users.
<1. Overview>
1-2
IM 33M01A20-40E
When the standard IT security model is defined after installing CENTUM VP, the accesses to the CENTUM VP related folders will be restricted. From then on, the installation needs to be continued by an administrative user that belongs to CTM_MAINTENANCE group (a user group for maintennance). However, the administrative user that performed the previous installation will be automatically registered to the CTM_MAINTENANCE group.
SEE ALSO For more information about setups of IT security, see the following:
7, “IT Setting Security”
n
Installation Procedures
The procedure for installing Windows and setup device drivers vary with the Windows operating systems. For the procedure that common for all the operating systems, the explanation will mainly use the user interfaces of Windows Vista. However, for the procedures typical for each operating system, the explanation will use the user interfaces of each system and describe the procedure separately.
<1.1 Flow Chart of Installation Procedures>
1-3
1.1
Flow Chart of Installation Procedures
The basic procedure for installing the CENTUM VP to a PC as a new installation is illustrated below. After the version upgrade installation (upgraded from CS 3000 to CENTUM VP or upgraded from CS 1000 to CENTUM VP), the procedures described in “Setting of IT security” and “Setting after the installation” also need to be performed. The procedures for installing Windows and Windows service packs are beyond the scope of this document. SEEALSO • For more information about installation of Windows, Windows service packs and security patches, see the
related documents provided by Microsoft Corporation.
• For more information about Installation of Console type HIS, see the following:
9, “Console type HIS Installation”
START Installation of Windows Installation of Windows service pack Installation of Windows Security patch Setting of Network (V net and Ethernet, etc.)
Installation of CENTUM VP Software (and Electronic
Documents) Setting of IT security Setting after the installation (Create user account, Setup
Windows environment for that user and setup UPS)
END
Refer to “3. Setting of Windows”
Refer to “5. Installation of USB driver for
Refer to “6. Installation of CENTUM VP Software”
Refer to “7. Setting of IT Security”
Refer to “8. Activities after the installation” Refer to “4. Setting of Network”
This step is not necessary if Windows is already installed on the PC
This step is not necessary if the Windows service pack is already installed on the PC
Setting of Windows (Display and Power
management etc.) Setting of Windows (Display and Power management etc.) 010101E.ai Refer the documents provided by Microsoft Figure Flow Chart of Installation Procedures
<1.1 Flow Chart of Installation Procedures>
1-4
IM 33M01A20-40E
n
Procedure of CENTUM VP Installation
When installing CENTUM VP, the installation menu included in the CENTUM VP software media (DVD-ROM) should be used.
l
CENTUM VP Installation Menu
After setting the CENTUM VP software media to the DVD-ROM drive, the installation menu will be automatically started. If the installation menu is not automatically started, you can use Windows Explorer to find CENTUMSetup.exe program under the top folder of the CENTUM VP software media and double click the program to run it.
010103E.ai
Figure Installation Menu
l
CENTUM VP Installation Menu Items
On the CENTUM VP installation menu, the buttons (installation tasks) are as follows:
Table CENTUM VP Installation Menu Buttons
Button (Installation Task) Description Reference
010102E.ai
6.1 New Installation 7. IT Setting Security
4.1 Installation of Control Bus Driver 4.2 Installation of Vnet/IP Open Communication Driver
5. Installation of USB driver for Operator Keyboard (OPKB) 9.2 Installation of RS-232C Driver Run new installation.
Set IT security settings. Install control bus driver
Install Vnet/IP open communication driver Install USB driver for operator keyboard (OPKB) Install RS-232C driver for console type HIS CENTUM VP Software
Setting IT Security Control Bus Driver Vnet/IP Open com driver USB driver for OPKB RS driver for Console HIS CS 1000 Project DB
conversion Upgrade CS 1000 project database to CENTUM VP. 6.4 Installation for Upgrading CS 1000 to CENTUM VP
<1.1 Flow Chart of Installation Procedures>
1-5
n
Information Required for Setup
The following information is required for the setup:
l
Computer Name/Station Name
IMPORTANT
Make sure to match the names of a computer and a station. If they do not match, we cannot guarantee the proper performance of the CENTUM VP system.
A computer name is a name used to identify each computer on the Windows network. An arbitrary computer name can be specified using the Windows Control Panel.
A station name is a name uniquely specified according to the Control bus address in the CENTUM VP system.
EXAMPLE: HIS0164
(HISddss: “dd” is the domain number and “ss” is the station number.)
l
IP Address
This is the address of the computer which can uniquely be identified by the Control bus or Ethernet.
Make sure to specify network addresses for the Control bus and Ethernet on separate subnets. EXAMPLES: 172.16.1.64 (Control Bus), 172.17.1.64 (Ethernet)
SEE
ALSO If an error occurs when IP address of an HIS is changed and downloaded, see the following:
“n If an error occurs when IP address of an HIS is changed and downloaded” in 12, “Troubleshooting”
IMPORTANT
• Even if no control bus interface card is installed, installed the control bus driver before using the Test Function.
• If using the Expanded Test Functions, be sure not to duplicate the control bus address that needs to be set for each connected PC.
The IP addresses set for control bus adapters should be the same control bus addresses set on System View for the PCs.
Example: 172.16.dd.ss
The IP addresses for different PCs should not be identical.
Note that the address can be the same as “domain number.station number” used for the HIS, but that the address should not be the same as “domain number.station number” used for the FCS. Set from 1 to 16 for the domain number.
<1.1 Flow Chart of Installation Procedures>
1-6
IM 33M01A20-40En
Subnet Mask
This information specifies a network or computer on Ethernet in combination with the IP address. EXAMPLE: 255.255.0.0IMPORTANT
Note the following items regarding to the subnet mask:
• Use the exist setting of the current network environment when installing the CENTUM VP system in an existing network environment.
• Use the default value determined by the IP address when installing the CENTUM VP system in a newly provided local network environment.(IP address: 172.17.dd.ss, subnet mask: 255.255.0.0).
Use the default IP address for the Control Bus (IP address: 172.16.dd.ss, subnet mask: 255.255.0.0).
l
Password of Administrative User
Get ready the password of the administrative user of the PC.
l
Preparations when User Account and User Group are Managed in Windows
Domain Controller.
SEE ALSO For more information about the preparations when user account and user group are managed in Windows
domain controller., see the following:
11, “Setting of Windows domain environment”
<1.2 Hardware Environment>
1-7
1.2
Hardware Environment
Regarding the information about the hardware environment of HIS, builders, GSGW, SIOS and other various subsystems, see the related GS documents.
SEE
ALSO • For information about Hardware Environment of HIS and Builder, see the following:
Model LHS1100, LHM1101 Standard Operation and Monitoring Function (GS 33M05D10-40E) Model LHS5100, LHM5100 Standard Builder Function (GS 33M10D10-40E)
• For information about Hardware Environment of GSGW, see the following:
Model LFS1250 GSGW Generic Subsystem Gateway Package (GS 33M20F10-40E)
• For information about Hardware Environment of SIOS, see the following:
<1.3 Software Environment>
1-8
IM 33M01A20-40E
1.3
Software Environment
This Section describes Software Environment.
n
Software Operating Environment
Support target OS below.• Windows Vista Business Edition Service Pack 1 • Windows XP Professional Service Pack 2 • Windows Server 2003 Service Pack 2 • Windows Server 2003 R2 Service Pack 2 64-bit OS is not supported.
IMPORTANT
In the PC that Windows is preinstalled; some third party utilities other than the operating systems might have been installed too. These utilities may not only unnecessarily occupy the HIS
resource, but also jeopardize the HIS performance. Thus, it is recommended to reinstall the OS only to the PC.
In the PC recommended by Yokogawa, the required software applications are all properly setup.
l
Software Compatibility
The CENTUM VP software is compatible with the commercial software listed below:
Table Compatible Commercial Software
Software type Software name Version Remarks
010301E.ai
Used with the report package, and Settings for FCS Data Setting/Acquisition Package (PICOT).
Used with the report package, and Settings for FCS Data Setting/Acquisition Package (PICOT).
Used with the electronic document package. Microsoft Excel (*1) 2003, 2007 6.0+SP5 2005 2003, 2007 6.0, 7.0 3.0 11.0 8.5i 7.0.5 Microsoft Word Microsoft Visual C++ Visual Studio
Microsoft Internet Explorer .NET Framework
APC PowerChute Business Edition Spreadsheet
Word processing Software development Document reader Uninterruptible power supply (UPS) Anti-virus
Others Adobe Reader
McAfee VirusScan Enterprise Symantec Endpoint Protection
Adobe Acrobat
8.1.2, 7.0 8.1, 7.0
Note: SP stands for service pack.
*1: [Visual Basic for Applications] and [Digital Certificate for VBA projects] of [Office Shared Features] need to be installed.
<1.3 Software Environment>
1-9
l
Revision Numbers of Report Package and Microsoft Excel
When using Report package, the different version of Microsoft Office may affect the functions of report package.
SEE
ALSO For more information about the report package revisions, see the following and check the release numbers of the
Microsoft products:
Table “Compatible Commercial Software”
When generating the report applications in different PCs, the versions of Microsoft Excel should be the same.
SEE
ALSO For the procedure of using the report files generated in the old version of Microsoft Excel in the new version of
Microsoft Excel, see the following:
<2. Hardware Setup>
2-1
2.
Hardware Setup
This Chapter describes how to setup the hardware before the CENTUM VP software installation. It is necessary to set domain and station numbers for the following switches before installing the software: • Control Bus interface card (VF701) • HF bus/RL bus interface card (FC311) • Field control station processor unit • Bus Converter (ABC11D, ABC11S) • Communication Gateway Unit (ACG10S) If you do not use the Bus Converter and Communication Gateway Unit, you do not need to set these items. TIP When the domain number and station number are correctly defined and a Control Bus is properly connected, theSND and RCV lamps turn on at power-on.
If the RCV lamp turns on while the SND lamp does not, check the dip switch setting of the corresponding card. Specifically, before installation, be sure that the control bus interface card for the PC is correctly set.
Before installing software, reconfirm that these settings are correct. Check that the Ethernet card are properly installed in a PC.
CAUTION
When removing the cards for setting dipswitches, the damages caused by static electricity should be prevented.
SEE
ALSO For more information about prevention of static electricity, see the following:
<2.1 Control Bus Station Address>
2-2
IM 33M01A20-40E2.1
Control Bus Station Address
The Control Bus interface card (VF701) has DIP switches and they must be set properly before installation of the CENTUM VP software:n
Locations of DIP switches on VF701
The DIP switches are used to set the domain number and the station number. They are located on the printed circuit board of the VF701 as illustrated below. The Control Bus station address is determined by the combination of the settings of these two DIP switches.
020101E.ai DIP switches Station number Domain number DOMAIN STATION SW1 DOM SW2 STN Figure VF701 DIP switches 1st Edition : Mar.23,2008-00
<2.1 Control Bus Station Address>
2-3
The domain and station numbers can be set or changed as described below:
n
Setting the Domain Number for VF701
One Control Bus system requires one domain number.
The domain number can be set in a range of 1 to 16 by turning the domain number DIP switch bits as shown below. Bits 2 and 3 must always be 0.
020102E.ai 1 0 DOMAIN NO. (MSB)(LSB) P 0 0 2 1 3 4 5 6 7 8
P (odd parity): Set in such a way that, of the 8 dip switches,
the sum of those switches set to 1 becomes an odd number.
MSB: Most Significant Bit
LSB: Least Significant Bit
Domain number (5 bits) Fixed to 0 (2 bits)
Parity of the domain number (1 bit) (odd parity)
Figure Domain Number Setting DIP switch
Table Domain Numbers & DIP switch Bit Positions
020103E.ai
1 2 DIP switch bit number3 4 5 6 7 8
0 0 0 0 0 0 0 1 0 0 0 0 0 0 1 0 1 0 0 0 0 0 1 1 0 0 0 0 0 1 0 0 1 0 0 0 0 1 0 1 1 0 0 0 0 1 1 0 0 0 0 0 0 1 1 1 0 0 0 0 1 0 0 0 1 0 0 0 1 0 0 1 1 0 0 0 1 0 1 0 0 0 0 0 1 0 1 1 1 0 0 0 1 1 0 0 0 0 0 0 1 1 0 1 0 0 0 0 1 1 1 0 1 0 0 0 1 1 1 1 Domain number 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 0 0 0 1 0 0 0 0 Bit setting: 0: Turn the switch to the lower in the above figure. 1: Turn the switch to the upper in the above figure.
<2.1 Control Bus Station Address>
2-4
IM 33M01A20-40E
n
Setting the Station Number for VF701
The station number can be set in a range of 1 to 64 by turning the station number DIP switch bits as shown below. Be Sure to set from No.64.
020104E.ai 1 0 2 1 3 4 5 6 7 8 P STATION NO. (MSB) (LSB)
P (odd parity): Set in such a way that, of the 8 dip switches,
the sum of those switches set to 1 becomes an odd number.
MSB: Most Significant Bit
LSB: Least Significant Bit
Station number (7 bits)
Parity of the station number (1 bits) (odd parity) Figure Station Number Setting DIP switch Table Station Numbers & DIP switch Bit Positions 020105E.ai Station number 1 1 2 3 4 5 6 7 8
DIP switch bit number
0 0 0 0 0 0 0 1 2 0 0 0 0 0 0 1 0 3 1 0 0 0 0 0 1 1 4 0 0 0 0 0 1 0 0 5 1 0 0 0 0 1 0 1 6 1 0 0 0 0 1 1 0 7 0 0 0 0 0 1 1 1 8 0 0 0 0 1 0 0 0 9 1 0 0 0 1 0 0 1 10 1 0 0 0 1 0 1 0 11 0 0 0 0 1 0 1 1 12 1 0 0 0 1 1 0 0 13 0 0 0 0 1 1 0 1 14 0 0 0 0 1 1 1 0 15 1 0 0 0 1 1 1 1 16 0 0 0 1 0 0 0 0 17 1 0 0 1 0 0 0 1 18 1 0 0 1 0 0 1 0 19 0 0 0 1 0 0 1 1 20 1 0 0 1 0 1 0 0 21 0 0 0 1 0 1 0 1 Station number 22 1 2 3 4 5 6 7 8
DIP switch bit number
0 0 0 1 0 1 1 0 23 1 0 0 1 0 1 1 1 24 1 0 0 1 1 0 0 0 ... ... ... ... ... ... ... ... 30 1 0 0 1 1 1 1 0 31 0 0 0 1 1 1 1 1 32 0 0 1 0 0 0 0 0 33 1 0 1 0 0 0 0 1 25 0 0 0 1 1 0 0 1 26 0 0 0 1 1 0 1 0 27 1 0 0 1 1 0 1 1 28 0 0 0 1 1 1 0 0 29 1 0 0 1 1 1 0 1 60 1 0 1 1 1 1 0 0 61 0 0 1 1 1 1 0 1 62 0 0 1 1 1 1 1 0 63 1 0 1 1 1 1 1 1 64 0 1 0 0 0 0 0 0 Bit setting: 0: Turn the switch to the lower in the above figure. 1: Turn the switch to the upper in the above figure. 1st Edition : Mar.23,2008-00
<2.2 Processor Unit>
2-5
2.2
Processor Unit
There are two types of processor unit. The processor unit is installed in a field control station and used for control computation: • CP703 • CP345 Their DIP switches must properly be set as described below. There is no difference between the two types of processor unit for the setting.n
Locations of DIP switches on Processor Unit
HRDY RDY CTRL COPY CN1 START /STOP STATION ADDRESS 0 1 PARTY 0 1 PARTY 020201E.ai CN1 connectorUsed for setting the domain number
Dip switches used for setting the station address
Used for setting the station number
NOTE : The CN1 connector is used only for maintenance.
<2.2 Processor Unit>
2-6
IM 33M01A20-40E
n
Setting the Domain Number
One Control Bus system requires one domain number.
The domain number can be set in a range of 1 to 16 by turning the domain number DIP switch bits as shown below. Bits 2 and 3 must always be 0.
020202E.ai 0 1 (MSB) DOM No. (LSB)
Parity of the domain number (1 bit) (odd parity) Fixed to 0 (2 bits)
Domain number (5 bits)
MSB: Most Significant Bit (highest-order bit) LSB: Least Significant Bit (lowest-order bit)
ODD PARITY 0 0 Figure Domain Number Setting DIP switch Table Domain Numbers & DIP switch Bit Positions Domain number 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 Bit 1 0 0 1 0 1 1 0 0 1 1 0 1 0 0 1 0 Bit 2 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Bit 3 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Bit 4 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1 Bit 5 0 0 0 0 0 0 0 1 1 1 1 1 1 1 1 0 Bit 6 0 0 0 1 1 1 1 0 0 0 0 1 1 1 1 0 Bit 7 0 1 1 0 0 1 1 0 0 1 1 0 0 1 1 0 Bit 8 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 020203E.ai Bit setting: 0: Turn the switch to the left in the above figure. 1: Turn the switch to the right in the above figure. 1st Edition : Mar.23,2008-00
<2.2 Processor Unit>
2-7
n
Setting the Station Number
Set station numbers in a range of 1 to 64 successively by turning the station number DIP switch bits as shown below:
020204E.ai 0 1 (MSB) STA No. (LSB)
MSB: Most Significant Bit (highest-order bit) LSB: Least Significant Bit (lowest-order bit)
Station number parity (1-bit) (odd parity)
Station number (7-bit) ODD PARITY Figure Station Number Setting DIP switch Table Station Numbers & DIP switch Bit Positions Station number 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 Bit 1 0 0 1 0 1 1 0 0 1 1 0 1 0 0 1 0 Bit 2 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Bit 3 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Bit 4 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1 Bit 5 0 0 0 0 0 0 0 1 1 1 1 1 1 1 1 0 Bit 6 0 0 0 1 1 1 1 0 0 0 0 1 1 1 1 0 Bit 7 0 1 1 0 0 1 1 0 0 1 1 0 0 1 1 0 Bit 8 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 Station number 17 18 30 31 32 33 60 61 62 63 64 Bit 1 1 1
--1 0 0 1
--1 0 0 1 0 Bit 2 0 0 0 0 0 0 0 0 0 0 1 Bit 3 0 0 0 0 1 1 1 1 1 1 0 Bit 4 1 1 1 1 0 0 1 1 1 1 0 Bit 5 0 0 1 1 0 0 1 1 1 1 0 Bit 6 0 0 1 1 0 0 1 1 1 1 0 Bit 7 0 1 1 1 0 0 0 0 1 1 0 Bit 8 1 0 0 1 0 1 0 1 0 1 0 020205E.ai Bit setting: 0: Turn the switch to the left in the above figure. 1: Turn the switch to the right in the above figure.
<2.3 Bus Converter>
2-8
IM 33M01A20-40E2.3
Bus Converter
This section discribes setting dipswitches on the processor card of ABC11D.n
Location of DIP Switches on Bus Converter
RDY CTRL COPY START /STOP CN1 V Net ADDRESS 0 1 0 1 ODD PARTY ODD PARTY 0 0 MSB MSB DOMAIN No. STATION No. LSB LSB 020301E.ai HRDYDIP switches used for setting the Control Bus station address For domain number setting
For station number setting
Figure Bus Converter’s processor card
SEE ALSO Form and setting of the bus converter DIP switches are same as the processor unit.
For above, see the following:
2.2, “Processor Unit”
<2.4 HF Bus/RL Bus Interface Card>
2-9
2.4
HF Bus/RL Bus Interface Card
The HF Bus/RL bus interface card (FC311) enables communication between the VL net for the CENTUM CS 3000 system and the RL bus for the existing µXL.
n
Location of DIP switch on FC311
This DIP switch on FC311 is set station number or unit number on lower system. RDY
CTRL
020401E.ai
DIP switches for setting the station no. or the unit no.
<2.4 HF Bus/RL Bus Interface Card>
2-10
IM 33M01A20-40E
n
Setting the Station Number for FC311
Set the station number in the range of 1 to 32.
Set the DIP switches as shown in the following table to set the necessary station number.
1 3 4 5 6 7 8 2 020402E.ai ODD PARITY (LSB) 0 1 1 STA NO. (MSB)
MSB: Most Significant Bit LSB: Least Significant Bit
Parity of the station number (1 bit, odd parity) Always 1 Station number Figure DIP Switches for Station Number Setting Table Station Numbers and Switch Positions Staition number Staition number 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 Bit 1 1 1 0 1 0 0 1 1 0 0 1 0 1 1 0 1 Bit 2 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Bit 3 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Bit 4 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1 Bit 5 0 0 0 0 0 0 0 1 1 1 1 1 1 1 1 0 Bit 6 0 0 0 1 1 1 1 0 0 0 0 1 1 1 1 0 Bit 7 0 1 1 0 0 1 1 0 0 1 1 0 0 1 1 0 Bit 8 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 17 18 19 20 21 Bit 1 0 0 1 0 1 Bit 2 1 1 1 1 1 Bit 3 0 0 0 0 0 Bit 4 1 1 1 1 1 Bit 5 0 0 0 0 0 Bit 6 0 0 0 1 1 Bit 7 0 1 1 0 0 Bit 8 1 0 1 0 1 22 1 1 0 1 0 1 1 0 23 0 1 0 1 0 1 1 1 24 0 1 0 1 1 0 0 0 25 1 1 0 1 1 0 0 1 26 1 1 0 1 1 0 1 0 27 0 1 0 1 1 0 1 1 28 1 1 0 1 1 1 0 0 29 0 1 0 1 1 1 0 1 30 0 1 0 1 1 1 1 0 31 1 1 0 1 1 1 1 1 32 1 1 1 0 0 0 0 0 020403E.ai
Note: Setting of the DIP switch
0: The switch is flipped to the left in the diagram above. 1: The switch is flipped to the right in the diagram above.
n
Setting the Unit Number for FC311
Set the unit number in the range of 1 to 21.
Setting DIP switches and unit number is same as station number for FC311.
<2.5 V net Interface Card>
2-11
2.5
V net Interface Card
The V net interface card is used to connect a V net or VL net of a domain differing from the domain for a V net connected to the master side, in order to perform communication. The following systems can be connected in the combination described: • CENTUM VP V net and another CENTUM VP V net • CENTUM VP V net and a CS 3000 V net• CENTUM VP V net and a CENTUM CS V net • CENTUM VP V net and a CS 1000 VL net
n
Location of DIP Switch on VF311
DIP switches for setting the V Net station address
020501E.ai
For domain number setting For station number setting
<2.5 V net Interface Card>
2-12
IM 33M01A20-40E
n
Settings for the V net Station Address Switches
Specify the station address set on the V net interface card using the same domain number and station number of the slave domain side.
With a dual-redundant converter, set the same numbers for the V net interface cards on both sides.
l
Setting the Domain Number (Upper DIP Switch)
Set the domain number for the slave side in the range between 1 and 16. The setting procedure is the same as for the processor unit.
SEE
ALSO For the domain number setting, see the following:
“n Setting the Domain Number” in 2.2, “Processor Unit”
l
Setting the Station Number (Lower DIP Switch)
Set the station number for the slave side in the range between 1 and 64. If the CS 1000 is in slave side, the range of station number is 1 to 24. The setting procedure is the same as for the processor unit.
SEE ALSO For the station number setting, see the following:
“n Setting the Station Number” in 2.2, “Processor Unit”
<2.6 Communication Gateway Unit>
2-13
2.6
Communication Gateway Unit
This section discribes setting dipswitches on ACG10S.n
Location of DIP Switches on ACG10S
020601E.ai Station number setting DIP switches Domain numbersetting DIP switches
<2.6 Communication Gateway Unit>
2-14
IM 33M01A20-40E
n
Setting the Domain Number for ACG10S
One Control Bus system requires one domain number.
The domain number can be set in a range of 1 to 16 by turning the domain number DIP switch bits as shown below. Bits 2 and 3 must always be 0.
1
0 1 2 3 4 5 6 7 8
DOMAIN NO.
P (odd parity): Set in such a way that, of the 8 dip switches,
the sum of those switches set to 1 becomes an odd number.
MSB: Most Significant Bit
LSB: Least Significant Bit
020602E.ai
(MSB)(LSB) P 0 0
Domain number (5 bits) Fixed to 0 (2 bits)
Parity of the domain number (1 bit) (odd parity)
Figure Domain Number Setting DIP Switch Table Domain Number & DIP Switch Bit Positions
1 2 DIP switch bit number3 4 5 6 7 8
0 0 0 0 0 0 0 1 0 0 0 0 0 0 1 0 1 0 0 0 0 0 1 1 0 0 0 0 0 1 0 0 1 0 0 0 0 1 0 1 1 0 0 0 0 1 1 0 0 0 0 0 0 1 1 1 0 0 0 0 1 0 0 0 1 0 0 0 1 0 0 1 1 0 0 0 1 0 1 0 0 0 0 0 1 0 1 1 1 0 0 0 1 1 0 0 0 0 0 0 1 1 0 1 0 0 0 0 1 1 1 0 1 0 0 0 1 1 1 1 Domain number 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 0 0 0 1 0 0 0 0 020603E.ai Bit setting: 0: Turn the switch to the down side in the above figure. 1: Turn the switch to the up side in the above figure. 1st Edition : Mar.23,2008-00
<2.6 Communication Gateway Unit>
2-15
n
Setting the Station Number
Set station numbers in a range of 1 to 64 successively by turning the station number DIP switch bits as shown below:
1
0 1 2 3 4 5 6 7 8
P
STATION NO.
P (odd parity): Set in such a way that, of the 8 dip switches,
the sum of those switches set to 1 becomes an odd number.
MSB: Most Significant Bit
LSB: Least Significant Bit
020604E.ai
(MSB) (LSB)
Station number (7 bits)
Parity of the station number (1 bits) (odd parity) Figure Station Number Setting DIP Switch Table Station Number & DIP Switch Bit Positions Station No. 1
1 2 3DIP Switch Bit No.4 5 6 7 8
0 0 0 0 0 0 0 1 2 0 0 0 0 0 0 1 0 3 1 0 0 0 0 0 1 1 4 0 0 0 0 0 1 0 0 5 1 0 0 0 0 1 0 1 6 1 0 0 0 0 1 1 0 7 0 0 0 0 0 1 1 1 8 0 0 0 0 1 0 0 0 9 1 0 0 0 1 0 0 1 10 1 0 0 0 1 0 1 0 11 0 0 0 0 1 0 1 1 12 1 0 0 0 1 1 0 0 13 0 0 0 0 1 1 0 1 14 0 0 0 0 1 1 1 0 15 1 0 0 0 1 1 1 1 16 0 0 0 1 0 0 0 0 Station No. 17
1 2 3DIP Switch Bit No.4 5 6 7 8
1 0 0 1 0 0 0 1 18 1 0 0 1 0 0 1 0 30 1 0 0 1 1 1 1 0 31 0 0 0 1 1 1 1 1 32 0 0 1 0 0 0 0 0 33 1 0 1 0 0 0 0 1 60 1 0 1 1 1 1 0 0 61 0 0 1 1 1 1 0 1 62 0 0 1 1 1 1 1 0 63 1 0 1 1 1 1 1 1 64 0 1 0 0 0 0 0 0 020605E.ai ... ... ... ... ... ... ... ... ... Bit setting: 0: Turn the switch to the down side in the above figure. 1: Turn the switch to the up side in the above figure.
<2.7 Installing Ethernet Card>
2-16
IM 33M01A20-40E2.7
Installing Ethernet Card
Before installing software, reconfirm that these settings are correct. Check that the Ethernet card are properly installed in a PC.n
Ethernet Card
The Ethernet is required when a network other than the Control Bus is connected.
Confirm that the Ethernet card is properly inserted and connected to the network via the proper cable.
SEE ALSO Refer to the network adapter manual for details.
<2.8 Setup Vnet/IP Station Address On Control Bus>
2-17
2.8
Setup Vnet/IP Station Address On Control
Bus
The dipswitches for setting the Vnet/IP station address can be found on Vnet/IP Interface Card (VI701). The station address needs to be set before installing the CENTUM VP software. How to setup the station address is explained below.n
Location of VI701 DIP switches
The address on the control bus consists of domain number and station number.
On the printed circuit board of VI701 card, the DIP switches for domain and station numbers are located. 020801E.ai DIP switch Station No. Domain No. DOMAIN STATION SW1 SW2 SW4 Action mode Figure Location of VI701 DIP switches
<2.8 Setup Vnet/IP Station Address On Control Bus>
2-18
IM 33M01A20-40E
n
Setup VI701 Domain Number
Set it to 1 for a single network system.
Unless other specified, all bits are set to 0 (OFF) at shipment from the factory.
Domain is a range of stations connected by a single Vnet/IP. Set the domain number in the range of 1 to 16. Set the DIP switches as shown in the following table to set the necessary domain number.
Bit 2 of the DIP switch are always 0.
020802E.ai
LSB MSB
1 0
MSB : Most Significant Bit (highest-order bit) LSB : Least Significant Bit (lowest order bit) P 0
Domain number Fixed to 0
Domain number parity (1 bit, odd parity)
2
1 3 4 5 6 7 8 Bit number
(An example where the address “Domain Number” 6) Figure DIP Switches for Domain Number Setting Table Domain Numbers and Switch Positions Domain number 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 Bit 1 0 0 1 0 1 1 0 0 1 1 0 1 0 0 1 0 Bit 2 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Bit 3 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Bit 4 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1 Bit 5 0 0 0 0 0 0 0 1 1 1 1 1 1 1 1 0 Bit 6 0 0 0 1 1 1 1 0 0 0 0 1 1 1 1 0 Bit 7 0 1 1 0 0 1 1 0 0 1 1 0 0 1 1 0 Bit 8 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 020803E.ai Setting of the DIP switch
0: The switch is flipped down in the diagram above. 1: The switch is flipped up in the diagram above.
<2.8 Setup Vnet/IP Station Address On Control Bus>
2-19
n
Setup VI701 Station Number
Set the station number in the range of 1 to 64. Set the DIP switches as shown in the following table to set the necessary station number.
020804E.ai 1 0 2 1 3 4 5 6 7 8 P LSB Station number MSB : Most Significant Bit (highest-order bit) LSB : Least Significant Bit (lowest-order bit)
Station number parity (1 bit, odd parity)
Bit number
(An example where the address “Station Number” 60) MSB Figure DIP Switches for Station Number Setting Table Station Numbers and Switch Positions Station number 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 Bit 1 0 0 1 0 1 1 0 0 1 1 0 1 0 0 1 0 Bit 2 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Bit 3 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Bit 4 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1 Bit 5 0 0 0 0 0 0 0 1 1 1 1 1 1 1 1 0 Bit 6 0 0 0 1 1 1 1 0 0 0 0 1 1 1 1 0 Bit 7 0 1 1 0 0 1 1 0 0 1 1 0 0 1 1 0 Bit 8 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 Station number 17 18 30 31 32 33 60 61 62 63 64 Bit 1 1 1 1 0 0 1 1 0 0 1 0 Bit 2 0 0 0 0 0 0 0 0 0 0 1 Bit 3 0 0 0 0 1 1 1 1 1 1 0 Bit 4 1 1 1 1 0 0 1 1 1 1 0 Bit 5 0 0 1 1 0 0 1 1 1 1 0 Bit 6 0 0 1 1 0 0 1 1 1 1 0 Bit 7 0 1 1 1 0 0 0 0 1 1 0 Bit 8 1 0 0 1 0 1 0 1 0 1 0 020805E.ai Setting of the DIP switch
0: The switch is flipped down in the diagram above. 1: The switch is flipped up in the diagram above.
<2.9 Setup Vnet/IP Station Address On Processor Module>
2-20
IM 33M01A20-40E2.9
Setup Vnet/IP Station Address On
Processor Module
The following processor modules support Vnet/IP • CP451 How to setup the station address on processor module is explained below.n
Location of Processor Module Dipswitches
020901E.aiVnet/IP station address setting switch
For domain number For station number
DO MA IN NO . STA TIO N N O. P 1 0 0 MS B -LS B P MS B -LS B Figure Rear Part of Processor Module (CP451) 1st Edition : Mar.23,2008-00
<2.9 Setup Vnet/IP Station Address On Processor Module>
2-21
n
Setup Processor Module Domain Number
A domain stands for a range of stations connected by a single train of the Vnet/IP. Set the domain number to a value from 1 to 16.
To set a domain number, set the dip switches as follows. Bits 2 must always be zero.
020902E.ai P 0 MSB LSB Domain number 0 1 Fixed to 0
Parity of the domain number (1 bit, odd parity)
MSB : Most Significant Bit (highest-order bit) LSB : Least Significant Bit (lowest-order bit)
Bit number 6 5 4 3 2 1 7 8 Figure Domain Number Setting Switches Table Domain Number and Dip Switch Positions Domain number 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 Bit 1 0 0 1 0 1 1 0 0 1 1 0 1 0 0 1 0 Bit 2 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Bit 3 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Bit 4 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1 Bit 5 0 0 0 0 0 0 0 1 1 1 1 1 1 1 1 0 Bit 6 0 0 0 1 1 1 1 0 0 0 0 1 1 1 1 0 Bit 7 0 1 1 0 0 1 1 0 0 1 1 0 0 1 1 0 Bit 8 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 020903E.ai Setting DIP switches
0: From the state shown in the above figure, the switch is tilted toward left. 1: From the state shown in the above figure, the switch is tilted toward right.
<2.9 Setup Vnet/IP Station Address On Processor Module>
2-22
IM 33M01A20-40E
n
Setup Processor Module Station Number
Set the station number to a value from 1 to 64. To set a station number, set the dip switches as follows.
020904E.ai
Station number
Station number parity (1 bit, odd parity)
MSB : Most Significant Bit (highest-order bit) LSB : Least Significant Bit (lowest-order bit)
Bit number P MSB LSB 0 1 6 5 4 3 2 1 7 8 Figure Station Number Setting Switches Table Station Number and Dip Switch Positions Station number 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 Bit 1 0 0 1 0 1 1 0 0 1 1 0 1 0 0 1 0 Bit 2 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Bit 3 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Bit 4 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1 Bit 5 0 0 0 0 0 0 0 1 1 1 1 1 1 1 1 0 Bit 6 0 0 0 1 1 1 1 0 0 0 0 1 1 1 1 0 Bit 7 0 1 1 0 0 1 1 0 0 1 1 0 0 1 1 0 Bit 8 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 Station number 17 18 30 31 32 33 60 61 62 63 64 Bit 1 1 1 1 0 0 1 1 0 0 1 0 Bit 2 0 0 0 0 0 0 0 0 0 0 1 Bit 3 0 0 0 0 1 1 1 1 1 1 0 Bit 4 1 1 1 1 0 0 1 1 1 1 0 Bit 5 0 0 1 1 0 0 1 1 1 1 0 Bit 6 0 0 1 1 0 0 1 1 1 1 0 Bit 7 0 1 1 1 0 0 0 0 1 1 0 Bit 8 1 0 0 1 0 1 0 1 0 1 0 020905E.ai Setting DIP switches
0: From the state shown in the above figure, the switch is tilted toward left. 1: From the state shown in the above figure, the switch is tilted toward right.
<2.10 Setup V net Router Addresses>
2-23
2.10 Setup V net Router Addresses
The V net Router (AVR10D) is used for handling the communications among the different domains on CENTUM VP system Vnet/IP networks, (CENTUM VP systems, CENTUM CS 3000 systems, CENTUM CS systems) V net networks, CENTUM CS 1000 system VLnet networks, as well as the communications between the station on Vnet/IP networks and the stations on V net or VL net networks. How to setup dipswitches on the communication module of the V net Router is explained below.n
Location of V net Router Dipswitches
021001E.ai 0 0 0 1 0 1 PARITY (MSB) DOMAIN (LSB) PARITY (MSB) STATION (LSB) VI451 HRDY RDYCTRL V NetADDRESS VNET/IPADDRESS
VNET/IP NORM MNT MODE RCV BUS1 SND RCV BUS2 SND
Dipswitches for address in V net domain
Dipswitches for address in Vnet/IP domain
Vnet/IP BUS1 connector Vnet/IP BUS2 connector
Mode switch
LED display
0
<2.10 Setup V net Router Addresses >
2-24
IM 33M01A20-40E
n
Setup V net Router Domain Number
A domain stands for a range of stations connected by a single train of the V net or Vnet/IP. Set the domain number to a value from 1 to 16.
To set a domain number, set the dip switches as follows.
As shown in the figures below, the 8-bit dip switches are numbered. Each bit corresponds to a number, from 1 to 8.
For V net domain, the bit 2 and bit 3 are always off. For Vnet/IP domain, the bit 2 is always off.
021002E.ai PARITY 0 0 MSB LSB Domain number 0 1 Fixed to 0
Domain number parity (1 bit, odd parity)
MSB : Most Significant Bit (highest-order bit) LSB : Least Significant Bit (lowest order bit)
0 1
DOMAIN V net
ADDRESS Vnet/IPADDRESS
0 MSB LSB 6 5 4 3 2 1 7 8 Figure Domain Number Setting Switches Table Domain Number and Dip Switch Positions Domain number 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 Bit 1 0 0 1 0 1 1 0 0 1 1 0 1 0 0 1 0 Bit 2 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Bit 3 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Bit 4 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1 Bit 5 0 0 0 0 0 0 0 1 1 1 1 1 1 1 1 0 Bit 6 0 0 0 1 1 1 1 0 0 0 0 1 1 1 1 0 Bit 7 0 1 1 0 0 1 1 0 0 1 1 0 0 1 1 0 Bit 8 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 021003E.ai Setting DIP switches
0: From the state shown in the above figure, the switch is tilted toward left. 1: From the state shown in the above figure, the switch is tilted toward right.
<2.10 Setup V net Router Addresses>
2-25
n
Setup V net Router Station Number
Set the station number to a value from 1 to 64. To set a station number, set the dip switches as follows.
021004E.ai
Station number
Station number parity (1 bit, odd parity)
MSB : Most Significant Bit (highest-order bit) LSB : Least Significant Bit (lowest-order bit)
6 5 4 3 2 1 7 8 PARITY MSB LSB 0 1 0 1 STATION V net
ADDRESS Vnet/IPADDRESS
Figure Station Number Setting Switches Table Station Number and Dip Switch Positions Station number 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 Bit 1 0 0 1 0 1 1 0 0 1 1 0 1 0 0 1 0 Bit 2 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Bit 3 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Bit 4 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1 Bit 5 0 0 0 0 0 0 0 1 1 1 1 1 1 1 1 0 Bit 6 0 0 0 1 1 1 1 0 0 0 0 1 1 1 1 0 Bit 7 0 1 1 0 0 1 1 0 0 1 1 0 0 1 1 0 Bit 8 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 Station number 17 18 30 31 32 33 60 61 62 63 64 Bit 1 1 1 1 0 0 1 1 0 0 1 0 Bit 2 0 0 0 0 0 0 0 0 0 0 1 Bit 3 0 0 0 0 1 1 1 1 1 1 0 Bit 4 1 1 1 1 0 0 1 1 1 1 0 Bit 5 0 0 1 1 0 0 1 1 1 1 0 Bit 6 0 0 1 1 0 0 1 1 1 1 0 Bit 7 0 1 1 1 0 0 0 0 1 1 0 Bit 8 1 0 0 1 0 1 0 1 0 1 0 021005E.ai Setting DIP switches
0: From the state shown in the above figure, the switch is tilted toward left. 1: From the state shown in the above figure, the switch is tilted toward right.
<3. Setting of Windows>
3-1
3.
Setting of Windows
The Windows settings need to be defined before installing CENTUM VP Software to the PC are described as follows. After installing Windows operating system, service packs and all the required security patches, do the following. The procedure explained below is based on the Classic style of Windows Vista Control Panel.<3.1 File System>
3-2
IM 33M01A20-40E3.1
File System
The file system of the disk partitions should be NTFS. If the partition of operating system is already formatted to FAT, it is necessary to convert it into NTFS and then reinstall the operating system. Other partitions should also be formatted into NTFS. 1st Edition : Mar.23,2008-00<3.2 Setting of Virtual Memory>
3-3
3.2
Setting of Virtual Memory
Set the Virtual memory by Custom size. The setting method is shown as follows. 1. Logon as an administrative user.
2. Choose [Control Panel] - [System] from [Start] menu so as to display System settings.
030201E.ai
Figure System
3. Choose [Advanced system settings] so as to open [System Properties], on [Advanced] tab, click [Settings] button of [Performance] so as to display [Performance Options].
030202E.ai
<3.2 Setting of Virtual Memory>
3-4
IM 33M01A20-40E
4. On [Advanced] tab of [Performance Options], click [Change] button of [Virtual memory] so as to display the [Virtual Memory] dialog box.
030203E.ai
Figure Virtual Memory
5. The paging file size of the selected drive can be defined as follows:
Choose [Custom size] and then enter the sizes for [Initial size] and [Maximum size].
A size that is three times of main memory size is recommended for the initial size. However, 4096MB is the upper limit. For an example, if the main memory size is 1GB, the initial size can be defined with 3072MB. However, if the main memory size is 2GB or 4GB, 4096MB should be used.
6. Click [OK] button.
<3.3 Set Display Properties>
3-5
3.3
Set Display Properties
How to set the display properties will be explained below.
n
For Windows Vista
1. Logon using the administrative user account that used for installation.
2. Choose [Control Panel] - [Personalization] - [Window Color and Appearance] from [Start] menu so as to display [Window Color and Appearance].
030301E.ai
<3.3 Set Display Properties>
3-6
IM 33M01A20-40E
3. Choose the option of [Open classic appearance properties for more color options] at the lower part of the window so as to display [Appearance Settings] dialog box.
Choose [Windows Aero] for [Color scheme] and then click [OK] button.
030302E.ai
Figure Appearance Settings
<3.3 Set Display Properties>
3-7
4. Choose [Control Panel] - [Personalization] - [Desktop Background] from [Start] menu so as to display a window for selecting [Desktop Background].
Choose [Solid Colors] for [Location] and then click [OK] button.
030303E.ai
Figure Selecting Desktop Background
TIP In Windows Vista, when the background color is defined as a solid color or another color after the first logon,
the background color may revert to black at the second logon. If this problem occurs, you need to define the background color again with the same procedure.
<3.3 Set Display Properties>
3-8
IM 33M01A20-40E
5. Choose [Personalization] - [Screen Saver] so as to display “Screen Saver Settings” dialog box.
Choose (None) for [Screen saver] and then click [OK] button.
030304E.ai
FigureScreen Saver Settings dialog
6. Choose [Personalization] - [Display Settings] so as to display “Display Settings” dialog box. Set the following settings and then click [OK] button.
• Colors : “Highest (32 bit)”
• Resolution : SXGA 1280 by 1024 pixels WXGA 1680 by 1050 pixels
030305E.ai
Figure Display Settings dialog
<3.3 Set Display Properties>
3-9
n
For Windows XP/Windows Server 2003
1. Logon as an administrative user.
2. Choose [Control Panel] - [Display] from [Start] menu so as to display [Display Properties]. 3. On [Desktop] tab, choose [None] for [Background].
030306E.ai
Figure Display Properties (Desktop Tab)
4. On [Screen Saver] tab, choose [None] for [Screen Saver].
030307E.ai